NYBY

Cu / PVC / ATA / PVC
0.6/1 kV IEC 60502-1

Deskripsi

Copper Conductor, PVC Insulated, Aluminium Tape Armor, PVC Sheathed

Aplikasi

  • For installation indoors, cable channels and in ground, for industry installations, switchgear, and power station, if there is a risk that low mechanical damage may occur

Susunan lapisan NYBY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / ATA / PVC.

Penampang konstruksi kabel NYBY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi PVC

    Polyvinyl chloride

    Isolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.

  3. 3

    Perisai pita aluminium (ATA)

    Aluminium tape armour

    Perisai non-magnetik — dipakai pada kabel inti tunggal agar tidak timbul rugi induksi.

  4. 4

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Spesifikasi Teknis

IEC 60502-1

NYB(AL)Y 1 x (16-800) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 15.4 396
25 16.2 497
35 17.3 608
50 19.3 785
70 21.5 1,011
95 23.5 1,298
120 25.0 1,552
150 27.0 1,850
185 29.5 2,279
240 32.5 2,926
300 35.5 3,521
400 39.5 4,476
500 43.5 5,645
630 48.0 7,190
800 53.0 8,941
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
16 1.15 1.376 0.412 0.458 94 98 97 101 1.84
25 0.727 0.870 0.374 0.420 124 127 127 131 2.88
35 0.524 0.627 0.356 0.402 151 152 155 156 4.03
50 0.387 0.463 0.341 0.387 184 180 189 185 5.75
70 0.268 0.321 0.324 0.370 230 221 236 226 8.05
95 0.193 0.232 0.313 0.359 282 264 289 269 10.93
120 0.153 0.184 0.303 0.349 326 299 334 305 13.80
150 0.124 0.150 0.298 0.344 372 335 380 341 17.25
185 0.0991 0.120 0.291 0.338 428 377 437 383 21.28
240 0.0754 0.093 0.285 0.331 506 434 515 438 27.60
300 0.0601 0.075 0.279 0.325 578 485 586 488 34.50
400 0.0470 0.060 0.278 0.324 663 542 668 542 41.20
500 0.0366 0.049 0.272 0.318 757 603 757 598 51.50
630 0.0283 0.040 0.265 0.311 858 665 852 654 64.89
800 0.0221 0.034 0.260 0.306 952 720 938 701 82.40

NYBY 2 x (1.5-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 14.4 300
2.5 14.4 319
4 15.6 384
6 16.7 457
10 18.6 602
16 21.0 782
25 24.0 1,078
35 26.0 1,355
50 29.5 1,662
70 33.0 2,209
95 38.0 2,964
120 42.5 3,960
150 46.5 4,764
185 51.5 5,820
240 57.5 7,358
300 63.5 9,012
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 14.478 0.340 23 27 0.17
2.5 7.41 8.866 0.304 31 36 0.29
4 4.61 5.516 0.303 41 48 0.46
6 3.08 3.685 0.288 52 60 0.69
10 1.83 2.190 0.269 71 81 1.15
16 1.15 1.376 0.255 94 105 1.84
25 0.727 0.870 0.255 124 135 2.88
35 0.524 0.627 0.246 152 163 4.03
50 0.387 0.464 0.247 184 193 5.75
70 0.268 0.321 0.238 232 238 8.05
95 0.193 0.232 0.238 282 283 10.93
120 0.153 0.184 0.233 330 324 13.80
150 0.124 0.150 0.233 376 363 17.25
185 0.0991 0.121 0.233 430 408 21.28
240 0.0754 0.093 0.232 506 472 27.60
300 0.0601 0.075 0.231 576 528 34.50

NYBY 3 x (1.5-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 14.4 308
2.5 14.4 335
4 16.3 442
6 17.5 534
10 19.6 719
16 22.0 953
25 25.5 1,336
35 28.0 1,701
50 30.5 1,999
70 34.5 2,700
95 40.0 3,974
120 43.0 4,739
150 47.5 5,765
185 52.5 7,046
240 58.5 9,015
300 64.0 10,964
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 14.478 0.340 20 23 0.17
2.5 7.41 8.866 0.304 26 31 0.29
4 4.61 5.516 0.303 35 41 0.46
6 3.08 3.685 0.288 44 51 0.69
10 1.83 2.190 0.269 61 69 1.15
16 1.15 1.376 0.255 80 89 1.84
25 0.727 0.870 0.255 106 115 2.88
35 0.524 0.627 0.246 131 138 4.03
50 0.387 0.464 0.247 164 170 5.75
70 0.268 0.321 0.238 205 207 8.05
95 0.193 0.232 0.238 255 249 10.93
120 0.153 0.184 0.233 294 284 13.80
150 0.124 0.150 0.233 336 317 17.25
185 0.0991 0.121 0.233 386 358 21.28
240 0.0754 0.093 0.232 455 413 27.60
300 0.0601 0.075 0.231 522 465 34.50

