PT. Hartaperindo Sejahtera — Distributor Resmi Kabelmetal Indonesia
182 tipe produk — spesifikasi resmi Kabelmetal Indonesia

N2XSKB(AL)Y

Cu / XLPE/ CTS / PVC / LS / PVC / DATA / PVC
3.6/6 kV IEC 60502-2

Deskripsi

Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Double Aluminium Tape Armor, PVC Sheathed

Aplikasi

  • For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and low mechanical damage may occur

Susunan lapisan N2XSKB(AL)Y dari dalam ke luar — sesuai kode konstruksi Cu / XLPE/ CTS / PVC / LS / PVC / DATA / PVC.

Penampang konstruksi kabel N2XSKB(AL)Y — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  5. 5

    Selubung timah (lead sheath)

    Lead sheath

    Kedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.

  6. 6

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  7. 7

    Perisai pita aluminium ganda (DATA)

    Double aluminium tape armour

    Dua lapis pita aluminium — perisai non-magnetik untuk kabel inti tunggal.

  8. 8

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XSKB(AL)Y.

Spesifikasi Teknis

N2XSKB(AL)Y 1 x (25-630) mm² 3.6/6 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 25.5 1,642
35 27.0 1,823
50 28.0 2,016
70 30.0 2,443
95 32.0 2,826
120 33.5 3,261
150 35.5 3,626
185 37.0 4,098
240 40.5 5,027
300 43.5 5,974
400 47.5 7,194
500 52.0 8,785
630 56.5 10,677
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.474 0.521 171 155 175 158 3.58 1.14
35 0.524 0.668 0.450 0.496 207 185 212 189 5.01 1.14
50 0.387 0.494 0.431 0.478 246 218 252 222 7.15 1.14
70 0.268 0.342 0.409 0.455 308 266 315 272 10.01 1.14
95 0.193 0.247 0.392 0.438 372 317 381 324 13.59 1.14
120 0.153 0.196 0.378 0.424 429 360 439 367 17.16 1.14
150 0.124 0.159 0.367 0.413 486 402 497 410 21.45 1.14
185 0.0991 0.128 0.355 0.401 555 453 566 460 26.46 1.14
240 0.0754 0.098 0.345 0.392 653 521 664 528 34.32 1.14
300 0.0601 0.079 0.339 0.385 744 584 754 590 42.90 1.14
400 0.0470 0.063 0.328 0.375 858 659 867 663 57.20 1.14
500 0.0366 0.050 0.322 0.368 980 737 985 737 71.50 1.14
630 0.0283 0.041 0.313 0.360 1111 818 1109 811 90.09 1.14

N2XSKB(AL)Y 1 x (25-630) mm² 6/10 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 27.5 1,815
35 29.0 2,012
50 30.0 2,291
70 32.0 2,648
95 34.0 3,116
120 35.5 3,447
150 37.5 3,940
185 39.5 4,496
240 42.5 5,390
300 44.5 6,068
400 48.5 7,329
500 52.5 8,869
630 56.5 10,742
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.488 0.535 172 154 176 157 3.58 1.14
35 0.524 0.668 0.465 0.511 208 184 213 188 5.01 1.14
50 0.387 0.494 0.447 0.493 248 217 254 222 7.15 1.14
70 0.268 0.342 0.422 0.468 309 265 316 271 10.01 1.14
95 0.193 0.247 0.405 0.451 375 317 383 323 13.59 1.14
120 0.153 0.196 0.390 0.436 430 359 439 365 17.16 1.14
150 0.124 0.159 0.378 0.424 489 402 499 409 21.45 1.14
185 0.0991 0.127 0.369 0.415 557 452 567 459 26.46 1.14
240 0.0754 0.098 0.356 0.403 654 520 665 527 34.32 1.14
300 0.0601 0.079 0.344 0.390 745 584 755 590 42.90 1.14
400 0.0470 0.063 0.333 0.379 858 658 867 662 57.20 1.14
500 0.0366 0.050 0.324 0.370 980 736 984 736 71.50 1.14
630 0.0283 0.041 0.315 0.361 1111 818 1109 811 90.09 1.14

