NA2XKRY
Al / XLPE / LS / PVC / AWA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Lead Sheathed, Aluminium Wire Armor, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where that is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation and operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XKRY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / LS / PVC / AWA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat aluminium (AWA)
Aluminium wire armourPerisai non-magnetik untuk kabel inti tunggal.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XKR(AL)Y 1 x (16-800) mm² 0.6/1
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 23.0 | 1,102 |
| 25 | 23.0 | 1,104 |
| 35 | 23.0 | 1,132 |
| 50 | 24.0 | 1,217 |
| 70 | 26.5 | 1,456 |
| 95 | 28.0 | 1,642 |
| 120 | 30.0 | 1,885 |
| 150 | 32.5 | 2,189 |
| 185 | 35.0 | 2,572 |
| 240 | 39.5 | 3,206 |
| 300 | 42.5 | 3,622 |
| 400 | 48.0 | 4,672 |
| 500 | 53.0 | 5,518 |
| 630 | 58.0 | 6,591 |
| 800 | 63.0 | 7,847 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.91 | 2.449 | 0.481 | 0.527 | 99 | 92 | 102 | 95 | 1.50 |
| 25 | 1.20 | 1.539 | 0.441 | 0.487 | 130 | 120 | 133 | 123 | 2.35 |
| 35 | 0.868 | 1.113 | 0.409 | 0.455 | 157 | 144 | 161 | 147 | 3.29 |
| 50 | 0.641 | 0.822 | 0.381 | 0.427 | 190 | 171 | 195 | 175 | 4.70 |
| 70 | 0.443 | 0.568 | 0.365 | 0.411 | 239 | 209 | 245 | 214 | 6.58 |
| 95 | 0.320 | 0.411 | 0.349 | 0.395 | 290 | 249 | 297 | 254 | 8.93 |
| 120 | 0.253 | 0.325 | 0.342 | 0.388 | 334 | 282 | 342 | 287 | 11.28 |
| 150 | 0.206 | 0.265 | 0.332 | 0.378 | 382 | 315 | 390 | 321 | 14.10 |
| 185 | 0.164 | 0.211 | 0.326 | 0.373 | 438 | 355 | 447 | 360 | 17.39 |
| 240 | 0.125 | 0.161 | 0.320 | 0.366 | 518 | 407 | 525 | 410 | 22.56 |
| 300 | 0.100 | 0.130 | 0.314 | 0.360 | 588 | 454 | 593 | 455 | 28.20 |
| 400 | 0.0778 | 0.102 | 0.303 | 0.349 | 687 | 513 | 689 | 510 | 37.60 |
| 500 | 0.0605 | 0.080 | 0.306 | 0.352 | 773 | 563 | 769 | 556 | 47.00 |
| 630 | 0.0469 | 0.063 | 0.300 | 0.346 | 874 | 622 | 864 | 609 | 59.22 |
| 800 | 0.0367 | 0.051 | 0.296 | 0.342 | 973 | 677 | 957 | 660 | 75.20 |
NA2XKRY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 24.0 | 1,441 |
| 16 | 27.0 | 1,860 |
| 25 | 29.5 | 2,143 |
| 35 | 32.0 | 2,472 |
| 50 | 35.0 | 2,958 |
| 70 | 40.5 | 3,934 |
| 95 | 45.0 | 4,773 |
| 120 | 50.0 | 5,975 |
| 150 | 54.0 | 6,836 |
| 185 | 60.5 | 8,250 |
| 240 | 66.0 | 9,861 |
| 300 | 72.0 | 11,513 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 73 | 77 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 98 | 102 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 127 | 130 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 156 | 156 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 188 | 185 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 238 | 228 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 289 | 272 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 337 | 311 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 379 | 345 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 437 | 392 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 514 | 453 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 585 | 509 | 28.20 |
NA2XKRY 3 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 25.5 | 1,669 |
| 16 | 28.0 | 1,992 |
| 25 | 30.5 | 2,307 |
| 35 | 33.5 | 2,771 |
| 50 | 37.0 | 3,183 |
| 70 | 42.0 | 3,954 |
| 95 | 45.5 | 4,681 |
| 120 | 50.5 | 5,842 |
| 150 | 56.0 | 6,872 |
| 185 | 61.0 | 8,003 |
| 240 | 67.5 | 9,743 |
| 300 | 72.5 | 11,202 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 62 | 65 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 83 | 85 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 108 | 109 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 133 | 131 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 165 | 159 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 206 | 194 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 252 | 233 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 294 | 266 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 333 | 296 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 384 | 336 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 452 | 388 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 517 | 438 | 28.20 |
NA2XKRY 4 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 27.0 | 1,846 |
| 16 | 30.0 | 2,211 |
| 25 | 33.0 | 2,688 |
| 35 | 37.0 | 3,362 |
| 50 | 41.5 | 3,878 |
| 70 | 46.5 | 4,766 |
| 95 | 52.5 | 6,117 |
| 120 | 57.5 | 7,219 |
| 150 | 64.0 | 8,549 |
| 185 | 69.0 | 9,955 |
| 240 | 76.0 | 12,104 |
| 300 | 83.5 | 14,803 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 68 | 70 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 92 | 92 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 121 | 118 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 149 | 142 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 174 | 163 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 216 | 199 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 267 | 239 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 308 | 271 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 355 | 306 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 405 | 344 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 477 | 398 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 547 | 449 | 28.20 |
NA2XKRY 5 x (10-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 28.5 | 2,025 |
| 16 | 32.0 | 2,453 |
| 25 | 35.5 | 3,026 |
| 35 | 40.5 | 3,922 |
| 50 | 45.0 | 4,800 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 71 | 72 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 95 | 93 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 124 | 120 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 153 | 144 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 185 | 169 | 4.70 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.