NYCY
Cu / PVC / CWS / PVC Deskripsi
Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed
Aplikasi
- For insallation in the ground, indoors, cable trunking and outdoors if subsequent mechanical damage is likely. For urban networks, household feeders and street lighting
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYCY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / CWS / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Pelindung kawat tembaga (CWS)
Copper wire screenLayar metalik — jalur balik arus gangguan & pemerataan medan listrik.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYCY.
Spesifikasi Teknis
NYCY 1 x (1.5-800) mm2 0.6/1 kV
| N Cr Se | o o ct re | m. ss ion � | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|---|---|
| A m | m | a | mm | kg/km |
| 1.5 | / | 1.5 | 9.9 | 121 |
| 2.5 | / | 2.5 | 10.4 | 143 |
| 4 | / | 4 | 11.4 | 188 |
| 6 | / | 6 | 11.9 | 233 |
| 10 | / | 10 | 12.9 | 324 |
| 16 | / | 16 | 14.4 | 456 |
| 25 | / | 16 | 16.1 | 582 |
| 35 | / | 16 | 17.2 | 687 |
| 50 | / | 25 | 19.7 | 943 |
| 70 | / | 35 | 22.0 | 1,259 |
| 95 | / | 50 | 24.5 | 1,678 |
| 120 | / | 70 | 27.0 | 2,122 |
| 150 | / | 70 | 28.5 | 2,410 |
| 185 | / | 95 | 31.5 | 3,049 |
| 240 | / | 120 | 35.0 | 3,898 |
| 300 | / | 150 | 38.0 | 4,778 |
| 400 | / | 185 | 43.0 | 6,031 |
| 500 | / | 240 | 47.5 | 7,689 |
| 630 | / | 300 | 52.5 | 9,778 |
| 800 | / | 400 | 58.5 | 12,427 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 / 1.5 | 12.1 | 14.478 | 0.555 | 0.601 | 24 | 27 | 24 | 28 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 0.514 | 0.561 | 31 | 35 | 32 | 36 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 0.485 | 0.531 | 41 | 46 | 42 | 47 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 0.457 | 0.503 | 52 | 57 | 53 | 59 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 0.420 | 0.466 | 70 | 76 | 72 | 78 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 0.399 | 0.445 | 94 | 99 | 96 | 101 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 0.373 | 0.419 | 124 | 127 | 127 | 130 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 0.355 | 0.401 | 151 | 152 | 155 | 156 | 4.03 |
| 50 / 25 | 0.387 | 0.463 | 0.345 | 0.391 | 185 | 181 | 190 | 185 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 0.329 | 0.375 | 232 | 221 | 237 | 226 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 0.322 | 0.368 | 284 | 263 | 290 | 267 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 0.316 | 0.363 | 329 | 297 | 334 | 300 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 0.310 | 0.357 | 373 | 331 | 378 | 333 | 17.25 |
| 185 / 95 | 0.0991 | 0.120 | 0.305 | 0.351 | 426 | 368 | 429 | 368 | 21.28 |
| 240 / 120 | 0.0754 | 0.092 | 0.298 | 0.344 | 495 | 416 | 495 | 412 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 0.294 | 0.340 | 555 | 455 | 550 | 447 | 34.50 |
| 400 / 185 | 0.0470 | 0.060 | 0.293 | 0.339 | 624 | 497 | 615 | 485 | 41.20 |
| 500 / 240 | 0.0366 | 0.048 | 0.289 | 0.335 | 694 | 537 | 684 | 523 | 51.50 |
| 630 / 300 | 0.0283 | 0.039 | 0.281 | 0.328 | 771 | 578 | 761 | 565 | 64.89 |
| 800 / 400 | 0.0221 | 0.033 | 0.281 | 0.327 | 853 | 621 | 851 | 613 | 82.40 |
NYCY 2 x (1.5-300) mm2 0.6/1 kV
| N Cr Se | o o ct re | m. ss ion | Overall Diameter approx. | Cable Weight approx. | Applicatio For insalla trunking an damage is feeders an |
|---|---|---|---|---|---|
| A | a | ||||
| m | m | � | mm | kg/km | |
| Special Fe | |||||
| 1.5 | / | 1.5 | 13.4 | 214 | • Fire Res |
| 2.5 | / | 2.5 | 14.3 | 258 | • Oil Resi |
| • UV Res | |||||
