NA2XSKB(AL)Y
Al / XLPE/ CTS / PVC / LS / PVC / DATA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Double Aluminium Tape Armor, PVC Sheathed
Aplikasi
- For indoor, outdoor, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and low mechanical damage may occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XSKB(AL)Y dari dalam ke luar — sesuai kode konstruksi Al / XLPE/ CTS / PVC / LS / PVC / DATA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 6
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 7
Perisai pita aluminium ganda (DATA)
Double aluminium tape armourDua lapis pita aluminium — perisai non-magnetik untuk kabel inti tunggal.
- 8
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XSKB(AL)Y 1 x (25-630) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 25.5 | 1,472 |
| 35 | 26.5 | 1,603 |
| 50 | 28.0 | 1,725 |
| 70 | 30.0 | 2,031 |
| 95 | 32.0 | 2,263 |
| 120 | 33.5 | 2,550 |
| 150 | 35.0 | 2,721 |
| 185 | 37.0 | 2,985 |
| 240 | 40.0 | 3,545 |
| 300 | 43.0 | 4,117 |
| 400 | 47.5 | 4,847 |
| 500 | 51.5 | 5,719 |
| 630 | 57.0 | 6,865 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) (k | Short circuit current at 1 sec ductor Screen ax. Max. A) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.479 | 0.526 | 132 | 120 | 135 | 122 2. | 35 1.14 |
| 35 | 0.868 | 1.113 | 0.452 | 0.498 | 160 | 143 | 164 | 146 3. | 29 1.14 |
| 50 | 0.641 | 0.822 | 0.433 | 0.479 | 191 | 169 | 195 | 172 4. | 70 1.14 |
| 70 | 0.443 | 0.568 | 0.409 | 0.455 | 239 | 207 | 245 | 211 6. | 58 1.14 |
| 95 | 0.320 | 0.411 | 0.391 | 0.437 | 290 | 247 | 297 | 252 8. | 93 1.14 |
| 120 | 0.253 | 0.325 | 0.378 | 0.424 | 335 | 281 | 343 | 287 11 | .28 1.14 |
| 150 | 0.206 | 0.265 | 0.368 | 0.414 | 378 | 313 | 386 | 320 14 | .10 1.14 |
| 185 | 0.164 | 0.211 | 0.355 | 0.401 | 434 | 355 | 444 | 362 17 | .39 1.14 |
| 240 | 0.125 | 0.161 | 0.347 | 0.393 | 511 | 409 | 522 | 417 22 | .56 1.14 |
| 300 | 0.100 | 0.129 | 0.340 | 0.387 | 584 | 460 | 595 | 467 28 | .20 1.14 |
| 400 | 0.0778 | 0.101 | 0.329 | 0.375 | 683 | 526 | 694 | 532 37 | .60 1.14 |
| 500 | 0.0605 | 0.080 | 0.324 | 0.370 | 786 | 595 | 796 | 599 47 | .00 1.14 |
| 630 | 0.0469 | 0.063 | 0.312 | 0.358 | 915 | 673 | 922 | 675 59 | .22 1.14 |
NA2XSKB(AL)Y 1 x (25-630) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 27.5 | 1,645 |
| 35 | 29.0 | 1,791 |
| 50 | 30.0 | 1,999 |
| 70 | 32.0 | 2,236 |
| 95 | 34.0 | 2,504 |
| 120 | 35.5 | 2,735 |
| 150 | 37.0 | 3,033 |
| 185 | 39.5 | 3,382 |
| 240 | 42.5 | 3,907 |
| 300 | 44.5 | 4,210 |
| 400 | 48.5 | 4,982 |
| 500 | 52.0 | 5,803 |
| 630 | 57.5 | 6,929 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) (k | Short circuit current at 1 sec ductor Screen ax. Max. A) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.494 | 0.540 | 133 | 119 | 136 | 122 2. | 35 1.14 |
