NYBY
Cu / PVC / ATA / PVC Deskripsi
Copper Conductor, PVC Insulated, Aluminium Tape Armor, PVC Sheathed
Aplikasi
- For installation indoors, cable channels and in ground, for industry installations, switchgear, and power station, if there is a risk that low mechanical damage may occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYBY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / ATA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Perisai pita aluminium (ATA)
Aluminium tape armourPerisai non-magnetik — dipakai pada kabel inti tunggal agar tidak timbul rugi induksi.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYBY.
Spesifikasi Teknis
NYB(AL)Y 1 x (16-800) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 15.4 | 396 |
| 25 | 16.2 | 497 |
| 35 | 17.3 | 608 |
| 50 | 19.3 | 785 |
| 70 | 21.5 | 1,011 |
| 95 | 23.5 | 1,298 |
| 120 | 25.0 | 1,552 |
| 150 | 27.0 | 1,850 |
| 185 | 29.5 | 2,279 |
| 240 | 32.5 | 2,926 |
| 300 | 35.5 | 3,521 |
| 400 | 39.5 | 4,476 |
| 500 | 43.5 | 5,645 |
| 630 | 48.0 | 7,190 |
| 800 | 53.0 | 8,941 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.15 | 1.376 | 0.412 | 0.458 | 94 | 98 | 97 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.374 | 0.420 | 124 | 127 | 127 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.356 | 0.402 | 151 | 152 | 155 | 156 | 4.03 |
| 50 | 0.387 | 0.463 | 0.341 | 0.387 | 184 | 180 | 189 | 185 | 5.75 |
| 70 | 0.268 | 0.321 | 0.324 | 0.370 | 230 | 221 | 236 | 226 | 8.05 |
| 95 | 0.193 | 0.232 | 0.313 | 0.359 | 282 | 264 | 289 | 269 | 10.93 |
| 120 | 0.153 | 0.184 | 0.303 | 0.349 | 326 | 299 | 334 | 305 | 13.80 |
| 150 | 0.124 | 0.150 | 0.298 | 0.344 | 372 | 335 | 380 | 341 | 17.25 |
| 185 | 0.0991 | 0.120 | 0.291 | 0.338 | 428 | 377 | 437 | 383 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.285 | 0.331 | 506 | 434 | 515 | 438 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.279 | 0.325 | 578 | 485 | 586 | 488 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.278 | 0.324 | 663 | 542 | 668 | 542 | 41.20 |
| 500 | 0.0366 | 0.049 | 0.272 | 0.318 | 757 | 603 | 757 | 598 | 51.50 |
| 630 | 0.0283 | 0.040 | 0.265 | 0.311 | 858 | 665 | 852 | 654 | 64.89 |
| 800 | 0.0221 | 0.034 | 0.260 | 0.306 | 952 | 720 | 938 | 701 | 82.40 |
NYBY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.4 | 300 |
| 2.5 | 14.4 | 319 |
| 4 | 15.6 | 384 |
| 6 | 16.7 | 457 |
| 10 | 18.6 | 602 |
| 16 | 21.0 | 782 |
| 25 | 24.0 | 1,078 |
| 35 | 26.0 | 1,355 |
| 50 | 29.5 | 1,662 |
| 70 | 33.0 | 2,209 |
| 95 | 38.0 | 2,964 |
| 120 | 42.5 | 3,960 |
| 150 | 46.5 | 4,764 |
| 185 | 51.5 | 5,820 |
| 240 | 57.5 | 7,358 |
| 300 | 63.5 | 9,012 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 105 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 124 | 135 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 152 | 163 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 184 | 193 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 232 | 238 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 282 | 283 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 330 | 324 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 376 | 363 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 430 | 408 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 506 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 576 | 528 | 34.50 |
NYBY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.4 | 308 |
| 2.5 | 14.4 | 335 |
| 4 | 16.3 | 442 |
| 6 | 17.5 | 534 |
| 10 | 19.6 | 719 |
| 16 | 22.0 | 953 |
| 25 | 25.5 | 1,336 |
| 35 | 28.0 | 1,701 |
| 50 | 30.5 | 1,999 |
| 70 | 34.5 | 2,700 |
| 95 | 40.0 | 3,974 |
| 120 | 43.0 | 4,739 |
| 150 | 47.5 | 5,765 |
| 185 | 52.5 | 7,046 |
| 240 | 58.5 | 9,015 |
| 300 | 64.0 | 10,964 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 20 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 26 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 35 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 44 | 51 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 61 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 106 | 115 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 131 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 164 | 170 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 205 | 207 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 255 | 249 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 294 | 284 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 336 | 317 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 386 | 358 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 455 | 413 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 522 | 465 | 34.50 |
NYBY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.4 | 317 |
| 2.5 | 15.2 | 379 |
| 4 | 17.5 | 518 |
| 6 | 18.9 | 633 |
| 10 | 21.5 | 873 |
| 16 | 24.0 | 1,170 |
| 25 | 27.5 | 1,658 |
| 35 | 30.5 | 2,126 |
| 50 | 36.0 | 2,632 |
| 70 | 40.5 | 3,870 |
| 95 | 46.0 | 5,125 |
| 120 | 50.0 | 6,190 |
| 150 | 56.5 | 7,563 |
| 185 | 60.5 | 9,199 |
| 240 | 68.0 | 11,751 |
