PT. Hartaperindo Sejahtera — Distributor Resmi Kabelmetal Indonesia
182 tipe produk — spesifikasi resmi Kabelmetal Indonesia

N2XSKR(AL)Y

Cu / XLPE/ CTS / PVC / LS / PVC / AWA / PVC
3.6/6 kV IEC 60502-2

Deskripsi

Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Aluminium Wire Armor, PVC Sheathed

Aplikasi

  • For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation

Susunan lapisan N2XSKR(AL)Y dari dalam ke luar — sesuai kode konstruksi Cu / XLPE/ CTS / PVC / LS / PVC / AWA / PVC.

Penampang konstruksi kabel N2XSKR(AL)Y — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  5. 5

    Selubung timah (lead sheath)

    Lead sheath

    Kedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.

  6. 6

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  7. 7

    Perisai kawat aluminium (AWA)

    Aluminium wire armour

    Perisai non-magnetik untuk kabel inti tunggal.

  8. 8

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XSKR(AL)Y.

Spesifikasi Teknis

N2XSKR(AL)Y 1 x (25-630) mm² 3.6/6 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 27.5 1,756
35 28.5 1,956
50 29.5 2,155
70 32.0 2,590
95 33.5 2,968
120 36.0 3,509
150 38.0 3,885
185 39.5 4,375
240 43.0 5,325
300 47.5 6,446
400 51.5 7,728
500 56.0 9,372
630 60.0 11,280
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.486 0.532 173 155 177 158 3.58 1.14
35 0.524 0.668 0.463 0.509 210 185 214 188 5.01 1.14
50 0.387 0.494 0.444 0.490 249 217 254 221 7.15 1.14
70 0.268 0.342 0.420 0.466 309 264 315 269 10.01 1.14
95 0.193 0.247 0.401 0.448 373 314 379 318 13.59 1.14
120 0.153 0.196 0.393 0.439 428 353 434 356 17.16 1.14
150 0.124 0.159 0.381 0.427 482 391 487 393 21.45 1.14
185 0.0991 0.127 0.368 0.414 545 436 548 437 26.46 1.14
240 0.0754 0.098 0.358 0.404 631 495 632 492 34.32 1.14
300 0.0601 0.079 0.356 0.402 706 539 703 532 42.90 1.14
400 0.0470 0.062 0.345 0.391 798 594 789 583 57.20 1.14
500 0.0366 0.050 0.337 0.383 892 649 877 633 71.50 1.14
630 0.0283 0.040 0.327 0.373 989 704 967 682 90.09 1.14

N2XSKR(AL)Y 1 x (25-630) mm² 6/10 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 29.5 1,950
35 30.5 2,140
50 32.0 2,437
70 34.5 2,884
95 36.5 3,362
120 38.0 3,713
150 40.0 4,215
185 42.0 4,788
240 45.0 5,706
300 48.5 6,570
400 52.5 7,852
500 56.5 9,431
630 60.5 11,343
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.501 0.547 174 154 178 157 3.58 1.14
35 0.524 0.668 0.475 0.521 210 184 215 188 5.01 1.14
50 0.387 0.494 0.459 0.505 250 217 255 221 7.15 1.14
7d0 0.268 0.342 0.438 0.484 312 263 317 267 10.01 1.14
95 0.193 0.247 0.419 0.465 376 312 381 316 13.59 1.14
120 0.153 0.196 0.404 0.450 428 351 433 354 17.16 1.14
150 0.124 0.159 0.391 0.437 483 391 488 393 21.45 1.14
185 0.0991 0.127 0.381 0.427 546 435 549 435 26.46 1.14
240 0.0754 0.098 0.368 0.414 632 493 632 490 34.32 1.14
300 0.0601 0.078 0.362 0.408 706 538 703 532 42.90 1.14
400 0.0470 0.062 0.348 0.394 799 594 790 583 57.20 1.14
500 0.0366 0.050 0.338 0.384 893 650 878 634 71.50 1.14
630 0.0283 0.040 0.328 0.374 990 705 969 683 90.09 1.14

