PT. Hartaperindo Sejahtera — Distributor Resmi Kabelmetal Indonesia
182 tipe produk — spesifikasi resmi Kabelmetal Indonesia

NA2XSY

Al / XLPE / CTS / PVC
0.6/1 kV IEC 60502-1

Deskripsi

Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed

Aplikasi

  • For power plants and switchgear as well as for installation of sub-station; for installation indoors in confinned spaces and cable channels because of small bending radius. As burried cable, because of its light weight prefered in where installation is difficult

Susunan lapisan NA2XSY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / CTS / PVC.

Penampang konstruksi kabel NA2XSY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor aluminium

    Aluminium conductor

    Penghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk NA2XSY.

Spesifikasi Teknis

NA2XSY 1 x (10-800) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 11.1 160
16 12.3 199
25 13.9 255
35 15.1 305
50 16.8 380
70 18.9 475
95 21.0 571
120 22.5 658
150 25.0 805
185 27.0 954
240 30.0 1,188
300 32.5 1,404
400 38.5 1,961
500 41.5 2,268
630 45.5 2,791
800 50.5 3,436
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current of conductor at 1 sec Max. (kA)
10 3.08 3.949 0.390 0.437 64 69 66 72 0.94
16 1.91 2.449 0.360 0.406 86 90 89 94 1.50
25 1.20 1.539 0.344 0.390 115 117 118 120 2.35
35 0.868 1.113 0.327 0.373 140 140 144 144 3.29
50 0.641 0.822 0.313 0.360 171 166 176 171 4.70
70 0.443 0.568 0.300 0.346 217 204 224 210 6.58
95 0.320 0.411 0.288 0.335 266 244 274 251 8.93
120 0.253 0.325 0.283 0.330 308 278 317 285 11.28
150 0.206 0.265 0.277 0.323 357 313 368 321 14.10
185 0.164 0.211 0.273 0.320 414 355 426 364 17.39
240 0.125 0.162 0.266 0.312 496 413 511 423 22.56
300 0.100 0.130 0.261 0.307 573 467 590 477 28.20
400 0.0778 0.102 0.258 0.304 687 537 706 549 37.60
500 0.0605 0.081 0.256 0.303 793 609 814 621 47.00
630 0.0469 0.064 0.253 0.299 923 691 947 704 59.22
800 0.0367 0.052 0.251 0.298 1060 775 1084 787 75.20

NA2XSY 2 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 16.9 352
16 19.4 464
25 22.0 589
35 24.5 733
50 27.5 863
70 31.5 1,124
95 35.5 1,465
120 39.0 1,770
150 42.0 2,079
185 48.0 2,635
240 53.0 3,255
300 58.5 3,985
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current of conductor at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 68 76 0.94
16 1.91 2.449 0.236 92 101 1.50
25 1.20 1.539 0.242 120 129 2.35
35 0.868 1.113 0.234 148 156 3.29
50 0.641 0.822 0.232 180 185 4.70
70 0.443 0.568 0.229 228 228 6.58
95 0.320 0.411 0.224 279 272 8.93
120 0.253 0.325 0.223 324 310 11.28
150 0.206 0.265 0.225 367 346 14.10
185 0.164 0.211 0.225 427 393 17.39
240 0.125 0.162 0.223 504 455 22.56
300 0.100 0.130 0.222 577 513 28.20

NA2XSY 3 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 17.8 390
16 21.0 518
25 23.0 667
35 26.0 835
50 28.0 856
70 32.0 1,155
95 35.5 1,454
120 39.0 1,769
150 43.5 2,149
185 48.5 2,616
240 54.0 3,317
300 59.0 4,005
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current of conductor at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 58 64 0.94
16 1.91 2.449 0.236 78 85 1.50
25 1.20 1.539 0.242 102 108 2.35
35 0.868 1.113 0.234 126 131 3.29
50 0.641 0.822 0.232 156 159 4.70
70 0.443 0.568 0.229 197 194 6.58
95 0.320 0.411 0.224 242 233 8.93
120 0.253 0.325 0.223 281 265 11.28
150 0.206 0.265 0.225 321 296 14.10
185 0.164 0.211 0.225 373 337 17.39
240 0.125 0.162 0.223 442 390 22.56
300 0.100 0.130 0.222 509 440 28.20

NA2XSY 4 x (10-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 19.3 456
16 22.5 612
25 25.0 797
35 28.0 1,003
50 32.0 1,090
70 36.5 1,464
95 40.5 1,875
120 45.5 2,312
150 51.5 2,814
185 55.5 3,382
240 62.0 4,288
300 68.0 5,180
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current of conductor at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 63 70 0.94
16 1.91 2.449 0.236 86 91 1.50
25 1.20 1.539 0.242 113 118 2.35
35 0.868 1.113 0.234 140 141 3.29
50 0.641 0.822 0.232 165 163 4.70
70 0.443 0.568 0.229 208 199 6.58
95 0.320 0.411 0.224 255 238 8.93
120 0.253 0.325 0.223 297 271 11.28
150 0.206 0.265 0.225 345 306 14.10
185 0.164 0.211 0.225 396 345 17.39
240 0.125 0.162 0.223 469 400 22.56
300 0.100 0.130 0.222 540 452 28.20

NA2XSY 5 x (10-50) mm² 0.6/1 kV

Data Konstruksi
om. ross ection Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
10 21.0 533
16 24.5 721
25 27.5 947
35 31.0 1,198
50 35.5 1,512
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current of conductor at 1 sec Max. (kA)
(mH/km)
10 3.08 3.949 0.248 65 71 0.94
16 1.91 2.449 0.236 89 93 1.50
25 1.20 1.539 0.242 118 120 2.35
35 0.868 1.113 0.234 146 144 3.29
50 0.641 0.822 0.232 177 169 4.70

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.