NYY
Cu / PVC / PVC 0.6/1 kV IEC 60502-1
Deskripsi
Copper Conductor, PVC Insulated, PVC Sheathed
Aplikasi
- Power cable Indoors, cable trunking, outdoors and burried in the ground, for power stations, industry and switchgear as well as for urban supply networks, if mechanical damage is unlikely
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NYY dari dalam ke luar — sesuai kode konstruksi Cu / PVC / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi PVC
Polyvinyl chlorideIsolasi utama — suhu kerja 70 °C, ekonomis dan andal untuk tegangan rendah.
- 3
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NYY.
Spesifikasi Teknis
IEC 60502-1
NYY 1 x (1.5-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 6.1 | 53 |
| 2.5 | 6.6 | 67 |
| 4 | 7.6 | 94 |
| 6 | 8.1 | 117 |
| 10 | 9.1 | 166 |
| 16 | 10.1 | 229 |
| 25 | 11.9 | 345 |
| 35 | 13.0 | 444 |
| 50 | 15.0 | 600 |
| 70 | 16.9 | 815 |
| 95 | 19.1 | 1,079 |
| 120 | 21.0 | 1,325 |
| 150 | 23.0 | 1,604 |
| 185 | 25.5 | 2,020 |
| 240 | 29.0 | 2,636 |
| 300 | 32.0 | 3,219 |
| 400 | 35.5 | 4,087 |
| 500 | 39.5 | 5,213 |
| 630 | 44.0 | 6,712 |
| 800 | 48.5 | 8,368 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 12.1 | 14.478 | 0.459 | 0.505 | 21 | 27 | 21 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.423 | 0.470 | 27 | 35 | 28 | 35 | 0.29 |
| 4 | 4.61 | 5.516 | 0.404 | 0.450 | 37 | 46 | 38 | 45 | 0.46 |
| 6 | 3.08 | 3.685 | 0.380 | 0.426 | 46 | 57 | 48 | 57 | 0.69 |
| 10 | 1.83 | 2.190 | 0.350 | 0.396 | 64 | 76 | 65 | 76 | 1.15 |
| 16 | 1.15 | 1.376 | 0.327 | 0.374 | 84 | 98 | 87 | 97 | 1.84 |
| 25 | 0.727 | 0.870 | 0.312 | 0.358 | 114 | 127 | 117 | 125 | 2.88 |
| 35 | 0.524 | 0.627 | 0.299 | 0.345 | 140 | 152 | 144 | 150 | 4.03 |
| 50 | 0.387 | 0.464 | 0.290 | 0.336 | 172 | 180 | 177 | 178 | 5.75 |
| 70 | 0.268 | 0.321 | 0.280 | 0.326 | 218 | 220 | 225 | 218 | 8.05 |
| 95 | 0.193 | 0.232 | 0.274 | 0.321 | 270 | 264 | 278 | 260 | 10.93 |
| 120 | 0.153 | 0.184 | 0.269 | 0.315 | 315 | 300 | 325 | 296 | 13.80 |
| 150 | 0.124 | 0.150 | 0.266 | 0.313 | 362 | 336 | 373 | 331 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.264 | 0.310 | 420 | 379 | 433 | 374 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.261 | 0.307 | 503 | 439 | 518 | 432 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.258 | 0.305 | 580 | 494 | 598 | 486 | 34.50 |
| 400 | 0.0470 | 0.061 | 0.256 | 0.302 | 674 | 558 | 695 | 549 | 41.20 |
| 500 | 0.0366 | 0.049 | 0.252 | 0.299 | 781 | 629 | 806 | 618 | 51.50 |
| 630 | 0.0283 | 0.041 | 0.247 | 0.293 | 901 | 704 | 930 | 692 | 64.89 |
| 800 | 0.0221 | 0.035 | 0.242 | 0.289 | 1018 | 775 | 1052 | 762 | 82.40 |
NYY 2 x (1.5-300) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 12.5 | 200 |
| 2.5 | 13.4 | 242 |
| 4 | 15.4 | 330 |
| 6 | 16.5 | 399 |
| 10 | 18.4 | 538 |
| 16 | 20.5 | 713 |
| 25 | 24.0 | 1,001 |
| 35 | 26.0 | 1,274 |
| 50 | 29.5 | 1,536 |
| 70 | 33.0 | 2,066 |
| 95 | 37.5 | 2,787 |
| 120 | 41.0 | 3,371 |
| 150 | 45.0 | 4,114 |
| 185 | 50.0 | 5,128 |
| 240 | 56.0 | 6,581 |
| 300 | 62.0 | 8,130 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 40 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 51 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 70 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 93 | 104 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 123 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 151 | 162 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 182 | 191 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 230 | 236 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 280 | 281 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 325 | 321 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 371 | 361 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 424 | 406 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 501 | 470 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 572 | 528 | 34.50 |
NYY 3 x (1.5-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.0 | 224 |
| 2.5 | 14.0 | 277 |
| 4 | 16.1 | 383 |
| 6 | 17.3 | 471 |