NYBY 4 x (1.5-300) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 14.4 317
2.5 15.2 379
4 17.5 518
6 18.9 633
10 21.5 873
16 24.0 1,170
25 27.5 1,658
35 30.5 2,126
50 36.0 2,632
70 40.5 3,870
95 46.0 5,125
120 50.0 6,190
150 56.5 7,563
185 60.5 9,199
240 68.0 11,751
300 74.0 14,348
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 14.478 0.328 22 27 0.17
2.5 7.41 8.866 0.304 30 36 0.29
4 4.61 5.516 0.303 40 47 0.46
6 3.08 3.685 0.288 51 58 0.69
10 1.83 2.190 0.269 69 78 1.15
16 1.15 1.376 0.255 92 100 1.84
25 0.727 0.870 0.255 123 130 2.88
35 0.524 0.627 0.246 151 156 4.03
50 0.387 0.464 0.247 174 175 5.75
70 0.268 0.321 0.238 220 215 8.05
95 0.193 0.232 0.238 271 257 10.93
120 0.153 0.184 0.233 313 292 13.80
150 0.124 0.150 0.233 362 329 17.25
185 0.0991 0.121 0.233 411 369 21.28
240 0.0754 0.093 0.232 487 427 27.60
300 0.0601 0.075 0.231 557 480 34.50

NYBY 5 x (1.5-50) mm² 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 15.0 357
2.5 16.3 443
4 18.9 612
6 20.5 754
10 23.5 1,041
16 26.0 1,406
25 30.0 2,006
35 33.5 2,599
50 38.5 3,342
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 14.478 0.328 23 28 0.17
2.5 7.41 8.866 0.304 31 36 0.29
4 4.61 5.516 0.303 42 48 0.46
6 3.08 3.685 0.288 53 59 0.69
10 1.83 2.190 0.269 72 79 1.15
16 1.15 1.376 0.255 95 102 1.84
25 0.727 0.870 0.255 128 132 2.88
35 0.524 0.627 0.246 157 158 4.03
50 0.387 0.464 0.247 191 186 5.75
SPLN 43-3

NYB(AL)Y 1 x (16-500) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 16.0 426
25 16.8 526
35 17.9 639
50 19.9 821
70 22.0 1,050
95 24.0 1,341
120 25.5 1,598
150 27.5 1,900
185 30.0 2,334
240 33.5 2,988
300 36.0 3,588
400 40.0 4,554
500 44.5 5,732
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Insulation Insulation Resistance at 20°C Min. (M.Ω.km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
16 1.15 1.376 40 0.420 0.466 95 98 97 101 1.84
25 0.727 0.870 40 0.381 0.428 125 126 128 130 2.88
35 0.524 0.627 30 0.363 0.409 152 151 156 156 4.03
50 0.387 0.463 30 0.347 0.393 185 179 189 185 5.75
70 0.268 0.321 30 0.329 0.376 231 220 237 225 8.05
95 0.193 0.232 30 0.318 0.365 283 262 290 269 10.93
120 0.153 0.184 30 0.308 0.354 327 298 335 305 13.80
150 0.124 0.150 20 0.302 0.349 372 333 380 340 17.25
185 0.0991 0.120 20 0.296 0.342 428 375 437 382 21.28
240 0.0754 0.093 20 0.288 0.335 506 432 514 437 27.60
300 0.0601 0.075 20 0.283 0.329 578 483 585 486 34.50
400 0.0470 0.060 20 0.281 0.327 662 540 666 540 41.20
500 0.0366 0.049 20 0.275 0.321 756 600 755 596 51.50