| 4 | / | 4 | 16.3 | 351 | • Flame R |
| 6 | / | 6 | 17.4 | 436 | • Flame R |
| • Heat Re | |||||
| 10 | / | 10 | 19.4 | 607 | |
| • Anti Ter | |||||
| 16 | / | 16 | 22.0 | 837 | • Anti Rod |
| 25 | / | 16 | 25.0 | 1,115 | • Low Sm |
| 35 | / | 16 | 27.5 | 1,379 | |
| 50 | / | 25 | 31.0 | 1,754 | |
| Conducto | |||||
| 70 | / | 35 | 34.5 | 2,368 | |
| 1.5 - 10 sq | |||||
| 95 | / | 50 | 39.5 | 3,224 | conductor |
| 120 | / | 70 | 43.5 | 4,005 | 16 sqmm |
| 25 - 300 sq | |||||
| 150 | / | 70 | 47.5 | 4,745 | |
| 185 | / | 95 | 52.5 | 5,974 | Standard |
| 1.5 - 95 sq | |||||
| 240 | / | 120 | 59.5 | 7,666 | |
| 120 - 300 | |||||
| 300 | / | 150 | 65.5 | 9,478 | Length Tol |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 0.328 | 24 | 28 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 0.304 | 31 | 37 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 0.288 | 53 | 60 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 0.269 | 72 | 81 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 0.255 | 96 | 106 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 0.255 | 126 | 136 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 0.246 | 154 | 164 | 4.03 |
| 50 / 25 | 0.387 | 0.464 | 0.247 | 187 | 194 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 0.238 | 234 | 239 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 0.238 | 285 | 284 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 0.233 | 332 | 324 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 0.233 | 377 | 362 | 17.25 |
| 185 / 95 | 0.0991 | 0.121 | 0.233 | 429 | 405 | 21.28 |
| 240 / 120 | 0.0754 | 0.093 | 0.232 | 503 | 466 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 0.231 | 568 | 517 | 34.50 |
NYCY 3 x (1.5-300) mm2 0.6/1 kV
| N Cr Se | o o ct re | m. ss ion | Overall Diameter approx. | Cable Weight approx. | Applicatio For insalla trunking an damage is l feeders and |
|---|---|---|---|---|---|
| A | a | ||||
| m | m | � | mm | kg/km | |
| Special Fe | |||||
| 1.5 | / | 1.5 | 13.9 | 242 | • Fire Res |
| 2.5 | / | 2.5 | 14.9 | 298 | • Oil Resis |
| • UV Resi | |||||
| 4 | / | 4 | 17.0 | 405 | • Flame R |
| 6 | / | 6 | 18.2 | 509 | • Flame R |
| • Heat Re | |||||
| 10 | / | 10 | 20.5 | 719 | |
| • Anti Term | |||||
| 16 | / | 16 | 23.0 | 1,001 | • Anti Rod |
| 25 | / | 16 | 26.5 | 1,365 | • Low Sm |
| 35 | / | 16 | 29.0 | 1,716 | |
| 50 | / | 25 | 32.5 | 2,089 | |
| Conductor | |||||
| 70 | / | 35 | 35.5 | 2,856 | |
| 1.5 - 10 sqm | |||||
| 95 | / | 50 | 40.5 | 3,865 | conductor s |
| 120 | / | 70 | 44.0 | 4,787 | 16 sqmm s |
| 25 - 35 sqm | |||||
| 150 | / | 70 | 48.5 | 5,742 | 50 - 300 sq |
| 185 | / | 95 | 53.5 | 7,177 | |
| Standard P | |||||
| 240 | / | 120 | 60.0 | 9,295 | |
| 1.5 - 95 sqm | |||||
| 300 | / | 150 | 66.0 | 11,468 | 120 - 300 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 0.328 | 20 | 24 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 0.304 | 27 | 31 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 0.303 | 35 | 41 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 0.288 | 45 | 51 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 0.269 | 61 | 69 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 0.255 | 82 | 90 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 0.255 | 108 | 115 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 0.246 | 132 | 139 | 4.03 |
| 50 / 25 | 0.387 | 0.464 | 0.247 | 167 | 171 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 0.238 | 208 | 208 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 0.238 | 255 | 250 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 0.233 | 296 | 284 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 0.233 | 337 | 317 | 17.25 |
