NAYY
Al / PVC / PVC Deskripsi
Aluminium Conductor, PVC Insulated, PVC Sheathed
Aplikasi
- Power cable Indoors, cable trunking, outdoors and burried in the ground, for power stations, industry and switchgear as well as for urban supply networks, if mechanical damage is unlikely
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NAYY dari dalam ke luar — sesuai kode konstruksi Al / PVC / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NAYY.
Spesifikasi Teknis
NAYY 1 x (10-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 9.1 | 103 |
| 16 | 10.3 | 135 |
| 25 | 11.9 | 186 |
| 35 | 13.1 | 231 |
| 50 | 15.0 | 306 |
| 70 | 17.1 | 391 |
| 95 | 19.2 | 498 |
| 120 | 21.0 | 583 |
| 150 | 23.5 | 725 |
| 185 | 26.0 | 886 |
| 240 | 29.0 | 1,142 |
| 300 | 32.0 | 1,388 |
| 400 | 35.5 | 1,706 |
| 500 | 40.5 | 2,219 |
| 630 | 44.5 | 2,709 |
| 800 | 48.5 | 3,272 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 10 | 3.08 | 3.701 | 0.350 | 0.396 | 49 | 59 | 50 | 58 | 0.76 |
| 16 | 1.91 | 2.295 | 0.323 | 0.370 | 66 | 77 | 68 | 76 | 1.22 |
| 25 | 1.20 | 1.442 | 0.313 | 0.359 | 88 | 98 | 91 | 97 | 1.90 |
| 35 | 0.868 | 1.043 | 0.298 | 0.344 | 109 | 118 | 112 | 117 | 2.66 |
| 50 | 0.641 | 0.770 | 0.290 | 0.336 | 134 | 140 | 138 | 138 | 3.80 |
| 70 | 0.443 | 0.533 | 0.279 | 0.325 | 170 | 171 | 175 | 169 | 5.32 |
| 95 | 0.320 | 0.385 | 0.274 | 0.320 | 210 | 205 | 216 | 202 | 7.22 |
| 120 | 0.253 | 0.305 | 0.270 | 0.316 | 244 | 233 | 251 | 229 | 9.12 |
| 150 | 0.206 | 0.249 | 0.265 | 0.312 | 283 | 261 | 291 | 258 | 11.40 |
| 185 | 0.164 | 0.198 | 0.264 | 0.310 | 328 | 296 | 339 | 292 | 14.06 |
| 240 | 0.125 | 0.152 | 0.260 | 0.306 | 395 | 344 | 407 | 339 | 18.24 |
| 300 | 0.100 | 0.122 | 0.258 | 0.304 | 456 | 388 | 471 | 382 | 22.80 |
| 400 | 0.0778 | 0.096 | 0.252 | 0.298 | 548 | 447 | 565 | 440 | 27.20 |
| 500 | 0.0605 | 0.076 | 0.251 | 0.298 | 633 | 507 | 653 | 499 | 34.00 |
| 630 | 0.0469 | 0.061 | 0.246 | 0.293 | 738 | 576 | 762 | 566 | 42.84 |
| 800 | 0.0367 | 0.050 | 0.242 | 0.289 | 848 | 646 | 877 | 635 | 54.40 |
NAYY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 18.4 | 411 |
| 16 | 21.0 | 536 |
| 25 | 23.5 | 675 |
| 35 | 26.0 | 834 |
| 50 | 29.5 | 964 |
| 70 | 33.0 | 1,229 |
| 95 | 38.0 | 1,632 |
| 120 | 41.0 | 1,926 |
| 150 | 44.0 | 2,259 |
| 185 | 50.5 | 2,877 |
| 240 | 55.5 | 3,576 |
| 300 | 61.5 | 4,375 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 54 | 61 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 73 | 81 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 94 | 103 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 116 | 125 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 141 | 148 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 178 | 183 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 218 | 219 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 253 | 250 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 285 | 279 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 331 | 317 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 390 | 366 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 447 | 413 | 22.80 |
NAYY 3 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 19.4 | 459 |
| 16 | 22.5 | 601 |
| 25 | 24.5 | 767 |
