NA2XSEKRY
Al / XLPE / CTS / PVC / LS / PVC / SWA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed
Aplikasi
- For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol. stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XSEKRY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / CTS / PVC / LS / PVC / SWA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 6
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 7
Perisai kawat baja bulat (SWA)
Steel round-wire armourProteksi mekanis + kekuatan tarik tinggi.
- 8
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XSEKRY 3 x (25-300) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 47.5 | 5,292 |
| 35 | 50.5 | 5,960 |
| 50 | 53.5 | 6,694 |
| 70 | 58.5 | 7,816 |
| 95 | 63.0 | 8,952 |
| 120 | 67.0 | 10,058 |
| 150 | 70.5 | 11,079 |
| 185 | 76.5 | 13,316 |
| 240 | 82.5 | 15,304 |
| 300 | 89.5 | 17,803 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.346 | 121 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.326 | 146 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.314 | 174 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.296 | 216 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.284 | 261 | 232 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.276 | 299 | 263 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.269 | 337 | 293 | 14.10 | 1.03 |
| 185 | 0.164 | 0.212 | 0.262 | 387 | 332 | 17.39 | 1.03 |
| 240 | 0.125 | 0.162 | 0.256 | 452 | 382 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.253 | 512 | 428 | 28.20 | 1.37 |
NA2XSEKRY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 52.5 | 6,335 |
| 35 | 55.5 | 6,981 |
| 50 | 58.5 | 7,718 |
| 70 | 63.5 | 8,879 |
| 95 | 68.0 | 10,158 |
| 120 | 71.5 | 11,267 |
| 150 | 76.5 | 13,142 |
| 185 | 81.0 | 14,630 |
| 240 | 87.0 | 16,697 |
| 300 | 92.5 | 18,908 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.372 | 122 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.350 | 147 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.336 | 175 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.316 | 218 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.303 | 262 | 231 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.293 | 300 | 262 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.285 | 340 | 293 | 14.10 | 1.03 |
| 185 | 0.164 | 0.211 | 0.277 | 389 | 332 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.268 | 452 | 381 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.261 | 512 | 427 | 28.20 | 1.37 |
NA2XSEKRY 3 x (25-300) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 58.5 | 7,592 |
| 35 | 62.0 | 8,443 |
| 50 | 64.5 | 9,175 |
| 70 | 69.5 | 10,550 |
| 95 | 73.5 | 11,761 |
| 120 | 79.0 | 13,570 |
| 150 | 82.5 | 14,776 |
| 185 | 87.0 | 16,439 |
| 240 | 93.0 | 18,692 |
| 300 | 98.0 | 20,807 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.400 | 123 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.376 | 148 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.361 | 176 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.338 | 218 | 193 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.323 | 264 | 231 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.312 | 303 | 262 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.304 | 340 | 292 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.294 | 388 | 330 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.284 | 453 | 380 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.276 | 512 | 426 | 28.20 | 1.37 |
NA2XSEKRY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 67.0 | 9,686 |
| 50 | 70.5 | 10,566 |
| 70 | 76.5 | 12,692 |
| 95 | 80.5 | 13,996 |
| 120 | 84.5 | 15,307 |
| 150 | 88.0 | 16,685 |
| 185 | 92.5 | 18,332 |
| 240 | 98.0 | 20,486 |
| 300 | 103.5 | 22,568 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.868 | 1.113 | 0.397 | 149 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.380 | 177 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.357 | 220 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.340 | 265 | 231 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.328 | 303 | 262 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.319 | 340 | 291 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.308 | 389 | 329 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.297 | 452 | 379 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.289 | 512 | 425 | 28.20 | 1.37 |
NA2XSEKRY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 84.5 | 15,094 |
| 70 | 90.0 | 16,760 |
| 95 | 94.0 | 18,309 |
| 120 | 98.0 | 19,700 |
| 150 | 101.5 | 21,121 |
| 185 | 106.0 | 22,985 |
| 240 | 111.5 | 25,236 |
| 300 | 117.0 | 28,050 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.641 | 0.822 | 0.423 | 179 | 157 | 4.70 | 1.37 |
| 70 | 0.443 | 0.568 | 0.396 | 220 | 192 | 6.58 | 1.37 |
| 95 | 0.320 | 0.411 | 0.377 | 265 | 229 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.364 | 303 | 260 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.353 | 341 | 290 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.340 | 389 | 328 | 17.39 | 1.37 |
| 240 | 0.125 | 0.161 | 0.327 | 452 | 377 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.317 | 510 | 422 | 28.20 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.