NA2XKY

Al / XLPE / LS / PVC
0.6/1 kV IEC 60502-1

Deskripsi

Aluminium Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed

Aplikasi

  • For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and mechanical damage is not likely to occur

Susunan lapisan NA2XKY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / LS / PVC.

Penampang konstruksi kabel NA2XKY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor aluminium

    Aluminium conductor

    Penghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Selubung timah (lead sheath)

    Lead sheath

    Kedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.

  4. 4

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk NA2XKY.

Spesifikasi Teknis

NA2XKY 1 x (16-800) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 17.7 848
25 17.7 850
35 17.7 873
50 18.9 959
70 21.0 1,135
95 23.0 1,307
120 25.0 1,526
150 27.5 1,791
185 30.0 2,140
240 33.5 2,634
300 36.0 2,978
400 42.0 3,946
500 45.0 4,545
630 50.0 5,474
800 55.0 6,613
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
16 1.91 2.449 0.431 0.478 94 91 96 94 1.50
25 1.20 1.539 0.391 0.438 122 118 125 122 2.35
35 0.868 1.113 0.360 0.406 148 142 152 146 3.29
50 0.641 0.822 0.337 0.383 179 169 184 174 4.70
70 0.443 0.568 0.320 0.366 226 207 233 213 6.58
95 0.320 0.411 0.309 0.355 277 247 285 254 8.93
120 0.253 0.325 0.305 0.351 321 281 330 289 11.28
150 0.206 0.265 0.298 0.344 370 316 381 325 14.10
185 0.164 0.211 0.295 0.341 429 358 441 368 17.39
240 0.125 0.162 0.288 0.334 513 416 528 427 22.56
300 0.100 0.130 0.281 0.328 591 470 607 481 28.20
400 0.0778 0.102 0.276 0.322 705 540 723 552 37.60
500 0.0605 0.081 0.274 0.321 812 612 833 625 47.00
630 0.0469 0.064 0.270 0.316 944 694 965 706 59.22
800 0.0367 0.052 0.269 0.315 1079 776 1099 786 75.20

NA2XKY 2 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 19.7 954
16 22.5 1,163
25 24.5 1,374
35 27.0 1,616
50 30.0 1,995
70 34.5 2,571
95 38.5 3,233
120 42.5 3,865
150 46.0 4,500
185 52.0 5,611
240 57.5 6,916
300 63.0 8,255
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 70 77 0.94
16 1.91 2.449 0.236 95 101 1.50
25 1.20 1.539 0.242 123 129 2.35
35 0.868 1.113 0.234 151 156 3.29
50 0.641 0.822 0.232 183 185 4.70
70 0.443 0.568 0.229 232 228 6.58
95 0.320 0.411 0.224 283 272 8.93
120 0.253 0.325 0.223 329 310 11.28
150 0.206 0.265 0.225 372 346 14.10
185 0.164 0.211 0.225 433 394 17.39
240 0.125 0.162 0.223 510 456 22.56
300 0.100 0.130 0.222 584 514 28.20

NA2XKY 3 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 21.0 1,026
16 23.5 1,260
25 26.0 1,502
35 28.5 1,861
50 31.0 1,978
70 35.5 2,559
95 39.0 3,123
120 43.0 3,729
150 47.5 4,485
185 52.5 5,385
240 59.0 6,776
300 64.0 7,940
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 60 65 0.94
16 1.91 2.449 0.236 80 85 1.50
25 1.20 1.539 0.242 105 109 2.35
35 0.868 1.113 0.234 129 131 3.29
50 0.641 0.822 0.232 160 159 4.70
70 0.443 0.568 0.229 201 195 6.58
95 0.320 0.411 0.224 247 233 8.93
120 0.253 0.325 0.223 286 266 11.28
150 0.206 0.265 0.225 327 297 14.10
185 0.164 0.211 0.225 379 337 17.39
240 0.125 0.162 0.223 449 391 22.56
300 0.100 0.130 0.222 517 442 28.20

NA2XKY 4 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 22.5 1,150
16 25.5 1,424
25 28.0 1,797
35 31.0 2,131
50 35.5 2,484
70 40.0 3,178
95 44.5 3,916
120 49.5 4,743
150 56.0 5,753
185 60.0 6,913
240 67.5 8,688
300 73.5 10,193
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 65 70 0.94
16 1.91 2.449 0.236 88 92 1.50
25 1.20 1.539 0.242 117 118 2.35
35 0.868 1.113 0.234 144 142 3.29
50 0.641 0.822 0.232 169 163 4.70
70 0.443 0.568 0.229 212 199 6.58
95 0.320 0.411 0.224 260 239 8.93
120 0.253 0.325 0.223 302 272 11.28
150 0.206 0.265 0.225 350 307 14.10
185 0.164 0.211 0.225 402 347 17.39
240 0.125 0.162 0.223 476 401 22.56
300 0.100 0.130 0.222 546 453 28.20

NA2XKY 5 x (10-50) mm² 0.6/1 kV

Data Konstruksi
om. ross ection Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 24.0 1,291
16 27.0 1,611
25 30.5 2,045
35 34.0 2,559
50 39.0 3,260
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 68 71 0.94
16 1.91 2.449 0.236 91 93 1.50
25 1.20 1.539 0.242 121 120 2.35
35 0.868 1.113 0.234 149 144 3.29
50 0.641 0.822 0.232 181 169 4.70

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.