| 35 | 27.5 | 952 |
| 50 | 30.0 | 986 |
| 70 | 34.0 | 1,301 |
| 95 | 38.5 | 1,682 |
| 120 | 41.5 | 1,973 |
| 150 | 46.0 | 2,399 |
| 185 | 50.5 | 2,936 |
| 240 | 57.0 | 3,741 |
| 300 | 62.5 | 4,534 |
| 400 | 69.0 | 5,644 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 46 | 52 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 62 | 69 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 81 | 88 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 100 | 106 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 126 | 131 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 158 | 160 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 194 | 192 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 225 | 219 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 257 | 245 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 297 | 278 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 352 | 322 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 405 | 364 | 22.80 |
| 400 | 0.0778 | 0.096 | 0.229 | 471 | 415 | 27.20 |
NAYY 4 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.5 | 541 |
| 16 | 24.5 | 715 |
| 25 | 27.0 | 920 |
| 35 | 30.0 | 1,147 |
| 50 | 35.5 | 1,306 |
| 70 | 39.0 | 1,659 |
| 95 | 44.5 | 2,163 |
| 120 | 48.5 | 2,599 |
| 150 | 54.5 | 3,164 |
| 185 | 59.0 | 3,867 |
| 240 | 66.0 | 4,854 |
| 300 | 72.5 | 5,884 |
| 400 | 82.5 | 7,473 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 53 | 59 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 71 | 77 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 93 | 99 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 115 | 119 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 134 | 135 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 167 | 165 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 207 | 198 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 240 | 225 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 277 | 254 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 316 | 286 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 377 | 332 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 433 | 376 | 22.80 |
| 400 | 0.0778 | 0.096 | 0.229 | 510 | 432 | 27.20 |
NAYY 5 x (10-50) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 23.0 | 636 |
| 16 | 26.5 | 847 |
| 25 | 29.5 | 1,098 |
| 35 | 33.0 | 1,389 |
| 50 | 38.0 | 1,731 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 54 | 60 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 73 | 78 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 97 | 101 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 120 | 121 | 2.66 |
| 50 | 0.641 | 0.771 | 0.247 | 147 | 144 | 3.80 |
NAYY 1 x (10-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 9.1 | 103 |
| 16 | 10.3 | 135 |
| 25 | 11.9 | 186 |
| 35 | 13.1 | 231 |
| 50 | 15.0 | 306 |
| 70 | 17.1 | 391 |
| 95 | 19.2 | 498 |
| 120 | 21.0 | 583 |
| 150 | 23.5 | 725 |
| 185 | 26.0 | 886 |
| 240 | 29.0 | 1,142 |
| 300 | 32.0 | 1,388 |
| 400 | 35.5 | 1,706 |
| 500 | 40.5 | 2,219 |
| 630 | 44.5 | 2,709 |
| 800 | 48.5 | 3,272 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 10 | 3.08 | 3.701 | 0.350 | 0.396 | 49 | 59 | 50 | 58 | 0.76 |
| 16 | 1.91 | 2.295 | 0.323 | 0.370 | 66 | 77 | 68 | 76 | 1.22 |