N2XSKB(AL)Y 1 x (25-630) mm² 8.7/15 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 30.0 2,129
35 31.5 2,322
50 32.5 2,539
70 35.0 2,966
95 36.5 3,348
120 38.5 3,884
150 40.0 4,283
185 42.5 4,933
240 45.0 5,636
300 47.5 6,545
400 51.5 7,867
500 55.0 9,396
630 59.5 11,331
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.507 0.553 173 154 177 157 3.58 1.14
35 0.524 0.668 0.481 0.527 210 184 214 188 5.01 1.14
50 0.387 0.494 0.463 0.509 250 217 255 221 7.15 1.14
70 0.268 0.342 0.439 0.485 311 265 317 270 10.01 1.14
95 0.193 0.247 0.419 0.465 375 316 383 322 13.59 1.14
120 0.153 0.196 0.407 0.453 432 358 440 364 17.16 1.14
150 0.124 0.159 0.393 0.439 490 401 499 407 21.45 1.14
185 0.0991 0.127 0.383 0.429 559 451 568 458 26.46 1.14
240 0.0754 0.098 0.367 0.413 655 520 665 526 34.32 1.14
300 0.0601 0.079 0.356 0.403 746 583 755 588 42.90 1.14
400 0.0470 0.062 0.344 0.391 859 657 866 660 57.20 1.14
500 0.0366 0.050 0.334 0.380 981 736 984 734 71.50 1.14
630 0.0283 0.040 0.325 0.371 1111 817 1107 809 90.09 1.14

N2XSKB(AL)Y 1 x (35-630) mm² 12/20 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
35 34.0 2,647
50 35.0 2,837
70 37.0 3,301
95 39.0 3,766
120 41.0 4,151
150 43.0 4,698
185 44.5 5,131
240 47.5 6,066
300 50.0 6,998
400 54.0 8,219
500 57.5 9,743
630 62.0 11,700
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
35 0.524 0.668 0.496 0.543 211 184 216 188 5.01 1.14
50 0.387 0.494 0.478 0.524 251 216 256 220 7.15 1.14
70 0.268 0.342 0.451 0.497 312 264 318 270 10.01 1.14
95 0.193 0.247 0.434 0.481 377 315 384 321 13.59 1.14
120 0.153 0.196 0.418 0.465 433 357 441 363 17.16 1.14
150 0.124 0.159 0.406 0.452 491 400 500 406 21.45 1.14
185 0.0991 0.127 0.391 0.438 559 450 569 457 26.46 1.14
240 0.0754 0.098 0.378 0.424 656 519 666 525 34.32 1.14
300 0.0601 0.078 0.367 0.413 747 582 756 587 42.90 1.14
400 0.0470 0.062 0.354 0.400 859 656 865 659 57.20 1.14
500 0.0366 0.050 0.342 0.388 981 735 984 733 71.50 1.14
630 0.0283 0.040 0.332 0.379 1111 816 1107 808 90.09 1.14

N2XSKB(AL)Y 1 x (50-630) mm² 18/30 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
50 41.5 3,774
70 43.5 4,161
95 45.0 4,525
120 47.0 5,064
150 48.5 5,511
185 51.0 6,247
240 53.5 7,089
300 56.5 8,071
400 60.0 9,445
500 63.5 11,040
630 68.0 13,139
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
50 0.387 0.494 0.512 0.559 253 215 258 219 7.15 1.14
70 0.268 0.342 0.483 0.529 314 263 320 268 10.01 1.14
95 0.193 0.247 0.462 0.508 378 314 385 319 13.59 1.14
120 0.153 0.196 0.446 0.492 435 356 442 362 17.16 1.14
150 0.124 0.159 0.431 0.477 492 399 500 405 21.45 1.14
185 0.0991 0.127 0.419 0.465 560 448 569 454 26.46 1.14
240 0.0754 0.097 0.403 0.449 656 517 664 522 34.32 1.14
300 0.0601 0.078 0.391 0.437 746 579 753 583 42.90 1.14
400 0.0470 0.062 0.375 0.422 858 654 863 654 57.20 1.14
500 0.0366 0.050 0.362 0.408 979 732 980 728 71.50 1.14
630 0.0283 0.040 0.352 0.398 1108 813 1101 802 90.09 1.14

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.