| 10 | 19.4 | 649 |
| 16 | 22.0 | 875 |
| 25 | 25.0 | 1,248 |
| 35 | 27.5 | 1,606 |
| 50 | 30.0 | 1,857 |
| 70 | 34.0 | 2,556 |
| 95 | 38.5 | 3,428 |
| 120 | 41.5 | 4,152 |
| 150 | 46.0 | 5,115 |
| 185 | 50.5 | 6,330 |
| 240 | 57.0 | 8,215 |
| 300 | 62.5 | 10,116 |
| 400 | 69.0 | 12,765 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 19 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 26 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 34 | 40 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 44 | 50 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 60 | 68 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 79 | 88 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 105 | 114 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 129 | 137 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 162 | 168 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 203 | 206 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 250 | 247 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 289 | 281 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 330 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 381 | 356 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 451 | 412 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 517 | 464 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.229 | 594 | 524 | 41.20 |
NYY 4 x (1.5-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.8 | 259 |
| 2.5 | 15.0 | 324 |
| 4 | 17.3 | 453 |
| 6 | 18.7 | 563 |
| 10 | 21.5 | 794 |
| 16 | 23.5 | 1,083 |
| 25 | 27.5 | 1,558 |
| 35 | 30.0 | 2,018 |
| 50 | 35.5 | 2,466 |
| 70 | 39.0 | 3,334 |
| 95 | 44.5 | 4,491 |
| 120 | 48.5 | 5,504 |
| 150 | 54.5 | 6,787 |
| 185 | 59.0 | 8,392 |
| 240 | 66.0 | 10,818 |
| 300 | 72.5 | 13,326 |
| 400 | 82.5 | 16,969 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 22 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 29 | 35 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 39 | 46 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 50 | 57 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 68 | 77 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 90 | 99 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 121 | 128 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 149 | 154 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 173 | 173 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 215 | 212 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 266 | 255 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 308 | 289 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 357 | 327 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 405 | 366 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 482 | 425 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 552 | 479 | 34.50 |
| 400 | 0.0470 | 0.060 | 0.229 | 643 | 545 | 41.20 |
NYY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.8 | 302 |
| 2.5 | 16.0 | 382 |
| 4 | 18.7 | 541 |
| 6 | 20.5 | 677 |
| 10 | 23.0 | 954 |
| 16 | 26.0 | 1,309 |
| 25 | 30.0 | 1,895 |
| 35 | 33.0 | 2,478 |
| 50 | 38.0 | 3,161 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 189 | 185 | 5.75 |
SNI IEC 60502-1 : 2009
NYY 1 x (1.5-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 6.1 | 53 |
| 2.5 | 6.6 | 67 |
| 4 | 7.6 | 94 |
| 6 | 8.1 | 117 |
| 10 | 9.1 | 166 |
| 16 | 10.1 | 229 |
| 25 | 11.9 | 345 |
| 35 | 13.0 | 444 |
| 50 | 15.0 | 600 |
| 70 | 16.9 | 815 |
| 95 | 19.1 | 1,079 |
| 120 | 21.0 | 1,325 |
| 150 | 23.0 | 1,604 |
| 185 | 25.5 | 2,020 |
| 240 | 29.0 | 2,636 |
| 300 | 32.0 | 3,219 |
| 400 | 35.5 | 4,087 |
| 500 | 39.5 | 5,213 |
| 630 | 44.0 | 6,712 |
| 800 | 48.5 | 8,368 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 12.1 | 14.478 | 0.459 | 0.505 | 21 | 27 | 21 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.423 | 0.470 | 27 | 35 | 28 | 35 | 0.29 |
| 4 | 4.61 | 5.516 | 0.404 | 0.450 | 37 | 46 | 38 | 45 | 0.46 |
| 6 | 3.08 | 3.685 | 0.380 | 0.426 | 46 | 57 | 48 | 57 | 0.69 |
| 10 | 1.83 | 2.190 | 0.350 | 0.396 | 64 | 76 | 65 | 76 | 1.15 |
