PT. Hartaperindo Sejahtera — Distributor Resmi Kabelmetal Indonesia
182 tipe produk — spesifikasi resmi Kabelmetal Indonesia

NA2XRY

Al / XLPE / AWA / PVC
0.6/1 kV IEC 60502-1

Deskripsi

Aluminium Conductor, XLPE Insulated, Aluminium Wire Armor, PVC Sheathed

Aplikasi

  • For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation

Susunan lapisan NA2XRY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / AWA / PVC.

Penampang konstruksi kabel NA2XRY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor aluminium

    Aluminium conductor

    Penghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Perisai kawat aluminium (AWA)

    Aluminium wire armour

    Perisai non-magnetik untuk kabel inti tunggal.

  4. 4

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk NA2XRY.

Spesifikasi Teknis

IEC 60502-1

NA2XR(AL)Y 1 x (25-800) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 16.6 344
35 17.8 403
50 19.5 486
70 22.0 591
95 23.5 699
120 25.5 830
150 28.0 994
185 30.0 1,160
240 33.5 1,428
300 36.0 1,678
400 42.5 2,365
500 45.5 2,704
630 50.0 3,272
800 56.5 4,175
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
25 1.20 1.539 0.379 0.426 123 120 126 123 2.35
35 0.868 1.113 0.360 0.406 149 143 153 147 3.29
50 0.641 0.822 0.343 0.389 181 169 186 174 4.70
70 0.443 0.568 0.326 0.372 228 207 234 213 6.58
95 0.320 0.411 0.313 0.359 278 247 285 253 8.93
120 0.253 0.325 0.310 0.356 323 281 331 287 11.28
150 0.206 0.265 0.302 0.348 371 315 380 321 14.10
185 0.164 0.211 0.296 0.342 427 356 436 361 17.39
240 0.125 0.162 0.287 0.333 507 410 516 416 22.56
300 0.100 0.130 0.282 0.328 580 460 589 464 28.20
400 0.0778 0.102 0.279 0.325 683 519 687 518 37.60
500 0.0605 0.080 0.276 0.322 775 580 775 574 47.00
630 0.0469 0.064 0.271 0.317 885 645 877 633 59.22
800 0.0367 0.052 0.273 0.319 980 693 961 672 75.20

NA2XRY 2 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 19.4 657
16 22.0 812
25 25.0 1,124
35 27.5 1,327
50 30.5 1,531
70 35.0 1,928
95 40.0 2,590
120 43.5 3,017
150 46.5 3,424
185 54.0 4,638
240 59.0 5,457
300 64.0 6,357
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 71 78 0.94
16 1.91 2.449 0.236 95 102 1.50
25 1.20 1.539 0.242 125 131 2.35
35 0.868 1.113 0.234 154 158 3.29
50 0.641 0.822 0.232 186 187 4.70
70 0.443 0.568 0.229 235 229 6.58
95 0.320 0.411 0.224 288 274 8.93
120 0.253 0.325 0.223 333 312 11.28
150 0.206 0.265 0.225 375 347 14.10
185 0.164 0.211 0.225 437 394 17.39
240 0.125 0.162 0.223 513 455 22.56
300 0.100 0.130 0.222 585 511 28.20

NA2XRY 3 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 20.5 712
16 23.5 893
25 26.5 1,232
35 29.0 1,458
50 31.5 1,553
70 36.5 2,182
95 40.0 2,597
120 43.5 2,994
150 49.5 3,959
185 54.0 4,583
240 60.0 5,522
300 65.0 6,408
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 60 65 0.94
16 1.91 2.449 0.236 81 86 1.50
25 1.20 1.539 0.242 106 110 2.35
35 0.868 1.113 0.234 131 133 3.29
50 0.641 0.822 0.232 162 161 4.70
70 0.443 0.568 0.229 205 197 6.58
95 0.320 0.411 0.224 250 235 8.93
120 0.253 0.325 0.223 290 267 11.28
150 0.206 0.265 0.225 332 299 14.10
185 0.164 0.211 0.225 384 338 17.39
240 0.125 0.162 0.223 451 390 22.56
300 0.100 0.130 0.222 516 438 28.20

NA2XRY 4 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 22.0 805
16 26.0 1,161
25 28.5 1,405
35 31.5 1,700
50 35.5 1,880
70 41.0 2,631
95 45.0 3,148
120 51.5 4,159
150 57.5 4,913
185 61.5 5,664
240 68.0 6,807
300 73.5 7,937
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 66 71 0.94
16 1.91 2.449 0.236 90 93 1.50
25 1.20 1.539 0.242 119 120 2.35
35 0.868 1.113 0.234 146 143 3.29
50 0.641 0.822 0.232 171 165 4.70
70 0.443 0.568 0.229 215 201 6.58
95 0.320 0.411 0.224 263 240 8.93
120 0.253 0.325 0.223 307 273 11.28
150 0.206 0.265 0.225 355 308 14.10
185 0.164 0.211 0.225 405 346 17.39
240 0.125 0.162 0.223 476 399 22.56
300 0.100 0.130 0.222 544 448 28.20