N2XSKR(AL)Y 1 x (25-630) mm² 8.7/15 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 32.0 2,275
35 33.0 2,473
50 35.0 2,782
70 37.5 3,227
95 39.0 3,619
120 41.0 4,172
150 43.0 4,581
185 45.0 5,248
240 49.0 6,118
300 51.5 7,080
400 55.5 8,443
500 59.5 10,014
630 63.5 11,963
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.518 0.565 175 154 179 157 3.58 1.14
35 0.524 0.668 0.492 0.538 212 184 216 187 5.01 1.14
50 0.387 0.494 0.478 0.524 253 216 257 220 7.15 1.14
70 0.268 0.342 0.453 0.499 312 262 317 266 10.01 1.14
95 0.193 0.247 0.433 0.479 375 311 381 314 13.59 1.14
120 0.153 0.196 0.420 0.466 429 350 434 353 17.16 1.14
150 0.124 0.159 0.405 0.451 483 389 488 391 21.45 1.14
185 0.0991 0.127 0.394 0.441 547 433 550 433 26.46 1.14
240 0.0754 0.098 0.384 0.430 631 488 631 485 34.32 1.14
300 0.0601 0.078 0.373 0.419 707 537 704 531 42.90 1.14
400 0.0470 0.062 0.360 0.406 799 593 792 583 57.20 1.14
500 0.0366 0.050 0.348 0.394 894 649 881 634 71.50 1.14
630 0.0283 0.040 0.338 0.384 992 704 973 684 90.09 1.14

N2XSKR(AL)Y 1 x (35-630) mm² 12/20 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
35 36.5 2,893
50 37.5 3,097
70 39.5 3,577
95 42.0 4,052
120 43.5 4,454
150 45.5 5,012
185 48.5 5,635
240 51.5 6,601
300 54.0 7,528
400 58.0 8,829
500 61.5 10,382
630 65.5 12,366
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
35 0.524 0.668 0.511 0.557 214 184 218 187 5.01 1.14
50 0.387 0.494 0.492 0.538 253 215 258 219 7.15 1.14
70 0.268 0.342 0.465 0.511 313 262 318 266 10.01 1.14
95 0.193 0.247 0.447 0.493 376 310 381 313 13.59 1.14
120 0.153 0.196 0.431 0.477 429 349 434 352 17.16 1.14
150 0.124 0.159 0.417 0.464 484 388 488 390 21.45 1.14
185 0.0991 0.127 0.409 0.455 547 430 549 430 26.46 1.14
240 0.0754 0.097 0.394 0.441 631 487 632 484 34.32 1.14
300 0.0601 0.078 0.382 0.428 709 538 707 531 42.90 1.14
400 0.0470 0.062 0.368 0.415 799 592 792 582 57.20 1.14
500 0.0366 0.050 0.356 0.402 896 649 883 635 71.50 1.14
630 0.0283 0.040 0.345 0.391 994 704 975 685 90.09 1.14

N2XSKR(AL)Y 1 x (50-630) mm² 18/30 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
50 44.0 4,076
70 47.5 4,633
95 49.0 5,006
120 51.0 5,587
150 52.5 6,034
185 55.0 6,826
240 58.0 7,686
300 60.0 8,674
400 64.0 10,117
500 67.5 11,755
630 72.5 13,893
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
50 0.387 0.494 0.524 0.571 254 214 258 217 7.15 1.14
70 0.268 0.342 0.500 0.547 315 260 320 264 10.01 1.14
95 0.193 0.247 0.479 0.525 378 308 382 311 13.59 1.14
120 0.153 0.196 0.463 0.509 431 346 435 349 17.16 1.14
150 0.124 0.159 0.447 0.493 485 385 489 386 21.45 1.14
185 0.0991 0.127 0.435 0.481 547 428 549 428 26.46 1.14
240 0.0754 0.097 0.418 0.464 631 485 632 483 34.32 1.14
300 0.0601 0.078 0.404 0.450 709 535 707 530 42.90 1.14
400 0.0470 0.062 0.389 0.435 802 592 796 583 57.20 1.14
500 0.0366 0.049 0.375 0.421 899 649 889 636 71.50 1.14
630 0.0283 0.040 0.364 0.410 998 706 983 688 90.09 1.14

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.