| 16 | 1.15 | 1.376 | 0.327 | 0.374 | 84 | 98 | 87 | 97 | 1.84 |
| 25 | 0.727 | 0.870 | 0.312 | 0.358 | 114 | 127 | 117 | 125 | 2.88 |
| 35 | 0.524 | 0.627 | 0.299 | 0.345 | 140 | 152 | 144 | 150 | 4.03 |
| 50 | 0.387 | 0.464 | 0.290 | 0.336 | 172 | 180 | 177 | 178 | 5.75 |
| 70 | 0.268 | 0.321 | 0.280 | 0.326 | 218 | 220 | 225 | 218 | 8.05 |
| 95 | 0.193 | 0.232 | 0.274 | 0.321 | 270 | 264 | 278 | 260 | 10.93 |
| 120 | 0.153 | 0.184 | 0.269 | 0.315 | 315 | 300 | 325 | 296 | 13.80 |
| 150 | 0.124 | 0.150 | 0.266 | 0.313 | 362 | 336 | 373 | 331 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.264 | 0.310 | 420 | 379 | 433 | 374 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.261 | 0.307 | 503 | 439 | 518 | 432 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.258 | 0.305 | 580 | 494 | 598 | 486 | 34.50 |
| 400 | 0.0470 | 0.061 | 0.256 | 0.302 | 674 | 558 | 695 | 549 | 41.20 |
| 500 | 0.0366 | 0.049 | 0.252 | 0.299 | 781 | 629 | 806 | 618 | 51.50 |
| 630 | 0.0283 | 0.041 | 0.247 | 0.293 | 901 | 704 | 930 | 692 | 64.89 |
| 800 | 0.0221 | 0.035 | 0.242 | 0.289 | 1018 | 775 | 1052 | 762 | 82.40 |
NYY 2 x (1.5-300) mm2 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 12.5 | 200 |
| 2.5 | 13.4 | 242 |
| 4 | 15.4 | 330 |
| 6 | 16.5 | 399 |
| 10 | 18.4 | 538 |
| 16 | 20.5 | 713 |
| 25 | 24.0 | 1,001 |
| 35 | 26.0 | 1,274 |
| 50 | 29.5 | 1,536 |
| 70 | 33.0 | 2,066 |
| 95 | 37.5 | 2,787 |
| 120 | 41.0 | 3,371 |
| 150 | 45.0 | 4,114 |
| 185 | 50.0 | 5,128 |
| 240 | 56.0 | 6,581 |
| 300 | 62.0 | 8,130 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 40 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 51 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 70 | 80 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 93 | 104 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 123 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 151 | 162 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 182 | 191 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 230 | 236 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 280 | 281 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 325 | 321 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 371 | 361 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 424 | 406 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 501 | 470 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 572 | 528 | 34.50 |
NYY 3 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.0 | 224 |
| 2.5 | 14.0 | 277 |
| 4 | 16.1 | 383 |
| 6 | 17.3 | 471 |
| 10 | 19.4 | 649 |
| 16 | 22.0 | 875 |
| 25 | 25.0 | 1,248 |
| 35 | 27.5 | 1,606 |
| 50 | 30.0 | 1,857 |
| 70 | 34.0 | 2,556 |
| 95 | 38.5 | 3,428 |
| 120 | 41.5 | 4,152 |
| 150 | 46.0 | 5,115 |
| 185 | 50.5 | 6,330 |
| 240 | 57.0 | 8,215 |
| 300 | 62.5 | 10,116 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 19 | 23 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 26 | 31 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 34 | 40 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 44 | 50 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 60 | 68 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 79 | 88 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 105 | 114 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 129 | 137 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 162 | 168 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 203 | 206 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 250 | 247 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 289 | 281 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 330 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 381 | 356 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 451 | 412 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 517 | 464 | 34.50 |
NYY 4 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.8 | 259 |
| 2.5 | 15.0 | 324 |
| 4 | 17.3 | 453 |
| 6 | 18.7 | 563 |
| 10 | 21.5 | 794 |
| 16 | 23.5 | 1,083 |
| 25 | 27.5 | 1,558 |
| 35 | 30.0 | 2,018 |
| 50 | 35.5 | 2,466 |
| 70 | 39.0 | 3,334 |
