NYRY
Cu / PVC / AWA / PVC Deskripsi
Copper Conductor, PVC Insulated, Aluminium Wire Armor, PVC Sheathed
Aplikasi
- For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYRY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / AWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Perisai kawat aluminium (AWA)
Aluminium wire armourPerisai non-magnetik untuk kabel inti tunggal.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYRY.
Spesifikasi Teknis
NYR(AL)Y 1 x (10-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 14.4 | 326 |
| 16 | 15.4 | 402 |
| 25 | 17.2 | 541 |
| 35 | 18.3 | 658 |
| 50 | 20.5 | 841 |
| 70 | 22.5 | 1,070 |
| 95 | 24.5 | 1,365 |
| 120 | 26.5 | 1,662 |
| 150 | 28.5 | 1,967 |
| 185 | 31.0 | 2,406 |
| 240 | 34.0 | 3,071 |
| 300 | 38.0 | 3,781 |
| 400 | 42.0 | 4,764 |
| 500 | 46.5 | 5,968 |
| 630 | 51.0 | 7,538 |
| 800 | 57.0 | 9,508 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 10 | 1.83 | 2.190 | 0.442 | 0.489 | 73 | 77 | 75 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.412 | 0.458 | 96 | 99 | 98 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.386 | 0.432 | 127 | 128 | 130 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.367 | 0.414 | 154 | 153 | 158 | 157 | 4.03 |
| 50 | 0.387 | 0.463 | 0.351 | 0.397 | 187 | 181 | 192 | 186 | 5.75 |
| 70 | 0.268 | 0.321 | 0.333 | 0.379 | 234 | 222 | 240 | 227 | 8.05 |
| 95 | 0.193 | 0.232 | 0.322 | 0.368 | 286 | 264 | 292 | 269 | 10.93 |
| 120 | 0.153 | 0.184 | 0.315 | 0.361 | 331 | 299 | 338 | 304 | 13.80 |
| 150 | 0.124 | 0.150 | 0.309 | 0.355 | 376 | 334 | 383 | 338 | 17.25 |
| 185 | 0.0991 | 0.120 | 0.302 | 0.348 | 431 | 375 | 438 | 378 | 21.28 |
| 240 | 0.0754 | 0.092 | 0.294 | 0.340 | 507 | 429 | 511 | 430 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.293 | 0.340 | 573 | 472 | 573 | 468 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.290 | 0.337 | 650 | 522 | 644 | 513 | 41.20 |
| 500 | 0.0366 | 0.048 | 0.284 | 0.330 | 732 | 573 | 719 | 557 | 51.50 |
| 630 | 0.0283 | 0.040 | 0.275 | 0.321 | 820 | 625 | 799 | 602 | 64.89 |
| 800 | 0.0221 | 0.033 | 0.275 | 0.321 | 883 | 651 | 851 | 620 | 82.40 |
NYRY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.0 | 347 |
| 2.5 | 15.0 | 403 |
| 4 | 16.9 | 516 |
| 6 | 18.8 | 701 |
| 10 | 21.0 | 874 |
| 16 | 23.0 | 1,082 |
| 25 | 27.0 | 1,565 |
| 35 | 29.0 | 1,893 |
| 50 | 32.5 | 2,293 |
| 70 | 37.0 | 3,150 |
| 95 | 42.0 | 4,037 |
| 120 | 45.0 | 4,725 |
| 150 | 50.5 | 6,041 |
| 185 | 55.5 | 7,253 |
| 240 | 61.5 | 8,949 |
| 300 | 67.5 | 10,731 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 24 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 32 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 54 | 61 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 73 | 82 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 97 | 106 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 128 | 137 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 157 | 165 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 188 | 194 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 238 | 240 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 288 | 284 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 333 | 323 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 381 | 363 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 433 | 406 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 506 | 466 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 573 | 520 | 34.50 |
NYRY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.5 | 382 |
| 2.5 | 15.5 | 448 |
| 4 | 18.4 | 678 |
| 6 | 19.6 | 783 |
| 10 | 22.0 | 1,006 |
| 16 | 24.0 | 1,276 |
| 25 | 28.0 | 1,863 |
| 35 | 30.5 | 2,279 |
| 50 | 33.5 | 2,644 |
| 70 | 38.5 | 3,664 |
| 95 | 42.5 | 4,661 |
| 120 | 45.5 | 5,487 |
| 150 | 51.5 | 7,040 |
| 185 | 56.5 | 8,457 |
| 240 | 62.5 | 10,579 |
| 300 | 68.0 | 12,683 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 20 | 24 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 27 | 32 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 36 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 46 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 63 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 83 | 90 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 110 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 134 | 140 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 168 | 171 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 212 | 209 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 259 | 250 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 299 | 284 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 342 | 317 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 391 | 357 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 457 | 409 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 519 | 457 | 34.50 |
NYRY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 15.4 | 425 |
| 2.5 | 16.5 | 509 |
| 4 | 19.6 | 767 |
| 6 | 21.0 | 904 |
| 10 | 23.5 | 1,179 |
| 16 | 27.0 | 1,657 |
| 25 | 30.5 | 2,236 |
| 35 | 33.5 | 2,768 |
| 50 | 40.0 | 3,639 |
| 70 | 43.0 | 4,592 |
| 95 | 50.0 | 6,338 |
| 120 | 54.0 | 7,547 |
| 150 | 60.5 | 9,073 |
| 185 | 65.0 | 10,835 |
| 240 | 72.0 | 13,543 |