| 25 | 1.20 | 1.442 | 0.313 | 0.359 | 88 | 98 | 91 | 97 | 1.90 |
| 35 | 0.868 | 1.043 | 0.298 | 0.344 | 109 | 118 | 112 | 117 | 2.66 |
| 50 | 0.641 | 0.770 | 0.290 | 0.336 | 134 | 140 | 138 | 138 | 3.80 |
| 70 | 0.443 | 0.533 | 0.279 | 0.325 | 170 | 171 | 175 | 169 | 5.32 |
| 95 | 0.320 | 0.385 | 0.274 | 0.320 | 210 | 205 | 216 | 202 | 7.22 |
| 120 | 0.253 | 0.305 | 0.270 | 0.316 | 244 | 233 | 251 | 229 | 9.12 |
| 150 | 0.206 | 0.249 | 0.265 | 0.312 | 283 | 261 | 291 | 258 | 11.40 |
| 185 | 0.164 | 0.198 | 0.264 | 0.310 | 328 | 296 | 339 | 292 | 14.06 |
| 240 | 0.125 | 0.152 | 0.260 | 0.306 | 395 | 344 | 407 | 339 | 18.24 |
| 300 | 0.100 | 0.122 | 0.258 | 0.304 | 456 | 388 | 471 | 382 | 22.80 |
| 400 | 0.0778 | 0.096 | 0.252 | 0.298 | 548 | 447 | 565 | 440 | 27.20 |
| 500 | 0.0605 | 0.076 | 0.251 | 0.298 | 633 | 507 | 653 | 499 | 34.00 |
| 630 | 0.0469 | 0.061 | 0.246 | 0.293 | 738 | 576 | 762 | 566 | 42.84 |
| 800 | 0.0367 | 0.050 | 0.242 | 0.289 | 848 | 646 | 877 | 635 | 54.40 |
NAYY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 18.4 | 411 |
| 16 | 21.0 | 536 |
| 25 | 23.5 | 675 |
| 35 | 26.0 | 834 |
| 50 | 29.5 | 964 |
| 70 | 33.0 | 1,229 |
| 95 | 38.0 | 1,632 |
| 120 | 41.0 | 1,926 |
| 150 | 44.0 | 2,259 |
| 185 | 50.5 | 2,877 |
| 240 | 55.5 | 3,576 |
| 300 | 61.5 | 4,375 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 54 | 61 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 73 | 81 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 94 | 103 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 116 | 125 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 141 | 148 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 178 | 183 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 218 | 219 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 253 | 250 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 285 | 279 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 331 | 317 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 390 | 366 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 447 | 413 | 22.80 |
NAYY 3 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 19.4 | 459 |
| 16 | 22.5 | 601 |
| 25 | 24.5 | 767 |
| 35 | 27.5 | 952 |
| 50 | 30.0 | 986 |
| 70 | 34.0 | 1,301 |
| 95 | 38.5 | 1,682 |
| 120 | 41.5 | 1,973 |
| 150 | 46.0 | 2,399 |
| 185 | 50.5 | 2,936 |
| 240 | 57.0 | 3,741 |
| 300 | 62.5 | 4,534 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 46 | 52 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 62 | 69 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 81 | 88 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 100 | 106 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 126 | 131 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 158 | 160 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 194 | 192 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 225 | 219 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 257 | 245 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 297 | 278 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 352 | 322 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 405 | 364 | 22.80 |
NAYY 4 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.5 | 541 |
| 16 | 24.5 | 715 |
