NYKRY
Cu / PVC / LS / PVC / AWA / PVC Deskripsi
Copper Conductor, PVC Insulated, Lead Sheathed, Aluminium Wire Armor, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where that is a risk that solvent, fuel and other chemicals may penetrate and high pulling stresses may occur during installation and operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYKRY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / LS / PVC / AWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat aluminium (AWA)
Aluminium wire armourPerisai non-magnetik untuk kabel inti tunggal.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NYKR(AL)Y 1 x (16-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 23.0 | 1,210 |
| 25 | 23.0 | 1,280 |
| 35 | 23.0 | 1,359 |
| 50 | 25.0 | 1,645 |
| 70 | 27.0 | 1,958 |
| 95 | 29.5 | 2,430 |
| 120 | 31.0 | 2,784 |
| 150 | 33.0 | 3,183 |
| 185 | 36.0 | 3,859 |
| 240 | 40.0 | 4,894 |
| 300 | 43.5 | 5,824 |
| 400 | 48.0 | 7,196 |
| 500 | 53.5 | 8,815 |
| 630 | 58.5 | 10,889 |
| 800 | 64.0 | 13,240 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.15 | 1.376 | 0.489 | 0.535 | 102 | 99 | 105 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.440 | 0.486 | 134 | 128 | 137 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.410 | 0.456 | 162 | 154 | 166 | 158 | 4.03 |
| 50 | 0.387 | 0.463 | 0.392 | 0.438 | 197 | 183 | 201 | 187 | 5.75 |
| 70 | 0.268 | 0.321 | 0.371 | 0.417 | 245 | 223 | 250 | 227 | 8.05 |
| 95 | 0.193 | 0.232 | 0.358 | 0.404 | 298 | 265 | 303 | 269 | 10.93 |
| 120 | 0.153 | 0.184 | 0.347 | 0.393 | 342 | 299 | 347 | 303 | 13.80 |
| 150 | 0.124 | 0.149 | 0.339 | 0.385 | 386 | 333 | 392 | 336 | 17.25 |
| 185 | 0.0991 | 0.120 | 0.331 | 0.378 | 441 | 372 | 445 | 374 | 21.28 |
| 240 | 0.0754 | 0.092 | 0.326 | 0.372 | 513 | 420 | 513 | 418 | 27.60 |
| 300 | 0.0601 | 0.074 | 0.321 | 0.367 | 578 | 464 | 575 | 458 | 34.50 |
| 400 | 0.0470 | 0.059 | 0.317 | 0.363 | 651 | 510 | 643 | 499 | 41.20 |
| 500 | 0.0366 | 0.048 | 0.313 | 0.359 | 722 | 549 | 708 | 533 | 51.50 |
| 630 | 0.0283 | 0.039 | 0.303 | 0.350 | 801 | 593 | 781 | 572 | 64.89 |
| 800 | 0.0221 | 0.032 | 0.298 | 0.344 | 874 | 632 | 849 | 607 | 82.40 |
NYKRY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 23.0 | 1,358 |
| 2.5 | 23.0 | 1,381 |
| 4 | 23.0 | 1,410 |
| 6 | 23.0 | 1,455 |
| 10 | 26.0 | 1,854 |
| 16 | 28.0 | 2,163 |
| 25 | 31.0 | 2,658 |
| 35 | 33.5 | 3,208 |
| 50 | 38.0 | 4,151 |
| 70 | 42.0 | 5,148 |
| 95 | 47.0 | 6,468 |
| 120 | 52.0 | 7,969 |
| 150 | 57.0 | 9,384 |
| 185 | 62.0 | 11,153 |
| 240 | 69.0 | 13,777 |
| 300 | 75.5 | 16,396 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 25 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 33 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 55 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 76 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 100 | 106 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 130 | 136 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 159 | 164 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 192 | 193 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 241 | 238 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 291 | 282 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 339 | 323 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 384 | 361 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 436 | 405 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 511 | 467 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 578 | 522 | 34.50 |
NYKRY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 23.0 | 1,381 |
| 2.5 | 23.0 | 1,399 |
| 4 | 23.0 | 1,432 |
| 6 | 24.5 | 1,711 |
| 10 | 27.0 | 2,026 |
| 16 | 29.0 | 2,411 |
| 25 | 32.5 | 3,033 |
| 35 | 35.5 | 3,668 |
| 50 | 39.5 | 4,401 |
| 70 | 43.5 | 5,518 |
| 95 | 50.0 | 7,346 |
| 120 | 53.0 | 8,504 |
| 150 | 58.5 | 10,300 |
| 185 | 63.5 | 12,213 |
| 240 | 70.5 | 15,214 |
| 300 | 78.0 | 18,796 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 21 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 28 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 37 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 47 | 51 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 65 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 85 | 90 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 111 | 115 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 136 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 172 | 170 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 214 | 207 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 263 | 249 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 303 | 282 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 344 | 316 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 394 | 356 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 462 | 410 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 527 | 459 | 34.50 |
NYKRY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 23.0 | 1,377 |
| 2.5 | 23.0 | 1,413 |
| 4 | 24.5 | 1,695 |
| 6 | 26.0 | 1,896 |
| 10 | 28.5 | 2,291 |
| 16 | 31.0 | 2,750 |
| 25 | 35.0 | 3,617 |
| 35 | 39.0 | 4,664 |
| 50 | 45.0 | 5,554 |
| 70 | 50.0 | 7,299 |
| 95 | 56.5 | 9,337 |
| 120 | 61.0 | 10,936 |
| 150 | 67.5 | 13,116 |
| 185 | 72.5 | 15,444 |
| 240 | 81.5 | 20,059 |
| 300 | 88.5 | 23,907 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 44 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 55 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 74 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 98 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 130 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 159 | 155 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 181 | 175 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 227 | 214 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 279 | 256 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 320 | 290 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 368 | 327 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 415 | 365 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 490 | 421 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 557 | 472 | 34.50 |
NYKRY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 23.0 | 1,404 |
| 2.5 | 23.0 | 1,431 |
| 4 | 26.0 | 1,875 |
| 6 | 27.5 | 2,124 |
| 10 | 30.0 | 2,577 |
| 16 | 33.5 | 3,233 |
| 25 | 39.0 | 4,506 |
| 35 | 42.5 | 5,506 |
| 50 | 49.0 | 7,284 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 25 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 33 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 45 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 57 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 77 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 101 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 135 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 164 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 199 | 185 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.