N2XFGbY
Cu / XLPE / SFWA / PVC Deskripsi
Copper Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed
Aplikasi
- For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XFGbY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / SFWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Perisai kawat baja pipih (SFWA)
Steel flat-wire armourProteksi mekanis berat — penanaman langsung & tarikan panjang.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk N2XFGbY.
Spesifikasi Teknis
N2XFGbY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 603 |
| 2.5 | 17.9 | 621 |
| 4 | 17.9 | 638 |
| 6 | 17.9 | 669 |
| 10 | 18.8 | 789 |
| 16 | 21.0 | 983 |
| 25 | 24.0 | 1,311 |
| 35 | 26.5 | 1,626 |
| 50 | 29.5 | 1,950 |
| 70 | 33.5 | 2,548 |
| 95 | 37.0 | 3,280 |
| 120 | 41.0 | 3,937 |
| 150 | 45.5 | 4,760 |
| 185 | 50.0 | 5,803 |
| 240 | 55.5 | 7,270 |
| 300 | 61.0 | 8,862 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.340 | 30 | 33 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.315 | 40 | 44 | 0.36 |
| 4 | 4.61 | 5.878 | 0.285 | 53 | 58 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 66 | 74 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 91 | 101 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 121 | 131 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 160 | 168 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 196 | 203 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 237 | 240 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 299 | 295 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 365 | 353 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 424 | 401 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 483 | 449 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 553 | 505 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 653 | 585 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 746 | 658 | 42.90 |
N2XFGbY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 615 |
| 2.5 | 17.9 | 634 |
| 4 | 17.9 | 664 |
| 6 | 17.9 | 711 |
| 10 | 19.7 | 892 |
| 16 | 22.0 | 1,163 |
| 25 | 25.5 | 1,572 |
| 35 | 28.0 | 1,972 |
| 50 | 30.0 | 2,252 |
| 70 | 34.5 | 3,026 |
| 95 | 37.5 | 3,876 |
| 120 | 41.0 | 4,667 |
| 150 | 46.0 | 5,692 |
| 185 | 50.5 | 6,927 |
| 240 | 56.0 | 8,800 |
| 300 | 61.0 | 10,708 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.340 | 26 | 28 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.304 | 34 | 37 | 0.36 |
| 4 | 4.61 | 5.878 | 0.285 | 45 | 50 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 56 | 63 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 77 | 85 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 103 | 110 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 136 | 142 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 167 | 170 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 206 | 206 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 259 | 252 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 317 | 301 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 367 | 343 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 419 | 383 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 484 | 433 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 571 | 500 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 654 | 563 | 42.90 |
N2XFGbY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 622 |
| 2.5 | 17.9 | 643 |
| 4 | 17.9 | 688 |
| 6 | 18.8 | 803 |
| 10 | 21.5 | 1,050 |
| 16 | 24.0 | 1,381 |
| 25 | 27.5 | 1,889 |
| 35 | 30.5 | 2,387 |
| 50 | 34.0 | 2,839 |
| 70 | 38.5 | 3,816 |
| 95 | 42.5 | 4,951 |
| 120 | 47.5 | 6,074 |
| 150 | 53.5 | 7,390 |
| 185 | 57.5 | 8,946 |
| 240 | 64.5 | 11,436 |
| 300 | 70.0 | 13,925 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.328 | 28 | 31 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.304 | 38 | 42 | 0.36 |
| 4 | 4.61 | 5.878 | 0.275 | 49 | 55 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 62 | 69 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 85 | 92 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 113 | 119 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 151 | 154 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 186 | 184 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 218 | 211 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 272 | 258 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 334 | 309 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 387 | 350 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 450 | 396 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 513 | 445 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 606 | 514 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 694 | 578 | 42.90 |
N2XFGbY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 628 |
| 2.5 | 17.9 | 667 |
| 4 | 18.7 | 773 |
| 6 | 20.5 | 929 |
| 10 | 23.0 | 1,220 |
| 16 | 26.0 | 1,614 |
| 25 | 30.0 | 2,253 |
| 35 | 33.0 | 2,871 |
| 50 | 37.5 | 3,626 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.328 | 29 | 33 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.293 | 38 | 43 | 0.36 |
| 4 | 4.61 | 5.878 | 0.275 | 51 | 56 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 64 | 70 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 88 | 93 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 117 | 121 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 157 | 156 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 193 | 187 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 233 | 220 | 7.15 |
N2XFGbY 2 x (25-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 25.0 | 1,374 |
| 35 | 27.0 | 1,699 |
| 50 | 30.0 | 2,004 |
| 70 | 34.0 | 2,610 |
| 95 | 38.0 | 3,352 |
| 120 | 41.5 | 4,017 |
| 150 | 46.0 | 4,849 |
| 185 | 50.5 | 5,907 |
| 240 | 56.5 | 7,386 |
| 300 | 61.5 | 8,996 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 25 | 0.727 | 0.927 | 0.240 | 150 | 167 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 186 | 201 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 226 | 239 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 290 | 295 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 353 | 355 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 413 | 404 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 468 | 458 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 540 | 516 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 590 | 600 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 745 | 695 | 42.90 |
N2XFGbY 3 x (25-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 26.0 | 1,634 |
| 35 | 28.5 | 2,043 |
| 50 | 30.5 | 2,307 |
| 70 | 35.0 | 3,048 |
| 95 | 38.0 | 3,929 |
| 120 | 41.5 | 4,725 |
| 150 | 46.0 | 5,714 |
| 185 | 50.5 | 6,953 |
| 240 | 57.0 | 8,921 |
| 300 | 61.5 | 10,840 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 25 | 0.727 | 0.927 | 0.240 | 130 | 141 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 159 | 170 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 193 | 201 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 245 | 249 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 302 | 299 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 349 | 340 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 400 | 381 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 464 | 434 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 552 | 506 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 640 | 585 | 42.90 |
N2XFGbY 4 x (16-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 24.5 | 1,434 |
| 25 | 28.0 | 1,954 |
| 35 | 31.0 | 2,462 |
| 50 | 35.0 | 2,901 |
| 70 | 39.0 | 3,890 |
| 95 | 43.0 | 5,033 |
| 120 | 48.0 | 6,170 |
| 150 | 54.0 | 7,500 |
| 185 | 58.5 | 9,064 |
| 240 | 65.0 | 11,575 |
| 300 | 70.5 | 14,077 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 16 | 1.15 | 1.467 | 0.238 | 96 | 108 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 130 | 141 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 159 | 170 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 193 | 201 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 245 | 249 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 302 | 299 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 349 | 340 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 400 | 381 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 464 | 434 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 552 | 506 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 640 | 585 | 42.90 |
N2XFGbY 5 x (16-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 26.5 | 1,671 |
| 25 | 30.5 | 2,324 |
| 35 | 34.0 | 2,952 |
| 50 | 38.5 | 3,699 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 16 | 1.15 | 1.466 | 0.238 | 96 | 108 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 130 | 141 | 3.58 |
| 35 | 0.524 | 0.668 | 0.233 | 159 | 170 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 193 | 201 | 7.15 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk N2XFGbY
Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.