| 185 / 95 | 0.0991 | 0.121 | 0.233 | 386 | 356 | 21.28 |
| 240 / 120 | 0.0754 | 0.093 | 0.232 | 454 | 409 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 0.231 | 516 | 456 | 34.50 |
NYCY 4 x (1.5-300) mm2 0.6/1 kV
| N Cr Se | o o ct re | m. ss ion | Overall Diameter approx. | Cable Weight approx. | Applicatio For insalla trunking an damage is feeders an |
|---|---|---|---|---|---|
| A | a | ||||
| m | m | � | mm | kg/km | |
| Special Fe | |||||
| 1.5 | / | 1.5 | 14.8 | 275 | • Fire Res |
| 2.5 | / | 2.5 | 15.9 | 344 | • Oil Resi |
| • UV Res | |||||
| 4 | / | 4 | 18.3 | 474 | • Flame R |
| 6 | / | 6 | 19.6 | 600 | • Flame R |
| • Heat Re | |||||
| 10 | / | 10 | 22.0 | 863 | |
| • Anti Ter | |||||
| 16 | / | 16 | 25.0 | 1,207 | • Anti Rod |
| 25 | / | 16 | 29.0 | 1,674 | • Low Sm |
| 35 | / | 16 | 31.0 | 2,120 | |
| 50 | / | 25 | 37.0 | 2,686 | |
| Conducto | |||||
| 70 | / | 35 | 40.5 | 3,628 | |
| 1.5 - 10 sq | |||||
| 95 | / | 50 | 46.5 | 4,923 | conductor |
| 120 | / | 70 | 51.0 | 6,128 | 16 sqmm |
| 25 - 35 sqm | |||||
| 150 | / | 70 | 57.5 | 7,406 | 50 - 300 sq |
| 185 | / | 95 | 62.0 | 9,227 | |
| Standard | |||||
| 240 | / | 120 | 69.5 | 11,890 | |
| 1.5 - 70 sq | |||||
| 300 | / | 150 | 76.0 | 14,669 | 95 - 300 s |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 0.328 | 23 | 28 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 0.303 | 41 | 47 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 0.269 | 70 | 78 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 0.255 | 93 | 101 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 0.255 | 125 | 130 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 0.246 | 152 | 156 | 4.03 |
| 50 / 25 | 0.387 | 0.464 | 0.247 | 176 | 175 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 0.238 | 220 | 214 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 0.238 | 272 | 257 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 0.233 | 315 | 292 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 0.233 | 363 | 328 | 17.25 |
| 185 / 95 | 0.0991 | 0.121 | 0.233 | 410 | 366 | 21.28 |
| 240 / 120 | 0.0754 | 0.093 | 0.232 | 484 | 421 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 0.231 | 550 | 469 | 34.50 |
NYCY 5 x (1.5-50) mm2 0.6/1 kV
| N Cr Se | o o ct re | m. ss ion | Overall Diameter approx. | Cable Weight approx. | Applicatio For insalla trunking an damage is feeders and |
|---|---|---|---|---|---|
| A | a | ||||
| m | m | � | mm | kg/km | |
| Special Fe | |||||
| 1.5 | / | 1.5 | 15.7 | 323 | • Fire Res |
| 2.5 | / | 2.5 | 17.0 | 401 | • Oil Resis |
| • UV Resi | |||||
| 4 | / | 4 | 19.6 | 560 | • Flame R |
| 6 | / | 6 | 21.5 | 712 | • Flame R |
| • Heat Re | |||||
| 10 | / | 10 | 24.0 | 1,020 | |
| • Anti Term | |||||
| 16 | / | 16 | 27.0 | 1,431 | • Anti Rod |
| 25 | / | 16 | 31.5 | 2,007 | • Low Sm |
| 35 | / | 16 | 34.0 | 2,576 | |
| 50 | / | 25 | 39.5 | 3,380 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 0.328 | 24 | 28 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 0.304 | 31 | 37 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 0.288 | 53 | 60 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 0.269 | 73 | 79 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 0.255 | 97 | 103 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 0.255 | 129 | 132 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 0.246 | 158 | 158 | 4.03 |
| 50 / 25 | 0.387 | 0.464 | 0.247 | 192 | 186 | 5.75 |
