NYFGbY
Cu / PVC / SFWA / PVC Deskripsi
Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed
Aplikasi
- For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYFGbY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / SFWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Perisai kawat baja pipih (SFWA)
Steel flat-wire armourProteksi mekanis berat — penanaman langsung & tarikan panjang.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYFGbY.
Spesifikasi Teknis
NYFGbY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 611 |
| 2.5 | 18.0 | 630 |
| 4 | 17.8 | 648 |
| 6 | 18.1 | 687 |
| 10 | 20.5 | 881 |
| 16 | 22.5 | 1,085 |
| 25 | 25.5 | 1,428 |
| 35 | 27.5 | 1,753 |
| 50 | 31.0 | 2,120 |
| 70 | 35.0 | 2,716 |
| 95 | 39.5 | 3,528 |
| 120 | 43.0 | 4,177 |
| 150 | 47.0 | 5,012 |
| 185 | 52.0 | 6,116 |
| 240 | 58.0 | 7,695 |
| 300 | 64.0 | 9,384 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 53 | 61 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 73 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 96 | 106 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 136 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 164 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 186 | 194 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 235 | 239 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 286 | 284 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 331 | 324 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 377 | 364 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 430 | 408 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 507 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 577 | 530 | 34.50 |
NYFGbY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.8 | 620 |
| 2.5 | 18.0 | 648 |
| 4 | 18.0 | 681 |
| 6 | 19.0 | 789 |
| 10 | 21.5 | 997 |
| 16 | 23.5 | 1,280 |
| 25 | 27.0 | 1,709 |
| 35 | 29.5 | 2,123 |
| 50 | 32.0 | 2,444 |
| 70 | 36.0 | 3,217 |
| 95 | 40.5 | 4,171 |
| 120 | 43.5 | 4,957 |
| 150 | 48.0 | 6,011 |
| 185 | 52.5 | 7,319 |
| 240 | 59.0 | 9,324 |
| 300 | 64.5 | 11,344 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 20 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 27 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 36 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 45 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 62 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 82 | 90 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 108 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 133 | 139 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 166 | 171 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 208 | 209 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 255 | 250 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 295 | 284 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 337 | 318 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 387 | 359 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 457 | 414 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 523 | 466 | 34.50 |
NYFGbY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 630 |
| 2.5 | 18.0 | 662 |
| 4 | 19.0 | 773 |
| 6 | 20.5 | 912 |
| 10 | 23.0 | 1,174 |
| 16 | 25.5 | 1,520 |
| 25 | 29.0 | 2,053 |
| 35 | 32.0 | 2,584 |
| 50 | 37.5 | 3,173 |
| 70 | 40.5 | 4,087 |
| 95 | 46.5 | 5,359 |
| 120 | 50.5 | 6,459 |
| 150 | 56.5 | 7,868 |
| 185 | 61.0 | 9,556 |
| 240 | 68.0 | 12,138 |
| 300 | 74.5 | 14,773 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 154 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 177 | 176 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 221 | 215 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 272 | 257 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 314 | 292 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 363 | 330 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 412 | 369 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 488 | 427 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 559 | 481 | 34.50 |
NYFGbY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.8 | 642 |
| 2.5 | 17.9 | 682 |
| 4 | 20.5 | 891 |
| 6 | 22.0 | 1,056 |
| 10 | 24.5 | 1,391 |
| 16 | 27.5 | 1,778 |
| 25 | 32.0 | 2,463 |
| 35 | 35.0 | 3,106 |
| 50 | 40.0 | 3,904 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 32 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 54 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 74 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 97 | 103 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 130 | 133 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 160 | 159 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 194 | 188 | 5.75 |
NYFGbY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 611 |
| 2.5 | 18.0 | 630 |
| 4 | 17.8 | 648 |
| 6 | 18.1 | 687 |
| 10 | 20.5 | 881 |
| 16 | 22.5 | 1,085 |
| 25 | 25.5 | 1,428 |
| 35 | 27.5 | 1,753 |
| 50 | 31.0 | 2,120 |
| 70 | 35.0 | 2,716 |
| 95 | 39.5 | 3,528 |
| 120 | 43.0 | 4,177 |
| 150 | 47.0 | 5,012 |
| 185 | 52.0 | 6,116 |
| 240 | 58.0 | 7,695 |
| 300 | 64.0 | 9,384 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 24 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 32 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 53 | 61 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 73 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 96 | 106 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 136 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 164 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 186 | 194 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 235 | 239 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 286 | 284 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 331 | 324 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 377 | 364 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 430 | 408 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 507 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 577 | 530 | 34.50 |
