NA2XKBY
Al / XLPE / LS / PVC / DATA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Lead Sheathed, Double Aluminium Tape Armor, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and low mechanical damage may occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XKBY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / LS / PVC / DATA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai pita aluminium ganda (DATA)
Double aluminium tape armourDua lapis pita aluminium — perisai non-magnetik untuk kabel inti tunggal.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XKB(AL)Y 1 x (16-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 22.0 | 1,042 |
| 25 | 22.0 | 1,044 |
| 35 | 21.5 | 1,051 |
| 50 | 23.0 | 1,155 |
| 70 | 25.0 | 1,351 |
| 95 | 26.5 | 1,528 |
| 120 | 28.5 | 1,763 |
| 150 | 30.5 | 2,038 |
| 185 | 33.5 | 2,410 |
| 240 | 37.0 | 2,933 |
| 300 | 39.5 | 3,335 |
| 400 | 45.5 | 4,340 |
| 500 | 49.0 | 4,990 |
| 630 | 54.0 | 6,012 |
| 800 | 59.5 | 7,208 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.91 | 2.449 | 0.471 | 0.517 | 98 | 92 | 100 | 94 | 1.50 |
| 25 | 1.20 | 1.539 | 0.431 | 0.478 | 128 | 119 | 131 | 122 | 2.35 |
| 35 | 0.868 | 1.113 | 0.397 | 0.444 | 155 | 143 | 159 | 147 | 3.29 |
| 50 | 0.641 | 0.822 | 0.372 | 0.418 | 187 | 170 | 192 | 174 | 4.70 |
| 70 | 0.443 | 0.568 | 0.353 | 0.399 | 235 | 208 | 241 | 213 | 6.58 |
| 95 | 0.320 | 0.411 | 0.338 | 0.384 | 285 | 248 | 293 | 254 | 8.93 |
| 120 | 0.253 | 0.325 | 0.331 | 0.377 | 329 | 282 | 337 | 288 | 11.28 |
| 150 | 0.206 | 0.265 | 0.321 | 0.367 | 377 | 316 | 386 | 322 | 14.10 |
| 185 | 0.164 | 0.211 | 0.316 | 0.362 | 435 | 357 | 445 | 363 | 17.39 |
| 240 | 0.125 | 0.161 | 0.307 | 0.353 | 516 | 412 | 526 | 418 | 22.56 |
| 300 | 0.100 | 0.130 | 0.301 | 0.347 | 589 | 462 | 599 | 467 | 28.20 |
| 400 | 0.0778 | 0.102 | 0.292 | 0.338 | 695 | 526 | 703 | 529 | 37.60 |
| 500 | 0.0605 | 0.080 | 0.290 | 0.336 | 793 | 591 | 797 | 589 | 47.00 |
| 630 | 0.0469 | 0.064 | 0.286 | 0.332 | 908 | 660 | 906 | 653 | 59.22 |
| 800 | 0.0367 | 0.051 | 0.283 | 0.329 | 1023 | 727 | 1012 | 713 | 75.20 |
NA2XKBY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 22.0 | 1,127 |
| 16 | 24.5 | 1,359 |
| 25 | 26.5 | 1,590 |
| 35 | 29.0 | 1,855 |
| 50 | 32.0 | 2,274 |
| 70 | 36.5 | 2,908 |
| 95 | 42.5 | 4,002 |
| 120 | 46.0 | 4,730 |
| 150 | 50.0 | 5,479 |
| 185 | 56.5 | 6,749 |
| 240 | 62.0 | 8,196 |
| 300 | 68.0 | 9,690 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 71 | 76 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 95 | 100 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 124 | 128 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 152 | 155 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 183 | 183 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 232 | 226 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 285 | 270 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 330 | 308 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 371 | 342 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 429 | 388 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 504 | 448 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 574 | 503 | 28.20 |
NA2XKBY 3 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 22.5 | 1,207 |
| 16 | 25.5 | 1,465 |
| 25 | 27.5 | 1,729 |
| 35 | 30.5 | 2,114 |
| 50 | 33.0 | 2,264 |
| 70 | 39.0 | 3,261 |
| 95 | 43.0 | 3,934 |
| 120 | 46.5 | 4,593 |
| 150 | 51.5 | 5,469 |
| 185 | 57.0 | 6,496 |
| 240 | 63.5 | 8,045 |
| 300 | 68.5 | 9,377 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 60 | 64 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 81 | 84 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 105 | 108 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 129 | 130 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 160 | 157 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 203 | 193 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 247 | 231 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 287 | 263 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 326 | 294 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 376 | 333 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 443 | 384 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 507 | 433 | 28.20 |
NA2XKBY 4 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 24.0 | 1,344 |
| 16 | 27.0 | 1,646 |
| 25 | 30.0 | 2,044 |
| 35 | 33.0 | 2,421 |
| 50 | 37.5 | 2,827 |
| 70 | 44.0 | 4,009 |
| 95 | 48.5 | 4,812 |
| 120 | 53.5 | 5,762 |
| 150 | 60.0 | 6,932 |
| 185 | 65.0 | 8,240 |
| 240 | 72.0 | 10,172 |
| 300 | 78.0 | 11,838 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 66 | 69 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 89 | 91 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 117 | 117 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 143 | 140 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 168 | 161 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 212 | 197 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 260 | 237 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 301 | 269 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 347 | 303 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 397 | 341 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 467 | 394 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 534 | 443 | 28.20 |
NA2XKBY 5 x (10-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 25.5 | 1,500 |
| 16 | 29.0 | 1,851 |
| 25 | 32.5 | 2,328 |
| 35 | 36.5 | 2,894 |
| 50 | 42.5 | 4,033 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 68 | 71 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 92 | 92 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 121 | 119 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 148 | 142 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 181 | 167 | 4.70 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NA2XKBY