N2XSEKY

Cu / XLPE / CTS / PVC / LS / PVC
3.6/6 kV IEC 60502-2

Deskripsi

Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed

Aplikasi

  • For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and mechanical damage is not likely to occur

Susunan lapisan N2XSEKY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC / LS / PVC.

Penampang konstruksi kabel N2XSEKY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  5. 5

    Selubung timah (lead sheath)

    Lead sheath

    Kedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.

  6. 6

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XSEKY.

Spesifikasi Teknis

N2XSEKY 3 x (25-300) mm² 3.6/6 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 40.0 3,806
35 43.0 4,495
50 46.0 5,306
70 50.5 6,520
95 54.5 7,887
120 58.5 9,259
150 62.0 10,708
185 66.0 12,470
240 72.5 15,194
300 79.5 18,433
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.342 152 146 3.58 1.03
35 0.524 0.668 0.325 185 175 5.01 1.03
50 0.387 0.494 0.313 220 205 7.15 1.03
70 0.268 0.342 0.296 274 251 10.01 1.03
95 0.193 0.247 0.285 332 299 13.59 1.03
120 0.153 0.196 0.276 381 339 17.16 1.03
150 0.124 0.160 0.268 433 380 21.45 1.03
185 0.0991 0.128 0.262 494 428 26.46 1.03
240 0.0754 0.099 0.255 579 493 34.32 1.37
300 0.0601 0.080 0.252 656 551 42.90 1.37

N2XSEKY 3 x (25-300) mm2 6/10 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 45.0 4,627
35 48.0 5,265
50 50.5 6,056
70 55.0 7,351
95 59.0 8,826
120 63.0 10,177
150 66.5 11,677
185 70.5 13,493
240 77.0 16,300
300 82.5 19,324
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.368 155 146 3.58 1.03
35 0.524 0.668 0.349 187 174 5.01 1.03
50 0.387 0.494 0.335 223 205 7.15 1.03
70 0.268 0.342 0.316 277 251 10.01 1.03
95 0.193 0.247 0.303 334 299 13.59 1.03
120 0.153 0.196 0.293 385 339 17.16 1.03
150 0.124 0.160 0.284 436 380 21.45 1.03
185 0.0991 0.128 0.277 497 428 26.46 1.37
240 0.0754 0.099 0.267 580 492 34.32 1.37
300 0.0601 0.080 0.261 658 551 42.90 1.37

N2XSEKY 3 x (25-300) mm² 8.7/15 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 50.5 5,566
35 53.5 6,361
50 56.5 7,209
70 61.0 8,669
95 65.0 10,144
120 68.5 11,353
150 72.0 12,915
185 76.5 14,896
240 82.5 17,956
300 88.0 20,818
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.395 157 146 3.58 1.03
35 0.524 0.668 0.374 190 174 5.01 1.03
50 0.387 0.494 0.359 226 205 7.15 1.03
70 0.268 0.342 0.338 279 250 10.01 1.03
95 0.193 0.247 0.324 338 299 13.59 1.03
120 0.153 0.196 0.312 387 339 17.16 1.03
150 0.124 0.159 0.302 439 380 21.45 1.37
185 0.0991 0.128 0.294 498 427 26.46 1.37
240 0.0754 0.098 0.283 582 491 34.32 1.37
300 0.0601 0.080 0.275 660 550 42.90 1.37

N2XSEKY 3 x (35-300) mm² 12/20 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
35 59.0 7,395
50 62.0 8,291
70 66.0 9,710
95 70.0 11,241
120 74.0 12,754
150 78.0 14,489
185 82.0 16,447
240 88.0 19,346
300 93.0 22,242
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
35 0.524 0.668 0.395 191 174 5.01 1.03
50 0.387 0.494 0.379 227 205 7.15 1.03
70 0.268 0.342 0.357 282 250 10.01 1.03
95 0.193 0.247 0.341 340 299 13.59 1.37
120 0.153 0.196 0.328 390 339 17.16 1.37
150 0.124 0.159 0.318 440 378 21.45 1.37
185 0.0991 0.128 0.308 500 426 26.46 1.37
240 0.0754 0.098 0.296 584 491 34.32 1.37
300 0.0601 0.079 0.287 662 550 42.90 1.37

N2XSEKY 3 x (50-300) mm² 18/30 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
50 74.5 11,207
70 79.0 12,891
95 83.0 14,575
120 86.5 16,208
150 90.5 18,033
185 94.5 20,146
240 100.5 23,254
300 106.0 26,810
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
50 0.387 0.494 0.421 230 204 7.15 1.37
70 0.268 0.342 0.396 284 249 10.01 1.37
95 0.193 0.247 0.378 342 297 13.59 1.37
120 0.153 0.196 0.364 392 337 17.16 1.37
150 0.124 0.159 0.351 443 377 21.45 1.37
185 0.0991 0.128 0.340 503 425 26.46 1.37
240 0.0754 0.098 0.326 586 489 34.32 1.37
300 0.0601 0.079 0.315 661 547 42.90 1.37

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.