| 300 | 74.0 | 14,348 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 22 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 40 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 51 | 58 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 69 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 92 | 100 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 123 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 151 | 156 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 174 | 175 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 220 | 215 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 271 | 257 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 313 | 292 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 362 | 329 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 411 | 369 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 487 | 427 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 557 | 480 | 34.50 |
NYBY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 15.0 | 357 |
| 2.5 | 16.3 | 443 |
| 4 | 18.9 | 612 |
| 6 | 20.5 | 754 |
| 10 | 23.5 | 1,041 |
| 16 | 26.0 | 1,406 |
| 25 | 30.0 | 2,006 |
| 35 | 33.5 | 2,599 |
| 50 | 38.5 | 3,342 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 53 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 72 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 95 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 128 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 157 | 158 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 191 | 186 | 5.75 |
NYB(AL)Y 1 x (16-500) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 16.0 | 426 |
| 25 | 16.8 | 526 |
| 35 | 17.9 | 639 |
| 50 | 19.9 | 821 |
| 70 | 22.0 | 1,050 |
| 95 | 24.0 | 1,341 |
| 120 | 25.5 | 1,598 |
| 150 | 27.5 | 1,900 |
| 185 | 30.0 | 2,334 |
| 240 | 33.5 | 2,988 |
| 300 | 36.0 | 3,588 |
| 400 | 40.0 | 4,554 |
| 500 | 44.5 | 5,732 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 16 | 1.15 | 1.376 | 40 | 0.420 | 0.466 | 95 | 98 | 97 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.381 | 0.428 | 125 | 126 | 128 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 30 | 0.363 | 0.409 | 152 | 151 | 156 | 156 | 4.03 |
| 50 | 0.387 | 0.463 | 30 | 0.347 | 0.393 | 185 | 179 | 189 | 185 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.329 | 0.376 | 231 | 220 | 237 | 225 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.318 | 0.365 | 283 | 262 | 290 | 269 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.308 | 0.354 | 327 | 298 | 335 | 305 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.302 | 0.349 | 372 | 333 | 380 | 340 | 17.25 |
| 185 | 0.0991 | 0.120 | 20 | 0.296 | 0.342 | 428 | 375 | 437 | 382 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.288 | 0.335 | 506 | 432 | 514 | 437 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.283 | 0.329 | 578 | 483 | 585 | 486 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.281 | 0.327 | 662 | 540 | 666 | 540 | 41.20 |
| 500 | 0.0366 | 0.049 | 20 | 0.275 | 0.321 | 756 | 600 | 755 | 596 | 51.50 |
NYBY 2 x (6-300) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 6 | 17.3 | 495 |
| 10 | 19.2 | 647 |
| 16 | 21.5 | 836 |
| 25 | 24.5 | 1,145 |
| 35 | 27.0 | 1,433 |
| 50 | 30.0 | 1,716 |
| 70 | 34.0 | 2,271 |
| 95 | 38.5 | 3,039 |
| 120 | 43.0 | 4,043 |
| 150 | 47.5 | 4,877 |
| 185 | 52.5 | 5,951 |
| 240 | 58.5 | 7,504 |
| 300 | 64.5 | 9,180 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 6 | 3.08 | 3.685 | 50 | 0.288 | 48 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 66 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 90 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 120 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 150 | 160 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 180 | 187 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 230 | 230 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 275 | 280 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 320 | 320 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 375 | 355 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 430 | 409 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 510 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 590 | 525 | 34.50 |
NYBY 3 x (4-400) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 4 | 16.9 | 476 |
| 6 | 18.1 | 572 |
| 10 | 20.5 | 764 |
| 16 | 22.5 | 1,006 |
| 25 | 26.0 | 1,401 |
| 35 | 28.5 | 1,776 |
| 50 | 31.5 | 2,056 |
| 70 | 35.0 | 2,766 |
| 95 | 41.0 | 4,051 |
| 120 | 43.5 | 4,823 |
| 150 | 48.5 | 5,883 |
| 185 | 53.0 | 7,153 |
| 240 | 59.5 | 9,142 |
| 300 | 65.0 | 11,131 |
| 400 | 71.5 | 13,916 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 280 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYBY 4 x (2.5-400) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 2.5 | 15.8 | 410 |
| 4 | 18.2 | 555 |
| 6 | 19.5 | 674 |
| 10 | 22.0 | 921 |
| 16 | 24.5 | 1,226 |
| 25 | 28.0 | 1,727 |
| 35 | 31.0 | 2,219 |
| 50 | 36.5 | 2,702 |
| 70 | 41.5 | 3,967 |
| 95 | 47.0 | 5,236 |
| 120 | 51.0 | 6,316 |
| 150 | 57.0 | 7,680 |
| 185 | 61.5 | 9,357 |
| 240 | 68.5 | 11,898 |
| 300 | 75.0 | 14,509 |
| 400 | 84.5 | 18,313 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 280 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYBY 5 x (4-50) mm2 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 4 | 19.5 | 652 |
| 6 | 21.5 | 798 |
| 10 | 24.0 | 1,092 |
| 16 | 26.5 | 1,466 |
| 25 | 31.0 | 2,080 |
| 35 | 34.5 | 2,700 |
| 50 | 40.5 | 3,805 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.463 | 40 | 0.247 | 160 | 165 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NYBY