NA2XSEKY
Al / XLPE / CTS / PVC / LS / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed
Aplikasi
- For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and mechanical damage is not likely to occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XSEKY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / CTS / PVC / LS / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XSEKY 3 x (25-300) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 39.5 | 3,292 |
| 35 | 43.0 | 3,824 |
| 50 | 46.0 | 4,419 |
| 70 | 50.5 | 5,264 |
| 95 | 54.5 | 6,172 |
| 120 | 58.5 | 7,089 |
| 150 | 62.0 | 7,938 |
| 185 | 66.0 | 9,076 |
| 240 | 72.0 | 10,662 |
| 300 | 78.5 | 12,746 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.346 | 118 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.326 | 143 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.314 | 170 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.296 | 213 | 195 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.284 | 258 | 233 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.276 | 297 | 264 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.269 | 336 | 295 | 14.10 | 1.03 |
| 185 | 0.164 | 0.212 | 0.262 | 386 | 335 | 17.39 | 1.03 |
| 240 | 0.125 | 0.162 | 0.256 | 453 | 387 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.253 | 516 | 434 | 28.20 | 1.37 |
NA2XSEKY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 44.5 | 4,107 |
| 35 | 47.5 | 4,591 |
| 50 | 50.5 | 5,166 |
| 70 | 55.0 | 6,095 |
| 95 | 59.5 | 7,113 |
| 120 | 63.0 | 8,006 |
| 150 | 66.0 | 8,902 |
| 185 | 70.5 | 10,099 |
| 240 | 76.5 | 11,762 |
| 300 | 82.0 | 13,631 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.372 | 120 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.350 | 145 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.336 | 173 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.316 | 215 | 195 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.303 | 260 | 232 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.293 | 299 | 264 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.285 | 338 | 295 | 14.10 | 1.03 |
| 185 | 0.164 | 0.211 | 0.277 | 388 | 335 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.268 | 454 | 386 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.261 | 517 | 434 | 28.20 | 1.37 |
NA2XSEKY 3 x (25-300) mm² 8,7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 50.5 | 5,040 |
| 35 | 53.5 | 5,683 |
| 50 | 56.0 | 6,315 |
| 70 | 61.0 | 7,414 |
| 95 | 65.0 | 8,435 |
| 120 | 68.5 | 9,183 |
| 150 | 72.0 | 10,136 |
| 185 | 76.5 | 11,502 |
| 240 | 82.0 | 13,411 |
| 300 | 87.5 | 15,117 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.400 | 121 | 113 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.376 | 147 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.361 | 175 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.338 | 217 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.323 | 263 | 232 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.312 | 302 | 264 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.304 | 340 | 295 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.294 | 389 | 333 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.284 | 455 | 385 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.276 | 518 | 433 | 28.20 | 1.37 |
NA2XSEKY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 59.0 | 6,715 |
| 50 | 61.5 | 7,395 |
| 70 | 66.0 | 8,454 |
| 95 | 70.0 | 9,534 |
| 120 | 74.0 | 10,584 |
| 150 | 77.5 | 11,701 |
| 185 | 82.0 | 13,053 |
| 240 | 87.5 | 14,796 |
| 300 | 92.0 | 16,533 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.868 | 1.113 | 0.397 | 148 | 135 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.380 | 176 | 159 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.357 | 219 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.340 | 264 | 232 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.328 | 303 | 264 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.319 | 341 | 294 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.308 | 391 | 333 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.297 | 456 | 385 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.289 | 519 | 433 | 28.20 | 1.37 |
NA2XSEKY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 74.0 | 10,304 |
| 70 | 79.0 | 11,636 |
| 95 | 83.0 | 12,875 |
| 120 | 86.5 | 14,038 |
| 150 | 90.0 | 15,232 |
| 185 | 94.5 | 16,752 |
| 240 | 100.0 | 18,690 |
| 300 | 105.5 | 21,079 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.641 | 0.822 | 0.423 | 178 | 158 | 4.70 | 1.37 |
| 70 | 0.443 | 0.568 | 0.396 | 221 | 194 | 6.58 | 1.37 |
| 95 | 0.320 | 0.411 | 0.377 | 266 | 231 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.364 | 305 | 263 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.353 | 343 | 293 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.340 | 393 | 332 | 17.39 | 1.37 |
| 240 | 0.125 | 0.161 | 0.327 | 458 | 383 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.317 | 519 | 430 | 28.20 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.