| 25 | 27.0 | 920 |
| 35 | 30.0 | 1,147 |
| 50 | 35.5 | 1,306 |
| 70 | 39.0 | 1,659 |
| 95 | 44.5 | 2,163 |
| 120 | 48.5 | 2,599 |
| 150 | 54.5 | 3,164 |
| 185 | 59.0 | 3,867 |
| 240 | 66.0 | 4,854 |
| 300 | 72.5 | 5,884 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 53 | 59 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 71 | 77 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 93 | 99 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 115 | 119 | 2.66 |
| 50 | 0.641 | 0.770 | 0.247 | 134 | 135 | 3.80 |
| 70 | 0.443 | 0.533 | 0.238 | 167 | 165 | 5.32 |
| 95 | 0.320 | 0.385 | 0.238 | 207 | 198 | 7.22 |
| 120 | 0.253 | 0.305 | 0.233 | 240 | 225 | 9.12 |
| 150 | 0.206 | 0.248 | 0.235 | 277 | 254 | 11.40 |
| 185 | 0.164 | 0.198 | 0.233 | 316 | 286 | 14.06 |
| 240 | 0.125 | 0.152 | 0.232 | 377 | 332 | 18.24 |
| 300 | 0.100 | 0.122 | 0.231 | 433 | 376 | 22.80 |
NAYY 5 x (10-50) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 23.0 | 636 |
| 16 | 26.5 | 847 |
| 25 | 29.5 | 1,098 |
| 35 | 33.0 | 1,389 |
| 50 | 38.0 | 1,731 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.701 | 0.269 | 54 | 60 | 0.76 |
| 16 | 1.91 | 2.295 | 0.253 | 73 | 78 | 1.22 |
| 25 | 1.20 | 1.442 | 0.257 | 97 | 101 | 1.90 |
| 35 | 0.868 | 1.043 | 0.247 | 120 | 121 | 2.66 |
| 50 | 0.641 | 0.771 | 0.247 | 147 | 144 | 3.80 |
NAYY 1 x (10-500) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 9.1 | 103 |
| 16 | 10.3 | 135 |
| 25 | 11.9 | 186 |
| 35 | 13.1 | 231 |
| 50 | 15.0 | 306 |
| 70 | 16.9 | 383 |
| 95 | 19.2 | 498 |
| 120 | 20.5 | 573 |
| 150 | 23.5 | 725 |
| 185 | 26.0 | 886 |
| 240 | 29.0 | 1,142 |
| 300 | 32.0 | 1,388 |
| 400 | 37.5 | 1,904 |
| 500 | 40.5 | 2,219 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 10 | 3.08 | 3.701 | 50 | 0.350 | 0.396 | 49 | 59 | 50 | 60 | 0.76 |
| 16 | 1.91 | 2.295 | 40 | 0.323 | 0.370 | 66 | 77 | 68 | 78 | 1.22 |
| 25 | 1.20 | 1.442 | 40 | 0.313 | 0.359 | 88 | 98 | 91 | 101 | 1.90 |
| 35 | 0.868 | 1.043 | 40 | 0.298 | 0.344 | 109 | 118 | 112 | 121 | 2.66 |
| 50 | 0.641 | 0.770 | 30 | 0.290 | 0.336 | 134 | 140 | 138 | 143 | 3.80 |
| 70 | 0.443 | 0.533 | 30 | 0.277 | 0.323 | 170 | 172 | 175 | 176 | 5.32 |
| 95 | 0.320 | 0.385 | 30 | 0.274 | 0.320 | 210 | 205 | 216 | 211 | 7.22 |
| 120 | 0.253 | 0.305 | 30 | 0.268 | 0.314 | 243 | 233 | 251 | 240 | 9.12 |
| 150 | 0.206 | 0.249 | 20 | 0.265 | 0.312 | 283 | 261 | 291 | 269 | 11.40 |
| 185 | 0.164 | 0.198 | 20 | 0.264 | 0.310 | 328 | 296 | 339 | 305 | 14.06 |
| 240 | 0.125 | 0.152 | 20 | 0.260 | 0.306 | 395 | 344 | 407 | 355 | 18.24 |
| 300 | 0.100 | 0.122 | 20 | 0.258 | 0.304 | 456 | 388 | 471 | 401 | 22.80 |
| 400 | 0.0778 | 0.096 | 20 | 0.252 | 0.298 | 548 | 447 | 565 | 462 | 27.20 |
| 500 | 0.0605 | 0.076 | 20 | 0.251 | 0.298 | 633 | 507 | 653 | 525 | 34.00 |
NAYY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 18.4 | 411 |
| 16 | 21.0 | 536 |
| 25 | 23.5 | 675 |
| 35 | 26.0 | 834 |
| 50 | 29.5 | 964 |
| 70 | 33.0 | 1,229 |
| 95 | 37.5 | 1,594 |
| 120 | 40.5 | 1,885 |
| 150 | 43.5 | 2,215 |
| 185 | 50.5 | 2,877 |
| 240 | 55.5 | 3,576 |
| 300 | 61.5 | 4,375 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 3.08 | 3.701 | 50 | 0.269 | 48 | 59 | 0.76 |
| 16 | 1.91 | 2.295 | 40 | 0.253 | 70 | 79 | 1.22 |