NYBY 2 x (6-300) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
6 17.3 495
10 19.2 647
16 21.5 836
25 24.5 1,145
35 27.0 1,433
50 30.0 1,716
70 34.0 2,271
95 38.5 3,039
120 43.0 4,043
150 47.5 4,877
185 52.5 5,951
240 58.5 7,504
300 64.5 9,180
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Insulation Insulation Resistance at 20°C Min. (M.Ω.km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
6 3.08 3.685 50 0.288 48 59 0.69
10 1.83 2.190 50 0.269 66 78 1.15
16 1.15 1.376 40 0.255 90 102 1.84
25 0.727 0.870 40 0.255 120 134 2.88
35 0.524 0.627 40 0.246 150 160 4.03
50 0.387 0.464 30 0.247 180 187 5.75
70 0.268 0.321 30 0.238 230 230 8.05
95 0.193 0.232 30 0.238 275 280 10.93
120 0.153 0.184 30 0.233 320 320 13.80
150 0.124 0.150 20 0.233 375 355 17.25
185 0.0991 0.121 20 0.233 430 409 21.28
240 0.0754 0.093 20 0.232 510 472 27.60
300 0.0601 0.075 20 0.231 590 525 34.50

NYBY 3 x (4-400) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
4 16.9 476
6 18.1 572
10 20.5 764
16 22.5 1,006
25 26.0 1,401
35 28.5 1,776
50 31.5 2,056
70 35.0 2,766
95 41.0 4,051
120 43.5 4,823
150 48.5 5,883
185 53.0 7,153
240 59.5 9,142
300 65.0 11,131
400 71.5 13,916
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Insulation Insulation Resistance at 20°C Min. (M.Ω.km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
4 4.61 5.516 50 0.303 34 41 0.46
6 3.08 3.685 50 0.288 44 52 0.69
10 1.83 2.190 50 0.269 60 69 1.15
16 1.15 1.376 40 0.255 80 89 1.84
25 0.727 0.870 40 0.255 105 116 2.88
35 0.524 0.627 40 0.246 130 138 4.03
50 0.387 0.464 30 0.247 160 165 5.75
70 0.268 0.321 30 0.238 200 205 8.05
95 0.193 0.232 30 0.238 245 245 10.93
120 0.153 0.184 30 0.233 285 280 13.80
150 0.124 0.150 20 0.233 325 315 17.25
185 0.0991 0.121 20 0.233 370 355 21.28
240 0.0754 0.093 20 0.232 435 415 27.60
300 0.0601 0.075 20 0.231 500 465 34.50
400 0.0470 0.060 20 0.229 600 535 41.20

NYBY 4 x (2.5-400) mm2 0.6/1 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
2.5 15.8 410
4 18.2 555
6 19.5 674
10 22.0 921
16 24.5 1,226
25 28.0 1,727
35 31.0 2,219
50 36.5 2,702
70 41.5 3,967
95 47.0 5,236
120 51.0 6,316
150 57.0 7,680
185 61.5 9,357
240 68.5 11,898
300 75.0 14,509
400 84.5 18,313
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Insulation Insulation Resistance at 20°C Min. (M.Ω.km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
2.5 7.41 8.866 50 0.304 25 32 0.29
4 4.61 5.516 50 0.303 34 41 0.46
6 3.08 3.685 50 0.288 44 52 0.69
10 1.83 2.190 50 0.269 60 69 1.15
16 1.15 1.376 40 0.255 80 89 1.84
25 0.727 0.870 40 0.255 105 116 2.88
35 0.524 0.627 40 0.246 130 138 4.03
50 0.387 0.464 30 0.247 160 165 5.75
70 0.268 0.321 30 0.238 200 205 8.05
95 0.193 0.232 30 0.238 245 245 10.93
120 0.153 0.184 30 0.233 285 280 13.80
150 0.124 0.150 20 0.233 325 315 17.25
185 0.0991 0.121 20 0.233 370 355 21.28
240 0.0754 0.093 20 0.232 435 415 27.60
300 0.0601 0.075 20 0.231 500 465 34.50
400 0.0470 0.060 20 0.229 600 535 41.20

NYBY 5 x (4-50) mm2 0.6/1 kV

Data Konstruksi
om. ross ection Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
4 19.5 652
6 21.5 798
10 24.0 1,092
16 26.5 1,466
25 31.0 2,080
35 34.5 2,700
50 40.5 3,805
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 70°C Max. (Ω/km) Insulation Insulation Resistance at 20°C Min. (M.Ω.km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
4 4.61 5.516 50 0.303 34 41 0.46
6 3.08 3.685 50 0.288 44 52 0.69
10 1.83 2.190 50 0.269 60 69 1.15
16 1.15 1.376 40 0.255 80 89 1.84
25 0.727 0.870 40 0.255 105 116 2.88
35 0.524 0.627 40 0.246 130 138 4.03
50 0.387 0.463 40 0.247 160 165 5.75

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.