NYM
Cu / PVC / PVC IEC 60227-4 : 1997
Deskripsi
Copper Conductor, PVC Insulated, PVC Sheathed
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYM dari dalam ke luar — sesuai kode konstruksi Cu / PVC / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYM.
Spesifikasi Teknis
IEC 60227-4 : 1997
NYM 2 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa compliance |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 9.5 | 116 | • Fire Resi |
| 2.5 | 10.5 | 157 | • Oil Resis |
| • Flame Re | |||
| 4 | 11.5 | 203 | • Heat Res |
| 6 | 12.5 | 262 | • Nylon Co |
| 10 | 16.0 | 426 | |
| 16 | 19.0 | 638 | |
| 25 | 23.0 | 962 | |
| 35 | 26.0 | 1,270 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 3 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa compliance |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 10.0 | 136 | • Fire Resi |
| 2.5 | 11.0 | 186 | • Oil Resis |
| • Flame Re | |||
| 4 | 12.0 | 246 | • Heat Res |
| 6 | 13.5 | 335 | • Nylon Co |
| 10 | 17.0 | 527 | |
| 16 | 20.5 | 816 | |
| 25 | 24.5 | 1,229 | |
| 35 | 27.5 | 1,601 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 4 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa compliance |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 10.5 | 161 | • Fire Resi |
| 2.5 | 12.0 | 224 | • Oil Resis |
| • Flame Re | |||
| 4 | 13.5 | 311 | • Heat Res |
| 6 | 15.5 | 424 | • Nylon Co |
| 10 | 18.5 | 648 | |
| 16 | 22.5 | 1,027 | |
| 25 | 27.5 | 1,579 | |
| 35 | 30.0 | 2,026 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 5 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa compliance |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 11.5 | 198 | • Fire Resi |
| 2.5 | 13.0 | 278 | • Oil Resis |
| • Flame Re | |||
| 4 | 15.0 | 400 | • Heat Res |
| 6 | 16.5 | 524 | • Nylon Co |
| 10 | 20.0 | 805 | |
| 16 | 25.0 | 1,274 | |
| 25 | 30.0 | 1,927 | |
| 35 | 33.5 | 2,514 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.0 | 077 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.0 | 065 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.0 | 065 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.0 | 052 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.0 | 050 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.0 | 044 | 0.244 | 134 | 4.03 |
SNI 04-6629.4 : 2006
NYM 2 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location an control pa compliance Special Fe |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1.5 | 9.5 | 116 | • Tinned Co |
| 2.5 | 10.5 | 157 | • Fire Resis |
| • Oil Resist | |||
| 4 | 11.5 | 203 | • Flame Re |
| 6 | 12.5 | 262 | • Heat Res |
| • Nylon Coa | |||
| 10 | 16.0 | 426 | |
| 16 | 19.0 | 638 | |
| 25 | 23.0 | 962 | |
| 35 | 26.0 | 1,270 |
| Conductor | Insulation | Inductance (mH/km) | Current-Carrying Capacity at 30° C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | ||||
|---|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20° C Max. (Ω/km) | AC Resistanc at 70° C Max. (Ω/km) | Insulation e Resistance at 70° C Min. (M.Ω.km) | |||||
| 1.5 | 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 | |
| 2.5 | 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 | |
| 4 | 4.61 | 5.516 | 0.007 | 7 | 0.297 | 34 | 0.46 | |
| 6 | 3.08 | 3.685 | 0.006 | 5 | 0.281 | 44 | 0.69 | |