NA2XRY 5 x (10-50) mm² 0.6/1 kV

Data Konstruksi
om. ross ection Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 23.5 918
16 28.0 1,315
25 30.5 1,615
35 34.5 1,971
50 40.0 2,662
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 68 72 0.94
16 1.91 2.449 0.236 93 94 1.50
25 1.20 1.539 0.242 123 122 2.35
35 0.868 1.113 0.234 151 145 3.29
50 0.641 0.822 0.232 185 172 4.70
SPLN 43-7

NA2XR(AL)Y 1 x (25-500) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 17.9 412
35 19.1 476
50 21.0 566
70 23.0 681
95 25.0 796
120 27.0 936
150 29.5 1,110
185 31.5 1,286
240 34.5 1,568
300 37.5 1,830
400 44.0 2,548
500 47.0 2,899
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
25 1.20 1.539 0.395 0.441 125 120 129 123 2.35
35 0.868 1.113 0.374 0.420 152 143 156 147 3.29
50 0.641 0.822 0.356 0.402 184 169 189 174 4.70
70 0.443 0.568 0.338 0.384 232 207 238 213 6.58
95 0.320 0.411 0.324 0.370 282 247 289 254 8.93
120 0.253 0.325 0.321 0.367 326 281 335 287 11.28
150 0.206 0.265 0.311 0.357 375 315 383 321 14.10
185 0.164 0.211 0.305 0.351 431 355 440 362 17.39
240 0.125 0.162 0.295 0.341 510 410 520 416 22.56
300 0.100 0.130 0.289 0.335 583 459 592 464 28.20
400 0.0778 0.102 0.285 0.331 685 518 689 518 37.60
500 0.0605 0.080 0.282 0.328 777 578 777 573 47.00

NA2XRGbY 2 x (25-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 26.0 1,268
35 28.5 1,492
50 32.0 1,702
70 36.0 2,108
95 40.5 2,799
120 44.0 3,245
150 47.5 3,669
185 54.5 4,913
240 59.5 5,758
300 65.0 6,754
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
25 1.20 1.539 0.242 119 130 2.35
35 0.868 1.113 0.234 145 157 3.29
50 0.641 0.822 0.232 175 185 4.70
70 0.443 0.568 0.229 220 229 6.58
95 0.320 0.411 0.224 272 276 8.93
120 0.253 0.325 0.223 317 320 11.28
150 0.206 0.265 0.225 362 351 14.10
185 0.164 0.211 0.225 420 400 17.39
240 0.125 0.162 0.223 497 467 22.56
300 0.100 0.130 0.222 577 532 28.20

NA2XRGbY 3 x (25-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 27.5 1,380
35 30.0 1,626
50 32.5 1,712
70 37.5 2,388
95 41.0 2,805
120 44.5 3,220
150 50.0 4,206
185 55.0 4,855
240 60.5 5,830
300 65.5 6,775
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
25 1.20 1.539 0.242 100 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 149 156 4.70
70 0.443 0.568 0.229 189 193 6.58
95 0.320 0.411 0.224 233 232 8.93
120 0.253 0.325 0.223 271 268 11.28
150 0.206 0.265 0.225 310 296 14.10
185 0.164 0.211 0.225 359 336 17.39
240 0.125 0.162 0.223 429 429 22.56
300 0.100 0.130 0.222 496 447 28.20

NA2XRGbY 4 x (16-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 26.5 1,302
25 29.5 1,564
35 32.5 1,881
50 36.5 2,060
70 42.0 2,844
95 46.0 3,382
120 52.0 4,416
150 58.0 5,203
185 62.0 5,975
240 68.5 7,194
300 74.5 8,356
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
16 1.91 2.449 0.236 75 84 1.50
25 1.20 1.539 0.242 110 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 149 156 4.70
70 0.443 0.568 0.229 189 193 6.58
95 0.320 0.411 0.224 233 232 8.93
120 0.253 0.325 0.223 271 268 11.28
150 0.206 0.265 0.225 310 296 14.10
185 0.164 0.211 0.225 359 336 17.39
240 0.125 0.162 0.223 429 393 22.56
300 0.100 0.130 0.222 496 447 28.20

NA2XRGbY 5 x (16-50) mm² 0.6/1 kV

Data Konstruksi
om. ross ection Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 28.5 1,467
25 31.5 1,787
35 35.5 2,183
50 40.5 2,853
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
16 1.91 2.449 0.236 75 84 1.50
25 1.20 1.539 0.242 100 110 2.35
35 0.868 1.113 0.234 123 132 3.29
50 0.641 0.822 0.232 149 156 4.70

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.

Minta penawaran untuk NA2XRY

Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.

Hubungi Kami