| 95 | 44.5 | 4,491 |
| 120 | 48.5 | 5,504 |
| 150 | 54.5 | 6,787 |
| 185 | 59.0 | 8,392 |
| 240 | 66.0 | 10,818 |
| 300 | 72.5 | 13,326 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 22 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 29 | 35 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 39 | 46 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 50 | 57 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 68 | 77 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 90 | 99 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 121 | 128 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 149 | 154 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 173 | 173 | 5.75 |
| 70 | 0.268 | 0.321 | 0.238 | 215 | 212 | 8.05 |
| 95 | 0.193 | 0.232 | 0.238 | 266 | 255 | 10.93 |
| 120 | 0.153 | 0.184 | 0.233 | 308 | 289 | 13.80 |
| 150 | 0.124 | 0.150 | 0.233 | 357 | 327 | 17.25 |
| 185 | 0.0991 | 0.121 | 0.233 | 405 | 366 | 21.28 |
| 240 | 0.0754 | 0.093 | 0.232 | 482 | 425 | 27.60 |
| 300 | 0.0601 | 0.075 | 0.231 | 552 | 479 | 34.50 |
NYY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.8 | 302 |
| 2.5 | 16.0 | 382 |
| 4 | 18.7 | 541 |
| 6 | 20.5 | 677 |
| 10 | 23.0 | 954 |
| 16 | 26.0 | 1,309 |
| 25 | 30.0 | 1,895 |
| 35 | 33.0 | 2,478 |
| 50 | 38.0 | 3,161 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 14.478 | 0.328 | 23 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 0.304 | 30 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 0.303 | 41 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 0.288 | 52 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 0.269 | 71 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 0.255 | 94 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 0.255 | 126 | 131 | 2.88 |
| 35 | 0.524 | 0.627 | 0.246 | 155 | 157 | 4.03 |
| 50 | 0.387 | 0.464 | 0.247 | 189 | 185 | 5.75 |
SPLN 43-1
NYY 1 x (1.5-500) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 6.1 | 53 |
| 2.5 | 6.6 | 67 |
| 4 | 7.6 | 94 |
| 6 | 8.1 | 117 |
| 10 | 9.1 | 166 |
| 16 | 10.1 | 229 |
| 25 | 11.9 | 345 |
| 35 | 13.0 | 444 |
| 50 | 15.0 | 600 |
| 70 | 16.7 | 807 |
| 95 | 19.1 | 1,079 |
| 120 | 21.0 | 1,316 |
| 150 | 23.0 | 1,604 |
| 185 | 25.5 | 2,020 |
| 240 | 29.0 | 2,636 |
| 300 | 32.0 | 3,219 |
| 400 | 35.5 | 4,087 |
| 500 | 39.5 | 5,213 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 12.1 | 14.478 | 50 | 0.459 | 0.505 | 21 | 27 | 21 | 28 | 0.17 |
| 2.5 | 7.41 | 8.866 | 50 | 0.423 | 0.470 | 27 | 35 | 28 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.404 | 0.450 | 37 | 46 | 38 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.380 | 0.426 | 46 | 57 | 48 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.350 | 0.396 | 64 | 76 | 65 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.327 | 0.374 | 84 | 98 | 87 | 101 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.312 | 0.358 | 114 | 127 | 117 | 130 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.299 | 0.345 | 140 | 152 | 144 | 156 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.290 | 0.336 | 172 | 180 | 177 | 185 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.278 | 0.324 | 218 | 221 | 224 | 227 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.274 | 0.321 | 270 | 264 | 278 | 271 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.267 | 0.313 | 315 | 300 | 324 | 309 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.266 | 0.313 | 362 | 336 | 373 | 346 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.264 | 0.310 | 420 | 379 | 433 | 391 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.261 | 0.307 | 503 | 439 | 518 | 453 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.258 | 0.305 | 580 | 494 | 598 | 510 | 34.50 |
| 400 | 0.0470 | 0.061 | 20 | 0.256 | 0.302 | 674 | 558 | 695 | 577 | 41.20 |
| 500 | 0.0366 | 0.049 | 20 | 0.252 | 0.299 | 781 | 629 | 806 | 650 | 51.50 |
NYY 2 x (1.5-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 12.5 | 200 |
| 2.5 | 13.4 | 242 |
| 4 | 15.4 | 330 |
| 6 | 16.5 | 399 |
| 10 | 18.4 | 538 |