| 25 | 1.20 | 1.442 | 40 | 0.257 | 94 | 102 | 1.90 |
| 35 | 0.868 | 1.043 | 40 | 0.247 | 115 | 125 | 2.66 |
| 50 | 0.641 | 0.770 | 30 | 0.247 | 140 | 147 | 3.80 |
| 70 | 0.443 | 0.533 | 30 | 0.238 | 155 | 156 | 5.32 |
| 95 | 0.320 | 0.385 | 30 | 0.238 | 190 | 191 | 7.22 |
| 120 | 0.253 | 0.305 | 30 | 0.233 | 220 | 220 | 9.12 |
| 150 | 0.206 | 0.248 | 20 | 0.235 | 245 | 245 | 11.40 |
| 185 | 0.164 | 0.198 | 20 | 0.233 | 275 | 275 | 14.06 |
| 240 | 0.125 | 0.152 | 20 | 0.232 | 320 | 320 | 18.24 |
| 300 | 0.100 | 0.122 | 20 | 0.231 | 365 | 365 | 22.80 |
NAYY 3 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 19.4 | 459 |
| 16 | 22.5 | 601 |
| 25 | 24.5 | 767 |
| 35 | 27.5 | 952 |
| 50 | 30.0 | 986 |
| 70 | 34.0 | 1,301 |
| 95 | 38.5 | 1,682 |
| 120 | 41.5 | 1,973 |
| 150 | 46.0 | 2,399 |
| 185 | 50.5 | 2,936 |
| 240 | 57.0 | 3,741 |
| 300 | 62.5 | 4,534 |
| 400 | 69.0 | 5,644 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 3.08 | 3.701 | 50 | 0.269 | 44 | 52 | 0.76 |
| 16 | 1.91 | 2.295 | 40 | 0.253 | 62 | 69 | 1.22 |
| 25 | 1.20 | 1.442 | 40 | 0.257 | 82 | 89 | 1.90 |
| 35 | 0.868 | 1.043 | 40 | 0.247 | 100 | 107 | 2.66 |
| 50 | 0.641 | 0.770 | 30 | 0.247 | 125 | 129 | 3.80 |
| 70 | 0.443 | 0.533 | 30 | 0.238 | 155 | 156 | 5.32 |
| 95 | 0.320 | 0.385 | 30 | 0.238 | 190 | 191 | 7.22 |
| 120 | 0.253 | 0.305 | 30 | 0.233 | 220 | 220 | 9.12 |
| 150 | 0.206 | 0.248 | 20 | 0.235 | 250 | 245 | 11.40 |
| 185 | 0.164 | 0.198 | 20 | 0.233 | 285 | 275 | 14.06 |
| 240 | 0.125 | 0.152 | 20 | 0.232 | 340 | 320 | 18.24 |
| 300 | 0.100 | 0.122 | 20 | 0.231 | 390 | 365 | 22.80 |
| 400 | 0.0778 | 0.096 | 20 | 0.229 | 460 | 420 | 27.20 |
NAYY 4 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.5 | 541 |
| 16 | 24.5 | 715 |
| 25 | 27.0 | 920 |
| 35 | 30.0 | 1,147 |
| 50 | 35.5 | 1,306 |
| 70 | 39.0 | 1,659 |
| 95 | 44.5 | 2,163 |
| 120 | 48.5 | 2,599 |
| 150 | 54.5 | 3,164 |
| 185 | 59.0 | 3,808 |
| 240 | 66.0 | 4,854 |
| 300 | 72.5 | 5,884 |
| 400 | 82.5 | 7,473 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 3.08 | 3.701 | 50 | 0.269 | 44 | 52 | 0.76 |
| 16 | 1.91 | 2.295 | 40 | 0.253 | 62 | 69 | 1.22 |
| 25 | 1.20 | 1.442 | 40 | 0.257 | 82 | 89 | 1.90 |
| 35 | 0.868 | 1.043 | 40 | 0.247 | 100 | 107 | 2.66 |
| 50 | 0.641 | 0.770 | 30 | 0.247 | 125 | 129 | 3.80 |
| 70 | 0.443 | 0.533 | 30 | 0.238 | 155 | 156 | 5.32 |
| 95 | 0.320 | 0.385 | 30 | 0.238 | 190 | 191 | 7.22 |
| 120 | 0.253 | 0.305 | 30 | 0.233 | 220 | 220 | 9.12 |
| 150 | 0.206 | 0.248 | 20 | 0.235 | 250 | 245 | 11.40 |
| 185 | 0.164 | 0.198 | 20 | 0.233 | 285 | 275 | 14.06 |
| 240 | 0.125 | 0.152 | 20 | 0.232 | 340 | 320 | 18.24 |
| 300 | 0.100 | 0.122 | 20 | 0.231 | 390 | 365 | 22.80 |
| 400 | 0.0778 | 0.096 | 20 | 0.229 | 460 | 420 | 27.20 |
NAYY 5 x (10-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 23.0 | 636 |
| 16 | 26.5 | 847 |
| 25 | 29.5 | 1,098 |
| 35 | 33.0 | 1,389 |
| 50 | 38.0 | 1,731 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 3.08 | 3.701 | 50 | 0.269 | 44 | 52 | 0.76 |
| 16 | 1.91 | 2.295 | 40 | 0.253 | 62 | 69 | 1.22 |
| 25 | 1.20 | 1.442 | 40 | 0.257 | 82 | 89 | 1.90 |
| 35 | 0.868 | 1.043 | 40 | 0.247 | 100 | 107 | 2.66 |
| 50 | 0.641 | 0.770 | 40 | 0.247 | 125 | 129 | 3.80 |