| 35 | 0.868 | 1.113 | 0.467 | 0.513 | 161 | 143 | 165 | 146 3. | 29 1.14 |
| 50 | 0.641 | 0.822 | 0.449 | 0.495 | 192 | 168 | 197 | 172 4. | 70 1.14 |
| 70 | 0.443 | 0.568 | 0.422 | 0.468 | 240 | 206 | 246 | 211 6. | 58 1.14 |
| 95 | 0.320 | 0.411 | 0.403 | 0.449 | 291 | 246 | 298 | 252 8. | 93 1.14 |
| 120 | 0.253 | 0.325 | 0.390 | 0.436 | 335 | 280 | 343 | 285 11 | .28 1.14 |
| 150 | 0.206 | 0.265 | 0.380 | 0.426 | 380 | 313 | 388 | 319 14 | .10 1.14 |
| 185 | 0.164 | 0.211 | 0.369 | 0.415 | 436 | 354 | 445 | 360 17 | .39 1.14 |
| 240 | 0.125 | 0.161 | 0.358 | 0.404 | 512 | 409 | 522 | 416 22 | .56 1.14 |
| 300 | 0.100 | 0.129 | 0.345 | 0.392 | 584 | 460 | 595 | 467 28 | .20 1.14 |
| 400 | 0.0778 | 0.101 | 0.333 | 0.379 | 683 | 525 | 694 | 532 37 | .60 1.14 |
| 500 | 0.0605 | 0.080 | 0.326 | 0.372 | 786 | 594 | 796 | 599 47 | .00 1.14 |
| 630 | 0.0469 | 0.063 | 0.313 | 0.359 | 915 | 673 | 922 | 675 59 | .22 1.14 |
NA2XSKB(AL)Y 1 x (25-630) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 30.0 | 1,958 |
| 35 | 31.5 | 2,100 |
| 50 | 32.5 | 2,247 |
| 70 | 35.0 | 2,554 |
| 95 | 36.5 | 2,785 |
| 120 | 38.5 | 3,172 |
| 150 | 40.0 | 3,375 |
| 185 | 42.5 | 3,819 |
| 240 | 44.5 | 4,152 |
| 300 | 47.0 | 4,685 |
| 400 | 51.5 | 5,519 |
| 500 | 54.5 | 6,325 |
| 630 | 60.0 | 7,523 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) (k | Short circuit current at 1 sec ductor Screen ax. Max. A) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.512 | 0.559 | 134 | 119 | 137 | 122 2. | 35 1.14 |
| 35 | 0.868 | 1.113 | 0.483 | 0.530 | 162 | 143 | 166 | 146 3. | 29 1.14 |
| 50 | 0.641 | 0.822 | 0.465 | 0.511 | 193 | 168 | 198 | 172 4. | 70 1.14 |
| 70 | 0.443 | 0.568 | 0.439 | 0.485 | 241 | 206 | 247 | 210 6. | 58 1.14 |
| 95 | 0.320 | 0.411 | 0.418 | 0.464 | 292 | 246 | 299 | 251 8. | 93 1.14 |
| 120 | 0.253 | 0.325 | 0.407 | 0.453 | 337 | 279 | 344 | 285 11 | .28 1.14 |
| 150 | 0.206 | 0.265 | 0.395 | 0.441 | 380 | 312 | 388 | 318 14 | .10 1.14 |
| 185 | 0.164 | 0.211 | 0.383 | 0.429 | 437 | 353 | 446 | 359 17 | .39 1.14 |
| 240 | 0.125 | 0.161 | 0.368 | 0.414 | 512 | 408 | 522 | 415 22 | .56 1.14 |
| 300 | 0.100 | 0.129 | 0.358 | 0.404 | 585 | 459 | 596 | 466 28 | .20 1.14 |
| 400 | 0.0778 | 0.101 | 0.345 | 0.391 | 683 | 524 | 693 | 530 37 | .60 1.14 |
| 500 | 0.0605 | 0.080 | 0.336 | 0.382 | 786 | 593 | 795 | 598 47 | .00 1.14 |
| 630 | 0.0469 | 0.063 | 0.323 | 0.369 | 914 | 672 | 920 | 673 59 | .22 1.14 |
NA2XSKB(AL)Y 1 x (35-630) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 33.5 | 2,425 |
| 50 | 35.0 | 2,545 |
| 70 | 37.0 | 2,889 |