NYFGbY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.8 | 620 |
| 2.5 | 18.0 | 648 |
| 4 | 18.0 | 681 |
| 6 | 19.0 | 789 |
| 10 | 21.5 | 997 |
| 16 | 23.5 | 1,280 |
| 25 | 27.0 | 1,709 |
| 35 | 29.5 | 2,123 |
| 50 | 32.0 | 2,444 |
| 70 | 36.0 | 3,217 |
| 95 | 40.5 | 4,171 |
| 120 | 43.5 | 4,957 |
| 150 | 48.0 | 6,011 |
| 185 | 52.5 | 7,319 |
| 240 | 59.0 | 9,324 |
| 300 | 64.5 | 11,344 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.351 | 20 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 27 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 36 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 45 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 62 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 82 | 90 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 108 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 133 | 139 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 166 | 171 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 208 | 209 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 255 | 250 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 295 | 284 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 337 | 318 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 387 | 359 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 457 | 414 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 523 | 466 | 34.50 |
NYFGbY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.9 | 630 |
| 2.5 | 18.0 | 662 |
| 4 | 19.0 | 773 |
| 6 | 20.5 | 912 |
| 10 | 23.0 | 1,174 |
| 16 | 25.5 | 1,520 |
| 25 | 29.0 | 2,053 |
| 35 | 32.0 | 2,584 |
| 50 | 37.5 | 3,173 |
| 70 | 40.5 | 4,087 |
| 95 | 46.5 | 5,359 |
| 120 | 50.5 | 6,459 |
| 150 | 56.5 | 7,868 |
| 185 | 61.0 | 9,556 |
| 240 | 68.0 | 12,138 |
| 300 | 74.5 | 14,773 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.315 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 154 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 177 | 176 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 221 | 215 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 272 | 257 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 314 | 292 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 363 | 330 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 412 | 369 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 488 | 427 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 559 | 481 | 34.50 |
NYFGbY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 17.8 | 642 |
| 2.5 | 17.9 | 682 |
| 4 | 20.5 | 891 |
| 6 | 22.0 | 1,056 |
| 10 | 24.5 | 1,391 |
| 16 | 27.5 | 1,778 |
| 25 | 32.0 | 2,463 |
| 35 | 35.0 | 3,106 |
| 50 | 40.0 | 3,904 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.340 | 24 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 32 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 54 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 74 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 97 | 103 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 130 | 133 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 160 | 159 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 194 | 188 | 5.75 |
NYFGbY 2 x (25-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 26.0 | 1,496 |
| 35 | 28.5 | 1,833 |
| 50 | 32.0 | 2,177 |
| 70 | 36.0 | 2,816 |
| 95 | 40.0 | 3,605 |
| 120 | 43.5 | 4,260 |
| 150 | 48.0 | 5,153 |
| 185 | 52.5 | 6,224 |
| 240 | 58.5 | 7,815 |
| 300 | 64.5 | 9,523 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 25 | 0.727 | 0.870 | 40 | 0.255 | 120 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 150 | 160 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 180 | 187 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 230 | 230 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 275 | 280 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 320 | 320 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 375 | 355 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 430 | 409 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 510 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 590 | 525 | 34.50 |
NYFGbY 3 x (25-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 27.5 | 1,776 |
| 35 | 30.0 | 2,199 |
| 50 | 32.5 | 2,502 |
| 70 | 36.5 | 3,286 |
| 95 | 41.0 | 4,249 |
| 120 | 44.0 | 5,041 |
| 150 | 48.5 | 6,108 |
| 185 | 53.0 | 7,427 |
| 240 | 59.5 | 9,451 |
| 300 | 65.0 | 11,483 |
| 400 | 71.5 | 14,273 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 280 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYFGbY 4 x (16-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 26.0 | 1,578 |
| 25 | 29.5 | 2,124 |
| 35 | 32.5 | 2,665 |
| 50 | 38.0 | 3,245 |
| 70 | 41.5 | 4,166 |
| 95 | 47.0 | 5,450 |
| 120 | 51.0 | 6,562 |
| 150 | 57.5 | 7,984 |
| 185 | 62.0 | 9,688 |
| 240 | 68.5 | 12,285 |
| 300 | 75.0 | 14,934 |
| 400 | 85.0 | 18,791 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 280 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYFGbY 5 x (16-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 16 | 28.0 | 1,840 |
| 25 | 32.5 | 2,540 |
| 35 | 35.5 | 3,194 |
| 50 | 40.5 | 3,982 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.463 | 30 | 0.247 | 160 | 165 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NYFGbY