NYCY 1x (1.5-500) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 /1.5 | 10.6 | 137 |
| 2.5 / 2.5 | 11.0 | 160 |
| 4 / 4 | 12.0 | 208 |
| 6 / 6 | 12.5 | 254 |
| 10 / 10 | 13.5 | 347 |
| 16 / 16 | 15.0 | 481 |
| 25 / 16 | 16.7 | 610 |
| 35 / 16 | 17.8 | 718 |
| 50 / 25 | 20.5 | 979 |
| 70 / 35 | 22.5 | 1,298 |
| 95 / 50 | 25.0 | 1,722 |
| 120 / 70 | 27.5 | 2,170 |
| 150 / 70 | 29.5 | 2,462 |
| 185 / 95 | 32.0 | 3,107 |
| 40 / 120 | 35.5 | 3,979 |
| 00 / 150 | 39.0 | 4,866 |
| 00 / 185 | 43.5 | 6,134 |
| 00 / 240 | 48.5 | 7,825 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance Trefoil formatio (mH/km | Flat n formation ) (mH/km) | Current - Carrying Capacity at 30° C in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.5 / 1.5 | 12.1 | 14.478 | 50 | 0.567 | 0.613 | 24 | 27 | 24 | 28 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 50 | 0.526 | 0.572 | 31 | 35 | 32 | 36 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 50 | 0.496 | 0.542 | 42 | 45 | 42 | 47 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 50 | 0.467 | 0.513 | 52 | 57 | 54 | 59 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 50 | 0.429 | 0.475 | 71 | 76 | 73 | 78 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 40 | 0.407 | 0.453 | 94 | 98 | 97 | 101 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 40 | 0.380 | 0.426 | 125 | 126 | 128 | 130 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 40 | 0.362 | 0.408 | 152 | 151 | 156 | 156 | 4.03 |
| 50 / 25 | 0.387 | 0.463 | 30 | 0.351 | 0.397 | 186 | 180 | 191 | 185 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 30 | 0.335 | 0.381 | 233 | 220 | 238 | 225 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 30 | 0.327 | 0.373 | 285 | 261 | 291 | 267 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 30 | 0.321 | 0.367 | 329 | 295 | 334 | 299 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 20 | 0.315 | 0.361 | 373 | 329 | 378 | 332 | 17.25 |
| 185 / 95 | 0.0991 | 0.120 | 20 | 0.309 | 0.355 | 425 | 366 | 428 | 367 | 21.28 |
| 240 / 120 | 0.0754 | 0.092 | 20 | 0.302 | 0.349 | 494 | 413 | 493 | 410 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 20 | 0.298 | 0.344 | 553 | 451 | 548 | 445 | 34.50 |
| 400 / 185 | 0.0470 | 0.060 | 20 | 0.297 | 0.343 | 621 | 493 | 613 | 483 | 41.20 |
| 500 / 240 | 0.0366 | 0.048 | 20 | 0.293 | 0.339 | 690 | 532 | 680 | 520 | 51.50 |
NYCY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 / 1.5 | 14.0 | 241 |
| 2.5 / 2.5 | 15.0 | 287 |
| 4 / 4 | 16.9 | 387 |
| 6 / 6 | 18.0 | 476 |
| 10 / 10 | 20.0 | 653 |
| 16 / 16 | 22.5 | 892 |
| 25 / 16 | 25.5 | 1,183 |
| 35 / 16 | 28.0 | 1,458 |
| 50 / 25 | 32.0 | 1,811 |
| 70 / 35 | 35.5 | 2,448 |
| 95 / 50 | 40.5 | 3,319 |
| 120 / 70 | 44.5 | 4,110 |
| 150 / 70 | 48.5 | 4,860 |
| 185 / 95 | 53.5 | 6,106 |
| 40 / 120 | 60.0 | 7,815 |
| 00 / 150 | 66.0 | 9,650 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 / 1.5 | 12.1 | 0.46 | 50 | 0.328 | 21 | 27 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 50 | 0.304 | 29 | 36 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 50 | 0.303 | 38 | 47 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 50 | 0.288 | 48 | 59 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 50 | 0.269 | 66 | 78 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 40 | 0.255 | 90 | 102 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 40 | 0.255 | 120 | 134 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 40 | 0.246 | 150 | 180 | 4.03 |