| 16 | 20.5 | 713 |
| 25 | 24.0 | 1,001 |
| 35 | 26.0 | 1,274 |
| 50 | 29.5 | 1,536 |
| 70 | 33.0 | 2,066 |
| 95 | 37.5 | 2,787 |
| 120 | 41.0 | 3,371 |
| 150 | 45.0 | 4,114 |
| 185 | 50.0 | 5,128 |
| 240 | 56.0 | 6,581 |
| 300 | 62.0 | 8,130 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 | 12.1 | 14.478 | 50 | 0.328 | 21 | 27 | 0.17 |
| 2.5 | 7.41 | 8.866 | 50 | 0.304 | 29 | 36 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.303 | 38 | 47 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 48 | 59 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 66 | 78 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 90 | 102 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 120 | 134 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 150 | 160 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 180 | 187 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 230 | 230 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 275 | 280 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 320 | 320 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 375 | 355 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 430 | 409 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 510 | 472 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 590 | 525 | 34.50 |
NYY 3 x (1.5-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.0 | 224 |
| 2.5 | 14.0 | 277 |
| 4 | 16.1 | 383 |
| 6 | 17.3 | 471 |
| 10 | 19.4 | 649 |
| 16 | 22.0 | 875 |
| 25 | 25.0 | 1,248 |
| 35 | 27.5 | 1,606 |
| 50 | 30.0 | 1,857 |
| 70 | 34.0 | 2,556 |
| 95 | 38.5 | 3,428 |
| 120 | 41.5 | 4,152 |
| 150 | 46.0 | 5,115 |
| 185 | 50.5 | 6,330 |
| 240 | 57.0 | 8,215 |
| 300 | 62.5 | 10,116 |
| 400 | 69.0 | 12,765 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 | 12.1 | 14.478 | 50 | 0.328 | 18 | 24 | 0.17 |
| 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 285 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYY 4 x (1.5-400) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 13.8 | 259 |
| 2.5 | 15.0 | 324 |
| 4 | 17.3 | 453 |
| 6 | 18.7 | 563 |
| 10 | 21.5 | 794 |
| 16 | 23.5 | 1,083 |
| 25 | 27.5 | 1,558 |
| 35 | 30.0 | 2,018 |
| 50 | 34.0 | 2,466 |
| 70 | 37.5 | 3,334 |
| 95 | 43.5 | 4,491 |
| 120 | 48.5 | 5,504 |
| 150 | 52.0 | 6,787 |
| 185 | 57.5 | 8,333 |
| 240 | 64.5 | 10,818 |
| 300 | 72.5 | 13,326 |
| 400 | 82.5 | 16,969 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 | 12.1 | 14.478 | 50 | 0.328 | 18 | 24 | 0.17 |
| 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.464 | 30 | 0.247 | 160 | 165 | 5.75 |
| 70 | 0.268 | 0.321 | 30 | 0.238 | 200 | 205 | 8.05 |
| 95 | 0.193 | 0.232 | 30 | 0.238 | 245 | 245 | 10.93 |
| 120 | 0.153 | 0.184 | 30 | 0.233 | 285 | 280 | 13.80 |
| 150 | 0.124 | 0.150 | 20 | 0.233 | 325 | 315 | 17.25 |
| 185 | 0.0991 | 0.121 | 20 | 0.233 | 370 | 355 | 21.28 |
| 240 | 0.0754 | 0.093 | 20 | 0.232 | 435 | 415 | 27.60 |
| 300 | 0.0601 | 0.075 | 20 | 0.231 | 500 | 465 | 34.50 |
| 400 | 0.0470 | 0.060 | 20 | 0.229 | 600 | 535 | 41.20 |
NYY 5 x (1.5-50) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.8 | 302 |
| 2.5 | 16.0 | 382 |
| 4 | 18.7 | 541 |
| 6 | 20.5 | 677 |
| 10 | 23.0 | 954 |
| 16 | 26.0 | 1,309 |
| 25 | 30.0 | 1,895 |
| 35 | 33.0 | 2,478 |
| 50 | 38.0 | 3,161 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 70°C Max. (Ω/km) | Insulation Insulation Resistance at 20°C Min. (M.Ω.km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|
| (mH/km) | |||||||
| 1.5 | 12.1 | 14.478 | 50 | 0.328 | 18 | 24 | 0.17 |
| 2.5 | 7.41 | 8.866 | 50 | 0.304 | 25 | 32 | 0.29 |
| 4 | 4.61 | 5.516 | 50 | 0.303 | 34 | 41 | 0.46 |
| 6 | 3.08 | 3.685 | 50 | 0.288 | 44 | 52 | 0.69 |
| 10 | 1.83 | 2.190 | 50 | 0.269 | 60 | 69 | 1.15 |
| 16 | 1.15 | 1.376 | 40 | 0.255 | 80 | 89 | 1.84 |
| 25 | 0.727 | 0.870 | 40 | 0.255 | 105 | 116 | 2.88 |
| 35 | 0.524 | 0.627 | 40 | 0.246 | 130 | 138 | 4.03 |
| 50 | 0.387 | 0.463 | 40 | 0.247 | 160 | 165 | 5.75 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.
Minta penawaran untuk NYY
Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.