NYKY
Cu / PVC / LS / PVC Deskripsi
Copper Conductor, PVC Insulated, Lead Sheathed, PVC Sheathed
Aplikasi
- For indoors, outdoors, in ground and in duct. Mainly on chemical industries, refineries, petrol stations and any other locations where there is a risk that solvent, fuel and other chemicals may penetrate and mechanical damage is not likely to occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYKY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / LS / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung timah (lead sheath)
Lead sheathKedap air & tahan kimia — untuk lingkungan korosif, terkontaminasi hidrokarbon.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NYKY 1 x (16-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 17.7 | 956 |
| 25 | 17.7 | 1,026 |
| 35 | 17.7 | 1,085 |
| 50 | 19.7 | 1,340 |
| 70 | 21.5 | 1,629 |
| 95 | 24.5 | 2,079 |
| 120 | 26.0 | 2,408 |
| 150 | 28.0 | 2,783 |
| 185 | 31.0 | 3,418 |
| 240 | 34.5 | 4,310 |
| 300 | 37.5 | 5,173 |
| 400 | 41.5 | 6,431 |
| 500 | 46.0 | 7,815 |
| 630 | 50.5 | 9,754 |
| 800 | 55.5 | 11,974 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.15 | 1.376 | 0.439 | 0.486 | 97 | 98 | 99 | 100 | 1.84 |
| 25 | 0.727 | 0.870 | 0.391 | 0.437 | 126 | 127 | 129 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 0.358 | 0.405 | 152 | 153 | 157 | 157 | 4.03 |
| 50 | 0.387 | 0.463 | 0.345 | 0.391 | 186 | 181 | 191 | 186 | 5.75 |
| 70 | 0.268 | 0.321 | 0.327 | 0.374 | 233 | 222 | 239 | 228 | 8.05 |
| 95 | 0.193 | 0.232 | 0.320 | 0.366 | 287 | 266 | 295 | 273 | 10.93 |
| 120 | 0.153 | 0.184 | 0.311 | 0.357 | 332 | 302 | 342 | 310 | 13.80 |
| 150 | 0.124 | 0.150 | 0.305 | 0.352 | 379 | 338 | 389 | 347 | 17.25 |
| 185 | 0.0991 | 0.120 | 0.301 | 0.347 | 438 | 382 | 450 | 391 | 21.28 |
| 240 | 0.0754 | 0.092 | 0.295 | 0.341 | 521 | 442 | 535 | 452 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.291 | 0.337 | 599 | 497 | 613 | 507 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.288 | 0.334 | 691 | 560 | 706 | 570 | 41.20 |
| 500 | 0.0366 | 0.048 | 0.281 | 0.328 | 795 | 629 | 810 | 639 | 51.50 |
| 630 | 0.0283 | 0.040 | 0.274 | 0.320 | 911 | 702 | 925 | 709 | 64.89 |
| 800 | 0.0221 | 0.033 | 0.270 | 0.316 | 1022 | 769 | 1032 | 772 | 82.40 |
NYKY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 18.8 | 893 |
| 2.5 | 18.8 | 916 |
| 4 | 18.8 | 945 |
| 6 | 19.0 | 979 |
| 10 | 21.0 | 1,193 |
| 16 | 23.0 | 1,448 |
| 25 | 26.0 | 1,852 |
| 35 | 28.5 | 2,297 |
| 50 | 32.0 | 2,889 |
| 70 | 36.0 | 3,724 |
| 95 | 41.0 | 4,824 |
| 120 | 44.5 | 5,746 |
| 150 | 49.0 | 6,933 |
| 185 | 54.0 | 8,419 |
| 240 | 60.5 | 10,689 |
| 300 | 66.5 | 12,950 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 53 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 73 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 96 | 105 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 135 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 164 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 186 | 193 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 235 | 238 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 286 | 283 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 332 | 323 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 378 | 362 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 431 | 407 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 508 | 471 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 578 | 528 | 34.50 |
NYKY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 18.8 | 916 |
| 2.5 | 18.8 | 933 |
| 4 | 18.8 | 966 |
| 6 | 19.8 | 1,086 |
| 10 | 22.0 | 1,346 |
| 16 | 24.5 | 1,659 |
| 25 | 27.5 | 2,159 |
| 35 | 30.5 | 2,704 |
| 50 | 33.0 | 3,095 |
| 70 | 37.0 | 4,046 |
| 95 | 42.0 | 5,258 |
| 120 | 45.0 | 6,256 |
| 150 | 50.0 | 7,779 |
| 185 | 55.0 | 9,408 |
| 240 | 61.5 | 12,050 |
| 300 | 67.5 | 14,519 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 21 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 27 | 30 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 36 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 46 | 51 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 62 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 82 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 108 | 115 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 133 | 139 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 167 | 170 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 209 | 208 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 256 | 249 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 296 | 283 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 338 | 317 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 390 | 358 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 460 | 414 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 526 | 465 | 34.50 |
NYKY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 18.8 | 912 |
| 2.5 | 18.8 | 948 |
| 4 | 19.8 | 1,071 |
| 6 | 21.5 | 1,234 |
| 10 | 24.0 | 1,558 |
| 16 | 26.0 | 1,944 |
| 25 | 30.0 | 2,653 |
| 35 | 33.5 | 3,346 |
| 50 | 38.5 | 4,044 |
| 70 | 42.5 | 5,191 |
| 95 | 48.5 | 6,910 |
| 120 | 52.5 | 8,321 |
| 150 | 59.0 | 10,124 |
| 185 | 63.5 | 12,186 |
| 240 | 71.0 | 15,531 |
| 300 | 78.0 | 18,967 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 154 | 156 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 177 | 175 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 221 | 214 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 273 | 257 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 315 | 291 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 365 | 329 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 413 | 368 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 489 | 426 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 560 | 479 | 34.50 |
NYKY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 18.8 | 923 |
| 2.5 | 18.8 | 966 |
| 4 | 21.5 | 1,213 |
| 6 | 23.0 | 1,409 |
| 10 | 25.5 | 1,790 |
| 16 | 28.5 | 2,340 |
| 25 | 33.0 | 3,215 |
| 35 | 36.5 | 4,054 |
| 50 | 41.5 | 5,218 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 54 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 74 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 98 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 131 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 160 | 158 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 194 | 186 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.