NYSY
Cu / PVC / CTS / PVC Deskripsi
Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed
Aplikasi
- For power plants and switchgear as well as for installation of sub-station; for installation indoors in confinned spaces and cable channels because of small bending radius. As burried c a b le , b e c a u s e o f i ts l i g h t weight prefered in w h e re i n st a ll a ti o n i s d if f i c u lt
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYSY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / CTS / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYSY.
Spesifikasi Teknis
NYSY 1 x (1.5-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 8.8 | 110 |
| 2.5 | 9.3 | 128 |
| 4 | 10.2 | 162 |
| 6 | 10.8 | 191 |
| 10 | 11.7 | 247 |
| 16 | 12.7 | 318 |
| 25 | 14.6 | 449 |
| 35 | 15.7 | 558 |
| 50 | 17.6 | 730 |
| 70 | 19.4 | 951 |
| 95 | 22.0 | 1,232 |
| 120 | 23.5 | 1,481 |
| 150 | 25.5 | 1,774 |
| 185 | 27.5 | 2,197 |
| 240 | 31.0 | 2,821 |
| 300 | 34.0 | 3,422 |
| 400 | 38.0 | 4,348 |
| 500 | 42.0 | 5,504 |
| 630 | 46.5 | 7,035 |
| 800 | 51.0 | 8,770 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 12.1 | 14.478 | 0.531 | 0.577 | 23 | 26 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.491 | 0.537 | 30 | 35 | 31 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.464 | 0.510 | 40 | 45 | 40 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.436 | 0.483 | 50 | 56 | 51 | 58 | 0.69 |
| 10 | 1.83 | 2.190 | 0.401 | 0.447 | 68 | 75 | 70 | 77 | 1.15 |
| 16 | 1.15 | 1.376 | 0.374 | 0.420 | 89 | 97 | 92 | 100 | 1.84 |
| 25 | 0.727 | 0.870 | 0.352 | 0.399 | 119 | 125 | 122 | 129 | 2.88 |
| 35 | 0.524 | 0.627 | 0.336 | 0.382 | 146 | 150 | 150 | 155 | 4.03 |
| 50 | 0.387 | 0.463 | 0.323 | 0.369 | 178 | 179 | 183 | 184 | 5.75 |
| 70 | 0.268 | 0.321 | 0.307 | 0.353 | 224 | 219 | 230 | 225 | 8.05 |
| 95 | 0.193 | 0.232 | 0.298 | 0.345 | 276 | 262 | 284 | 269 | 10.93 |
| 120 | 0.153 | 0.184 | 0.289 | 0.335 | 320 | 299 | 329 | 306 | 13.80 |
| 150 | 0.124 | 0.150 | 0.285 | 0.331 | 366 | 335 | 376 | 343 | 17.25 |
| 185 | 0.0991 | 0.120 | 0.280 | 0.326 | 424 | 379 | 436 | 388 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.273 | 0.319 | 505 | 439 | 518 | 448 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.270 | 0.316 | 581 | 493 | 596 | 503 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.268 | 0.314 | 672 | 557 | 689 | 567 | 41.20 |
| 500 | 0.0366 | 0.049 | 0.263 | 0.310 | 776 | 626 | 793 | 636 | 51.50 |
| 630 | 0.0283 | 0.040 | 0.257 | 0.303 | 891 | 699 | 909 | 709 | 64.89 |
| 800 | 0.0221 | 0.034 | 0.253 | 0.299 | 1003 | 768 | 1020 | 776 | 82.40 |
NYSY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 12.2 | 206 |
| 2.5 | 13.2 | 249 |
| 4 | 15.1 | 336 |
| 6 | 16.3 | 405 |
| 10 | 18.2 | 543 |
| 16 | 20.5 | 716 |
| 25 | 23.5 | 1,001 |
| 35 | 26.0 | 1,270 |
| 50 | 29.0 | 1,565 |
| 70 | 33.0 | 2,099 |
| 95 | 37.5 | 2,821 |
| 120 | 40.5 | 3,409 |
| 150 | 45.0 | 4,176 |
| 185 | 50.0 | 5,169 |
| 240 | 56.0 | 6,627 |
| 300 | 62.0 | 8,203 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 31 | 37 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 60 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 81 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 105 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 123 | 135 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 152 | 163 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 183 | 193 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 231 | 238 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 282 | 283 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 327 | 323 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 373 | 362 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 426 | 407 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 502 | 470 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 572 | 527 | 34.50 |
NYSY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 12.8 | 232 |
| 2.5 | 13.8 | 285 |
| 4 | 15.9 | 392 |
| 6 | 17.1 | 480 |
| 10 | 19.2 | 657 |
| 16 | 21.5 | 883 |
| 25 | 25.0 | 1,254 |
| 35 | 27.5 | 1,610 |
| 50 | 30.0 | 1,900 |
| 70 | 34.0 | 2,587 |
| 95 | 38.5 | 3,462 |
| 120 | 41.0 | 4,189 |
| 150 | 46.0 | 5,173 |
| 185 | 50.5 | 6,371 |
| 240 | 57.0 | 8,256 |
| 300 | 62.0 | 10,161 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 20 | 24 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 26 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 35 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 44 | 51 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 60 | 68 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 106 | 114 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 163 | 169 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 204 | 207 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 251 | 248 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 291 | 283 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 332 | 316 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 383 | 357 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 452 | 413 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 518 | 464 | 34.50 |
NYSY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.6 | 267 |
| 2.5 | 14.7 | 333 |
| 4 | 17.1 | 463 |
| 6 | 18.5 | 573 |
| 10 | 21.0 | 805 |
| 16 | 23.5 | 1,093 |
| 25 | 27.0 | 1,568 |
| 35 | 30.0 | 2,026 |
| 50 | 35.5 | 2,514 |
| 70 | 39.0 | 3,369 |
| 95 | 44.5 | 4,532 |
| 120 | 48.5 | 5,565 |
| 150 | 54.5 | 6,832 |
| 185 | 59.0 | 8,435 |
| 240 | 66.0 | 10,866 |
| 300 | 72.5 | 13,378 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 22 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 29 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 40 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 50 | 58 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 69 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 91 | 100 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 122 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 150 | 155 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 174 | 174 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 217 | 213 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 268 | 256 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 310 | 290 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 359 | 328 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 407 | 367 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 483 | 426 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 554 | 479 | 34.50 |
NYSY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.6 | 311 |
| 2.5 | 15.8 | 393 |
| 4 | 18.5 | 552 |
| 6 | 20.0 | 688 |
| 10 | 23.0 | 966 |
| 16 | 25.5 | 1,321 |
| 25 | 29.5 | 1,906 |
| 35 | 33.0 | 2,488 |
| 50 | 38.0 | 3,213 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current of conductor at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 48 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 79 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 95 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 127 | 132 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 156 | 158 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 190 | 186 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.