| 10 | 1.83 | 2.190 | 0.006 | 5 | 0.278 | 61 | 1.15 | |
| 16 | 1.15 | 1.376 | 0.005 | 2 | 0.255 | 82 | 1.84 | |
| 25 | 0.727 | 0.870 | 0.005 | 0 | 0.252 | 1 | 08 | 2.88 |
| 35 | 0.524 | 0.627 | 0.004 | 4 | 0.244 | 1 | 34 | 4.03 |
NYM 3 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location an control pa compliance Special Fe |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1.5 | 10.0 | 136 | • Tinned Co |
| 2.5 | 11.0 | 186 | • Fire Resis |
| • Oil Resist | |||
| 4 | 12.0 | 246 | • Flame Re |
| 6 | 13.5 | 335 | • Heat Res |
| • Nylon Coa | |||
| 10 | 17.0 | 527 | |
| 16 | 20.5 | 816 | |
| 25 | 24.5 | 1,229 | |
| 35 | 27.5 | 1,601 |
| Conductor | Insulation | Inductance (mH/km) | Current-Carrying Capacity at 30° C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | ||||
|---|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20° C Max. (Ω/km) | AC Resistanc at 70° C Max. (Ω/km) | Insulation e Resistance at 70° C Min. (M.Ω.km) | |||||
| 1.5 | 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 | |
| 2.5 | 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 | |
| 4 | 4.61 | 5.516 | 0.007 | 7 | 0.297 | 34 | 0.46 | |
| 6 | 3.08 | 3.685 | 0.006 | 5 | 0.281 | 44 | 0.69 | |
| 10 | 1.83 | 2.190 | 0.006 | 5 | 0.278 | 61 | 1.15 | |
| 16 | 1.15 | 1.376 | 0.005 | 2 | 0.255 | 82 | 1.84 | |
| 25 | 0.727 | 0.870 | 0.005 | 0 | 0.252 | 1 | 08 | 2.88 |
| 35 | 0.524 | 0.627 | 0.004 | 4 | 0.244 | 1 | 34 | 4.03 |
NYM 4 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location an control pa compliance Special Fe |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1.5 | 10.5 | 161 | • Tinned Co |
| 2.5 | 12.0 | 224 | • Fire Resis |
| • Oil Resist | |||
| 4 | 13.5 | 311 | • Flame Re |
| 6 | 15.5 | 424 | • Heat Res |
| • Nylon Co | |||
| 10 | 18.5 | 648 | |
| 16 | 22.5 | 1,027 | |
| 25 | 27.5 | 1,579 | |
| 35 | 30.0 | 2,026 |
| Conductor | Insulation | Inductance (mH/km) | Current-Carrying Capacity at 30° C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | ||||
|---|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20° C Max. (Ω/km) | AC Resistanc at 70° C Max. (Ω/km) | Insulation e Resistance at 70° C Min. (M.Ω.km) | |||||
| 1.5 | 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 | |
| 2.5 | 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 | |
| 4 | 4.61 | 5.516 | 0.007 | 7 | 0.297 | 34 | 0.46 | |
| 6 | 3.08 | 3.685 | 0.006 | 5 | 0.281 | 44 | 0.69 | |
| 10 | 1.83 | 2.190 | 0.006 | 5 | 0.278 | 61 | 1.15 | |
| 16 | 1.15 | 1.376 | 0.005 | 2 | 0.255 | 82 | 1.84 | |
| 25 | 0.727 | 0.870 | 0.005 | 0 | 0.252 | 1 | 08 | 2.88 |
| 35 | 0.524 | 0.627 | 0.004 | 4 | 0.244 | 1 | 34 | 4.03 |
NYM 5 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location an control pa compliance Special Fe |
|---|---|---|---|
| mm² | mm | kg/km | |
| 1.5 | 11.5 | 198 | • Tinned Co |
| 2.5 | 13.0 | 278 | • Fire Resis |
| • Oil Resist | |||
| 4 | 15.0 | 400 | • Flame Re |
| 6 | 16.5 | 524 | • Heat Res |
| • Nylon Co | |||
| 10 | 20.0 | 805 | |
| 16 | 25.0 | 1,274 | |
| 25 | 30.0 | 1,927 | |
| 35 | 33.5 | 2,514 |
| Insulation | Inductance (mH/km) | Current-Carrying Capacity at 30° C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | ||||
|---|---|---|---|---|---|---|---|
