NA2XKFGbY
Al / XLPE / LS / PVC / SFWA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where that is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation and operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XKFGbY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / LS / PVC / SFWA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat baja pipih (SFWA)
Steel flat-wire armourProteksi mekanis berat — penanaman langsung & tarikan panjang.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XKFGbY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 23.0 | 1,454 |
| 16 | 25.5 | 1,708 |
| 25 | 28.0 | 1,987 |
| 35 | 30.5 | 2,274 |
| 50 | 33.5 | 2,756 |
| 70 | 38.5 | 3,464 |
| 95 | 42.5 | 4,223 |
| 120 | 46.5 | 4,985 |
| 150 | 50.0 | 5,747 |
| 185 | 56.5 | 7,047 |
| 240 | 62.0 | 8,561 |
| 300 | 68.0 | 10,070 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 72 | 77 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 97 | 101 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 126 | 129 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 154 | 156 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 186 | 184 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 234 | 226 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 285 | 270 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 330 | 308 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 371 | 342 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 429 | 388 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 504 | 448 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 574 | 503 | 28.20 |
NA2XKFGbY 3 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 24.0 | 1,533 |
| 16 | 27.0 | 1,839 |
| 25 | 29.0 | 2,150 |
| 35 | 32.5 | 2,597 |
| 50 | 34.5 | 2,757 |
| 70 | 39.5 | 3,468 |
| 95 | 43.5 | 4,151 |
| 120 | 47.0 | 4,823 |
| 150 | 52.0 | 5,772 |
| 185 | 57.0 | 6,797 |
| 240 | 63.5 | 8,403 |
| 300 | 69.0 | 9,757 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 61 | 65 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 82 | 85 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 106 | 108 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 131 | 130 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 162 | 158 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 203 | 193 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 247 | 231 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 287 | 263 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 326 | 293 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 376 | 332 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 443 | 384 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 506 | 432 | 28.20 |
NA2XKFGbY 4 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 25.5 | 1,694 |
| 16 | 28.5 | 2,042 |
| 25 | 31.5 | 2,502 |
| 35 | 35.0 | 2,928 |
| 50 | 39.0 | 3,392 |
| 70 | 44.5 | 4,242 |
| 95 | 48.5 | 5,076 |
| 120 | 54.0 | 6,072 |
| 150 | 60.5 | 7,269 |
| 185 | 65.0 | 8,608 |
| 240 | 72.5 | 10,592 |
| 300 | 78.5 | 12,273 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 67 | 70 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 90 | 91 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 119 | 117 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 145 | 140 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 171 | 162 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 213 | 197 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 260 | 237 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 301 | 268 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 348 | 303 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 397 | 341 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 467 | 393 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 533 | 442 | 28.20 |
NA2XKFGbY 5 x (10-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 27.0 | 1,872 |
| 16 | 30.5 | 2,270 |
| 25 | 34.0 | 2,836 |
| 35 | 38.0 | 3,451 |
| 50 | 42.5 | 4,251 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 69 | 71 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 93 | 93 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 122 | 119 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 150 | 142 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 181 | 167 | 4.70 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NA2XKFGbY
Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.