| 50 / 25 | 0.387 | 0.464 | 30 | 0.247 | 180 | 210 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 30 | 0.238 | 230 | 260 | 8.05 |
| 95 / 50 | 0.193 | 0.232 | 30 | 0.238 | 280 | 315 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 30 | 0.233 | 320 | 320 | 13.80 |
| 150 / 70 | 0.124 | 0.150 | 20 | 0.233 | 375 | 355 | 17.25 |
| 185 / 95 | 0.0991 | 0.121 | 20 | 0.233 | 430 | 409 | 21.28 |
| 240 / 120 | 0.0754 | 0.093 | 20 | 0.232 | 510 | 472 | 27.60 |
| 300 / 150 | 0.0601 | 0.075 | 20 | 0.231 | 590 | 525 | 34.50 |
NYCY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 / 1.5 | 14.5 | 269 |
| 2.5 / 2.5 | 15.6 | 328 |
| 4 / 4 | 17.7 | 441 |
| 6 / 6 | 18.9 | 548 |
| 10 / 10 | 21.0 | 765 |
| 16 / 16 | 24.0 | 1,055 |
| 25 / 16 | 27.0 | 1,431 |
| 35 / 16 | 29.5 | 1,792 |
| 50 / 25 | 33.0 | 2,148 |
| 70 / 35 | 36.5 | 2,924 |
| 95 / 50 | 41.0 | 3,962 |
| 120 / 70 | 45.0 | 4,891 |
| 150 / 70 | 49.5 | 5,863 |
| 185 / 95 | 54.0 | 7,310 |
| 40 / 120 | 61.0 | 9,451 |
| 00 / 150 | 67.0 | 11,703 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 50 | 0.328 | 18 | 24 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 / 25 | 0.387 | 0.463 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 / 50 | 0.193 | 0.231 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 30 | 0.233 | 285 | 285 | 13.80 |
| 150 / 70 | 0.124 | 0.149 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 / 95 | 0.0991 | 0.120 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 / 120 | 0.0754 | 0.091 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 / 150 | 0.0601 | 0.073 | 20 | 0.231 | 500 | 465 | 34.50 |
NYCY 2 x (1.5-300) mm² 0.6/1 kV — tabel lanjutan (2)
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 / 1.5 | 15.4 | 304 |
| 2.5 / 2.5 | 16.5 | 376 |
| 4 / 4 | 18.9 | 512 |
| 6 / 6 | 20.5 | 642 |
| 10 / 10 | 23.0 | 912 |
| 16 / 16 | 25.5 | 1,265 |
| 25 / 16 | 29.5 | 1,744 |
| 35 / 16 | 31.5 | 2,200 |
| 50 / 25 | 37.5 | 2,757 |
| 70 / 35 | 41.0 | 3,707 |
| 95 / 50 | 47.0 | 5,034 |
| 120 / 70 | 52.0 | 6,254 |
| 150 / 70 | 58.0 | 7,549 |
| 185 / 95 | 62.0 | 9,328 |
| 40 / 120 | 70.5 | 12,071 |
| 00 / 150 | 76.5 | 14,867 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 50 | 0.328 | 18 | 24 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 / 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 / 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 / 16 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 / 16 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 / 25 | 0.387 | 0.463 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 / 35 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 / 50 | 0.193 | 0.231 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 / 70 | 0.153 | 0.184 | 30 | 0.233 | 285 | 285 | 13.80 |
| 150 / 70 | 0.124 | 0.149 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 / 95 | 0.0991 | 0.119 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 / 120 | 0.0754 | 0.091 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 / 150 | 0.0601 | 0.073 | 20 | 0.231 | 500 | 465 | 34.50 |
NYCY 5 x (1.5-6) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 / 1.5 | 16.4 | 353 |
| 2.5 / 2.5 | 17.6 | 435 |
| 4 / 4 | 20.5 | 601 |
| 6 / 6 | 22.0 | 757 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 / 1.5 | 12.1 | 14.478 | 50 | 0.328 | 15 | 19 | 0.17 |
| 2.5 / 2.5 | 7.41 | 8.866 | 50 | 0.304 | 21 | 26 | 0.29 |
| 4 / 4 | 4.61 | 5.516 | 50 | 0.303 | 27 | 34 | 0.46 |
| 6 / 6 | 3.08 | 3.685 | 50 | 0.288 | 37 | 42 | 0.69 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NYCY
Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.