| DC Resistance at 20° C Max. (Ω/km) | AC Resistanc at 70° C Max. (Ω/km) | Insulation e Resistance at 70° C Min. (M.Ω.km) | |||||
| 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 | |
| 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 | |
| 4.61 | 5.516 | 0.007 | 7 | 0.297 | 34 | 0.46 | |
| 3.08 | 3.685 | 0.006 | 5 | 0.281 | 44 | 0.69 | |
| 1.83 | 2.190 | 0.006 | 5 | 0.278 | 61 | 1.15 | |
| 1.15 | 1.376 | 0.005 | 2 | 0.255 | 82 | 1.84 | |
| 0.727 | 0.870 | 0.005 | 0 | 0.252 | 1 | 08 | 2.88 |
| 0.524 | 0.627 | 0.004 | 4 | 0.244 | 1 | 34 | 4.03 |
SPLN 42-2:1992
NYM 2 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa complianc |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 9.5 | 116 | • Fire Resi |
| 2.5 | 11.0 | 157 | • Oil Resis |
| • Flame Re | |||
| 4 | 12.0 | 203 | • Heat Res |
| 6 | 13.5 | 262 | • Nylon Co |
| 10 | 17.0 | 426 | |
| 16 | 19.0 | 638 | |
| 25 | 23.0 | 962 | |
| 35 | 26.0 | 1,270 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 3 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICA For buildi location a control pa complianc |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special F | |||
| 1.5 | 10.0 | 136 | • Fire Res |
| 2.5 | 11.5 | 186 | • Oil Resis |
| • Flame R | |||
| 4 | 13.0 | 246 | • Heat Res |
| 6 | 14.5 | 335 | • Nylon Co |
| 10 | 18.0 | 527 | |
| 16 | 20.5 | 816 | |
| 25 | 24.5 | 1,229 | |
| 35 | 27.5 | 1,601 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 4 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICAT For buildin location a control pa complianc |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special Fe | |||
| 1.5 | 11.0 | 161 | • Fire Resi |
| 2.5 | 12.5 | 224 | • Oil Resis |
| • Flame Re | |||
| 4 | 14.5 | 311 | • Heat Res |
| 6 | 16.0 | 424 | • Nylon Co |
| 10 | 19.5 | 648 | |
| 16 | 22.5 | 1,027 | |
| 25 | 27.5 | 1,579 | |
| 35 | 30.0 | 2,026 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.01 | 0 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.00 | 9 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
NYM 5 x (1.5 - 35) mm² 300/500 V
| Nom. ross ection Area | Overall Diameter approx. | Cable Weight approx. | APPLICA For buildi location a control pa complianc |
|---|---|---|---|
| mm� | mm | kg/km | |
| Special F | |||
| 1.5 | 12.0 | 198 | • Fire Res |
| 2.5 | 13.5 | 278 | • Oil Resis |
| • Flame R | |||
| 4 | 16.0 | 400 | • Heat Res |
| 6 | 17.5 | 524 | • Nylon Co |
| 10 | 21.5 | 805 | |
| 16 | 25.0 | 1,274 | |
| 25 | 30.0 | 1,927 | |
| 35 | 33.5 | 2,514 |
| Conductor | Insulation | Inductance | Current-Carrying Capacity at 30°C * in air Max. (A) | Short circuit current at 1 sec Max. (kA) | |||
|---|---|---|---|---|---|---|---|
| Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Resistance at 70°C Min. (M.Ω.km) | (mH/km) | |||
| 1.5 | 12.1 | 14.478 | 0.0 | 10 | 0.329 | 19 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.0 | 09 | 0.318 | 25 | 0.29 |
| 4 | 4.61 | 5.516 | 0.00 | 77 | 0.297 | 34 | 0.46 |
| 6 | 3.08 | 3.685 | 0.00 | 65 | 0.281 | 44 | 0.69 |
| 10 | 1.83 | 2.190 | 0.00 | 65 | 0.278 | 61 | 1.15 |
| 16 | 1.15 | 1.376 | 0.00 | 52 | 0.255 | 82 | 1.84 |
| 25 | 0.727 | 0.870 | 0.00 | 50 | 0.252 | 108 | 2.88 |
| 35 | 0.524 | 0.627 | 0.00 | 44 | 0.244 | 134 | 4.03 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.