| 95 | 39.5 | 3,204 |
| 120 | 41.0 | 3,439 |
| 150 | 42.5 | 3,789 |
| 185 | 44.5 | 4,018 |
| 240 | 47.0 | 4,580 |
| 300 | 49.5 | 5,136 |
| 400 | 54.0 | 5,871 |
| 500 | 57.0 | 6,671 |
| 630 | 62.5 | 7,895 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) (k | Short circuit current at 1 sec ductor Screen ax. Max. A) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 35 | 0.868 | 1.113 | 0.499 | 0.545 | 163 | 142 | 167 | 145 3. | 29 1.14 |
| 50 | 0.641 | 0.822 | 0.480 | 0.526 | 194 | 168 | 198 | 171 4. | 70 1.14 |
| 70 | 0.443 | 0.568 | 0.451 | 0.497 | 243 | 206 | 248 | 210 6. | 58 1.14 |
| 95 | 0.320 | 0.411 | 0.433 | 0.479 | 293 | 245 | 300 | 250 8. | 93 1.14 |
| 120 | 0.253 | 0.325 | 0.418 | 0.465 | 337 | 279 | 344 | 284 11 | .28 1.14 |
| 150 | 0.206 | 0.265 | 0.408 | 0.454 | 381 | 311 | 389 | 317 14 | .10 1.14 |
| 185 | 0.164 | 0.211 | 0.391 | 0.438 | 437 | 353 | 446 | 359 17 | .39 1.14 |
| 240 | 0.125 | 0.161 | 0.379 | 0.425 | 513 | 407 | 523 | 414 22 | .56 1.14 |
| 300 | 0.100 | 0.129 | 0.368 | 0.414 | 586 | 458 | 596 | 465 28 | .20 1.14 |
| 400 | 0.0778 | 0.101 | 0.354 | 0.400 | 682 | 523 | 692 | 529 37 | .60 1.14 |
| 500 | 0.0605 | 0.080 | 0.344 | 0.390 | 786 | 593 | 794 | 597 47 | .00 1.14 |
| 630 | 0.0469 | 0.063 | 0.330 | 0.377 | 913 | 671 | 918 | 672 59 | .22 1.14 |
NA2XSKB(AL)Y 1 x (50-630) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 41.5 | 3,480 |
| 70 | 43.5 | 3,749 |
| 95 | 45.0 | 3,964 |
| 120 | 47.0 | 4,352 |
| 150 | 48.5 | 4,600 |
| 185 | 51.0 | 5,134 |
| 240 | 53.5 | 5,600 |
| 300 | 56.0 | 6,206 |
| 400 | 60.0 | 7,095 |
| 500 | 63.0 | 7,958 |
| 630 | 69.0 | 9,343 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) (k | Short circuit current at 1 sec ductor Screen ax. Max. A) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 50 | 0.641 | 0.822 | 0.514 | 0.561 | 196 | 167 | 200 | 170 4. | 70 1.14 |
| 70 | 0.443 | 0.568 | 0.483 | 0.529 | 244 | 205 | 249 | 209 6. | 58 1.14 |
| 95 | 0.320 | 0.411 | 0.461 | 0.507 | 295 | 244 | 300 | 249 8. | 93 1.14 |
| 120 | 0.253 | 0.325 | 0.446 | 0.492 | 339 | 278 | 345 | 283 11 | .28 1.14 |
| 150 | 0.206 | 0.265 | 0.433 | 0.479 | 382 | 310 | 389 | 316 14 | .10 1.14 |
| 185 | 0.164 | 0.211 | 0.419 | 0.465 | 438 | 351 | 446 | 357 17 | .39 1.14 |
| 240 | 0.125 | 0.161 | 0.404 | 0.451 | 513 | 406 | 522 | 412 22 | .56 1.14 |
| 300 | 0.100 | 0.129 | 0.392 | 0.439 | 585 | 456 | 593 | 462 28 | .20 1.14 |
| 400 | 0.0778 | 0.101 | 0.376 | 0.422 | 681 | 521 | 690 | 526 37 | .60 1.14 |
| 500 | 0.0605 | 0.079 | 0.365 | 0.411 | 784 | 590 | 790 | 593 47 | .00 1.14 |
| 630 | 0.0469 | 0.063 | 0.350 | 0.396 | 909 | 669 | 912 | 668 59 | .22 1.14 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.