NYKFGbY
Cu / PVC / LS / PVC / SFWA / PVC Deskripsi
Copper Conductor, PVC Insulated, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where that is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation and operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYKFGbY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / LS / PVC / SFWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat baja pipih (SFWA)
Steel flat-wire armourProteksi mekanis berat — penanaman langsung & tarikan panjang.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NYKFGbY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 22.5 | 1,360 |
| 2.5 | 22.5 | 1,384 |
| 4 | 22.5 | 1,413 |
| 6 | 22.5 | 1,448 |
| 10 | 24.5 | 1,703 |
| 16 | 26.5 | 2,024 |
| 25 | 29.5 | 2,503 |
| 35 | 32.5 | 3,034 |
| 50 | 35.5 | 3,704 |
| 70 | 40.0 | 4,640 |
| 95 | 45.0 | 5,924 |
| 120 | 48.5 | 6,930 |
| 150 | 53.0 | 8,238 |
| 185 | 58.5 | 9,901 |
| 240 | 65.0 | 12,393 |
| 300 | 71.5 | 14,884 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 25 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 55 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 75 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 98 | 105 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 129 | 135 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 157 | 163 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 189 | 192 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 237 | 236 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 287 | 280 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 332 | 320 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 376 | 358 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 427 | 400 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 500 | 460 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 565 | 513 | 34.50 |
NYKFGbY 3 x (1.5-300) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 22.5 | 1,384 |
| 2.5 | 22.5 | 1,401 |
| 4 | 22.5 | 1,434 |
| 6 | 23.5 | 1,588 |
| 10 | 25.5 | 1,889 |
| 16 | 27.5 | 2,270 |
| 25 | 31.0 | 2,847 |
| 35 | 34.0 | 3,478 |
| 50 | 37.0 | 3,949 |
| 70 | 41.0 | 5,012 |
| 95 | 46.0 | 6,364 |
| 120 | 49.5 | 7,464 |
| 150 | 54.5 | 9,115 |
| 185 | 59.5 | 10,947 |
| 240 | 66.5 | 13,817 |
| 300 | 72.5 | 16,487 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 21 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 28 | 30 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 37 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 47 | 51 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 64 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 84 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 110 | 114 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 134 | 137 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 168 | 169 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 210 | 206 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 257 | 246 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 296 | 279 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 336 | 312 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 385 | 351 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 451 | 403 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 512 | 450 | 34.50 |
NYKFGbY 4 x (1.5-300) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 22.5 | 1,379 |
| 2.5 | 22.5 | 1,416 |
| 4 | 23.5 | 1,572 |
| 6 | 25.0 | 1,772 |
| 10 | 27.0 | 2,139 |
| 16 | 29.5 | 2,595 |
| 25 | 33.5 | 3,401 |
| 35 | 37.0 | 4,170 |
| 50 | 42.5 | 5,050 |
| 70 | 46.5 | 6,281 |
| 95 | 52.5 | 8,202 |
| 120 | 57.0 | 9,733 |
| 150 | 64.0 | 11,780 |
| 185 | 68.5 | 14,001 |
| 240 | 76.5 | 17,562 |
| 300 | 83.5 | 21,253 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 54 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 73 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 96 | 100 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 127 | 129 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 154 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 178 | 173 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 222 | 212 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 272 | 254 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 313 | 287 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 360 | 323 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 406 | 360 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 477 | 414 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 541 | 461 | 34.50 |
NYKFGbY 5 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 22.5 | 1,407 |
| 2.5 | 22.5 | 1,433 |
| 4 | 25.0 | 1,751 |
| 6 | 26.5 | 1,984 |
| 10 | 29.0 | 2,410 |
| 16 | 32.0 | 3,048 |
| 25 | 36.5 | 4,038 |
| 35 | 40.5 | 5,001 |
| 50 | 45.5 | 6,304 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 25 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 33 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 44 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 56 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 75 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 99 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 132 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 160 | 155 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 192 | 181 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.