NFA2X-T
Al / XLPE 0.6/1 kV SPLN 42-10:1993
Deskripsi
Aluminium Conductor, XLPE Insulated, with Aluminium Alloy Support Messenger
Aplikasi
- Twisted / bundled insulated conductors for overhead (aerial) low voltage distribution and service drop
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NFA2X-T dari dalam ke luar — sesuai kode konstruksi Al / XLPE.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
Spesifikasi Teknis
NFA2X-T (2 x 25 + 25 mm2 - 2 x 95 + 70 mm2) 0.6/1 kV
| Conductor Nom. Cross Section Area | Approxim Overall Diameter approx. | ate Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 2x25+25 | 20.6 | 319 |
| 2x35+25 | 24.1 | 400 |
| 2x50+35 | 27.5 | 546 |
| 2x70+50 | 32.4 | 739 |
| 2x95+70 | 36.9 | 973 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C ( Ω/km ) Phase | Messenger | AC Resistance at 90°C (Ω/km) Phase | Messenger | Calculated Breaking Load of Messenger ( kg ) | Current-Carrying Capacity at 30°C * in air ( A ) | Short circuit current at 1 sec (kA) |
|---|---|---|---|---|---|---|---|
| 2x25+25 | 1.20 | 1.38 | 1.539 | 1.769 | 712 | 103 | 2.35 |
| 2x35+25 | 0.868 | 1.38 | 1.113 | 1.769 | 712 | 125 | 3.29 |
| 2x50+35 | 0.641 | 0.986 | 0.822 | 1.264 | 997 | 154 | 4.70 |
| 2x70+50 | 0.443 | 0.690 | 0.568 | 0.885 | 1395 | 196 | 6.58 |
| 2x95+70 | 0.320 | 0.450 | 0.410 | 0.577 | 1932 | 242 | 8.93 |
NFA2X-T (3 x 25 + 25 mm2 - 3 x 95 + 70 mm2) 0.6/1 kV
| Conductor Nom. Cross Section Area | Approxim Overall Diameter approx. | ate Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 3x25+25 | 23.1 | 425 |
| 3x35+25 | 27.0 | 547 |
| 3x50+35 | 30.8 | 745 |
| 3x70+50 | 36.3 | 1008 |
| 3x95+70 | 41.3 | 1325 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C ( Ω/km ) Phase | Messenger | AC Resistance at 90°C (Ω/km) Phase | Messenger | Calculated Breaking Load of messenger ( kg ) | Current-Carrying Capacity at 30°C * in air ( A ) | Short circuit current at 1 sec (kA) |
|---|---|---|---|---|---|---|---|
| 3x25+25 | 1.20 | 1.38 | 1.539 | 1.769 | 712 | 103 | 2.35 |
| 3x35+25 | 0.868 | 1.38 | 1.113 | 1.769 | 712 | 125 | 3.29 |
| 3x50+35 | 0.641 | 0.986 | 0.822 | 1.264 | 997 | 154 | 4.70 |
| 3x70+50 | 0.443 | 0.690 | 0.568 | 0.885 | 1395 | 196 | 6.58 |
| 3x95+70 | 0.320 | 0.450 | 0.410 | 0.577 | 1932 | 242 | 8.93 |
NFA2X-T (3 x 25 + 25 +16 mm2 - 3 x 95 + 70 + 16 mm2) 0.6/1 kV
| Conductor Nom. Cross Section Area | Approxim Overall Diameter approx. | ate Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 3x25+25+16 | 25.8 | 495 |
| 3x35+25+16 | 30.2 | 618 |
| 3x50+35+16 | 34.4 | 816 |
| 3x70+50+16 | 40.6 | 1079 |
| 3x95+70+16 | 46.2 | 1395 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C ( Ω/km ) Phase | Messenger | Lighting Ph | AC Resistance at 90°C (Ω/km) ase Messenger | Lighting | Calculated Breaking Load of Messenger ( kg ) | Current-Carrying Capacity at 30°C * in air Phase | Lighting | Short circuit current at 1 sec (kA) |
|---|---|---|---|---|---|---|---|---|---|
| ( A ) | ( A ) | ||||||||
| 3x25+25+16 | 1.20 | 1.38 | 1.91 1.5 | 39 1.769 | 2.449 | 712 | 103 | 72 | 2.35 |
| 3x35+25+16 | 0.868 | 1.38 | 1.91 1.1 | 13 1.769 | 2.449 | 712 | 125 | 72 | 3.29 |
| 3x50+35+16 | 0.641 | 0.986 | 1.91 0.8 | 22 1.264 | 2.449 | 997 | 154 | 72 | 4.70 |
| 3x70+50+16 | 0.443 | 0.690 | 1.91 0.5 | 68 0.885 | 2.449 | 1395 | 196 | 72 | 6.58 |
| 3x95+70+16 | 0.320 | 0.450 | 1.91 0.4 | 10 0.577 | 2.449 | 1932 | 242 | 72 | 8.93 |
NFA2X-T (3x25+25+2x16mm2 - 3x95+70+2x16mm2) 0.6/1 kV
| Conductor Nom. Cross Section Area | Approxim Overall Diameter approx. | ate Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 3x25+25+2x16 | 28.7 | 540 |
| 3x35+25+2x16 | 33.6 | 662 |
| 3x50+35+2x16 | 38.3 | 860 |
| 3x70+50+2x16 | 45.1 | 1123 |
| 3x95+70+2x16 | 51.3 | 1440 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C ( Ω/km ) Phase | Messenger | Lighting Ph | AC Resistance at 90°C (Ω/km) ase Messenger | Lighting | Calculated Breaking Load of Messenger ( kg ) | Current-Carrying Capacity at 30°C * in air Phase | Lighting | Short circuit current at 1 sec (kA) |
|---|---|---|---|---|---|---|---|---|---|
| ( A ) | ( A ) | ||||||||
| 3x25+25+2x16 | 1.20 | 1.38 | 1.91 1.5 | 39 1.769 | 2.449 | 712 | 103 | 72 | 2.35 |
| 3x35+25+2x16 | 0.868 | 1.38 | 1.91 1.1 | 13 1.769 | 2.449 | 712 | 125 | 72 | 3.29 |
| 3x50+35+2x16 | 0.641 | 0.986 | 1.91 0.8 | 22 1.264 | 2.449 | 997 | 154 | 72 | 4.70 |
| 3x70+50+2x16 | 0.443 | 0.690 | 1.91 0.5 | 68 0.885 | 2.449 | 1395 | 196 | 72 | 6.58 |
| 3x95+70+2x16 | 0.320 | 0.450 | 1.91 0.4 | 10 0.577 | 2.449 | 1932 | 242 | 72 | 8.93 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.