| 300 | 78.0 | 16,333 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 42 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 53 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 72 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 96 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 128 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 156 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 180 | 176 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 224 | 215 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 277 | 258 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 318 | 292 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 366 | 328 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 413 | 365 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 485 | 420 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 550 | 468 | 34.50 |
NYRY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 16.3 | 482 |
| 2.5 | 17.6 | 581 |
| 4 | 21.0 | 882 |
| 6 | 22.5 | 1,055 |
| 10 | 26.0 | 1,515 |
| 16 | 29.0 | 1,945 |
| 25 | 33.0 | 2,649 |
| 35 | 37.5 | 3,538 |
| 50 | 42.5 | 4,437 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 24 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 32 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 43 | 49 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 55 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 75 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 99 | 104 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 132 | 133 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 163 | 160 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 197 | 188 | 5.75 |
NYR(AL)Y 1 x (10-500) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 15.7 | 384 |
| 16 | 16.7 | 465 |
| 25 | 18.6 | 611 |
| 35 | 19.7 | 733 |
| 50 | 22.0 | 925 |
| 70 | 23.5 | 1,162 |
| 95 | 26.0 | 1,467 |
| 120 | 28.0 | 1,773 |
| 150 | 30.0 | 2,085 |
| 185 | 32.5 | 2,535 |
| 240 | 35.5 | 3,214 |
| 300 | 38.5 | 3,847 |
| 400 | 43.5 | 4,924 |
| 500 | 47.5 | 6,145 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 10 | 1.83 | 2.190 | 50 | 0.460 | 0.506 | 75 | 77 | 77 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.429 | 0.475 | 98 | 100 | 101 | 103 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.401 | 0.447 | 129 | 128 | 133 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.382 | 0.428 | 157 | 153 | 161 | 158 | 4.03 |
| 50 | 0.387 | 0.463 | 30 | 0.364 | 0.410 | 190 | 181 | 195 | 186 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.345 | 0.391 | 237 | 221 | 243 | 227 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.333 | 0.379 | 290 | 264 | 296 | 270 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.325 | 0.371 | 335 | 299 | 342 | 304 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.318 | 0.365 | 380 | 333 | 386 | 338 | 17.25 |
| 185 | 0.0991 | 0.120 | 20 | 0.310 | 0.356 | 435 | 374 | 441 | 378 | 21.28 |
| 240 | 0.0754 | 0.092 | 20 | 0.302 | 0.348 | 510 | 428 | 514 | 429 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.296 | 0.342 | 579 | 476 | 581 | 474 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.296 | 0.342 | 652 | 521 | 646 | 512 | 41.20 |
| 500 | 0.0366 | 0.048 | 20 | 0.289 | 0.335 | 734 | 572 | 721 | 557 | 51.50 |
NYRGbY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.0 | 873 |
| 16 | 23.0 | 1,088 |
| 25 | 27.5 | 1,722 |
| 35 | 30.0 | 2,070 |
| 50 | 33.0 | 2,444 |
| 70 | 38.0 | 3,324 |
| 95 | 43.0 | 4,257 |
| 120 | 46.0 | 4,963 |
| 150 | 51.5 | 6,294 |
| 185 | 56.5 | 7,536 |
| 240 | 62.5 | 9,264 |
| 300 | 68.0 | 11,119 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 1.83 | 2.190 | 50 | 0.269 | 66 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 90 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 120 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 150 | 160 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 180 | 187 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 230 | 230 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 275 | 280 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 320 | 320 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 375 | 355 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 430 | 409 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 510 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 590 | 525 | 34.50 |
NYRGbY 3 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 22.0 | 1,004 |
| 16 | 24.5 | 1,276 |
| 25 | 29.0 | 2,024 |
| 35 | 31.5 | 2,459 |
| 50 | 34.5 | 2,815 |
| 70 | 38.5 | 3,798 |
| 95 | 43.5 | 4,895 |
| 120 | 46.5 | 5,745 |
| 150 | 52.0 | 7,299 |
| 185 | 57.0 | 8,741 |
| 240 | 63.5 | 10,902 |
| 300 | 67.0 | 12,956 |
| 400 | 75.0 | 16,037 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 285 | 13.80 |
| 150 | 0.124 | 0.150 | 30 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYRGbY 4 x (10-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 24.0 | 1,182 |
| 16 | 27.5 | 1,804 |
| 25 | 31.5 | 2,410 |
| 35 | 34.5 | 2,962 |
| 50 | 39.0 | 3,743 |
| 70 | 42.5 | 4,713 |
| 95 | 50.0 | 6,552 |
| 120 | 55.0 | 7,828 |
| 150 | 58.0 | 9,140 |
| 185 | 64.5 | 11,081 |
| 240 | 70.5 | 13,786 |
| 300 | 79.0 | 16,779 |
| 400 | 88.5 | 20,882 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 285 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYRGbY 5 x (10-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 27.0 | 1,655 |
| 16 | 30.0 | 2,118 |
| 25 | 34.5 | 2,853 |
| 35 | 38.0 | 3,754 |
| 50 | 43.0 | 4,640 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 10 | 1.83 | 2.190 | 40 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.463 | 30 | 0.247 | 160 | 165 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NYRY
Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.