N2XSB(AL)Y
Cu / XLPE/ CTS / PVC / ATA / PVC Deskripsi
Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed
Aplikasi
- For installation indoor, in ground direct burried, for power station and switchgear, if there is a risk that low mechanical damage may occur
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XSB(AL)Y dari dalam ke luar — sesuai kode konstruksi Cu / XLPE/ CTS / PVC / ATA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai pita aluminium (ATA)
Aluminium tape armourPerisai non-magnetik — dipakai pada kabel inti tunggal agar tidak timbul rugi induksi.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
N2XSB(AL)Y 1 x (25-630) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 21.5 | 729 |
| 35 | 22.5 | 856 |
| 50 | 23.5 | 998 |
| 70 | 25.5 | 1,244 |
| 95 | 27.0 | 1,531 |
| 120 | 28.5 | 1,804 |
| 150 | 30.0 | 2,058 |
| 185 | 32.0 | 2,451 |
| 240 | 35.0 | 3,077 |
| 300 | 37.5 | 3,720 |
| 400 | 41.0 | 4,554 |
| 500 | 45.5 | 5,715 |
| 630 | 49.0 | 7,136 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Co Max. (A) | Short circuit current at 1 sec nductor Screen Max. Max. (kA) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.437 | 0.484 | 164 | 153 | 168 | 157 | 3.58 1.14 |
| 35 | 0.524 | 0.668 | 0.415 | 0.461 | 199 | 183 | 204 | 188 | 5.01 1.14 |
| 50 | 0.387 | 0.494 | 0.398 | 0.444 | 237 | 216 | 243 | 221 | 7.15 1.14 |
| 70 | 0.268 | 0.342 | 0.374 | 0.421 | 296 | 264 | 304 | 270 1 | 0.01 1.14 |
| 95 | 0.193 | 0.247 | 0.358 | 0.404 | 360 | 316 | 369 | 323 1 | 3.59 1.14 |
| 120 | 0.153 | 0.196 | 0.346 | 0.392 | 416 | 358 | 426 | 366 1 | 7.16 1.14 |
| 150 | 0.124 | 0.159 | 0.334 | 0.380 | 473 | 402 | 484 | 410 2 | 1.45 1.14 |
| 185 | 0.0991 | 0.128 | 0.325 | 0.371 | 541 | 453 | 554 | 462 2 | 6.46 1.14 |
| 240 | 0.0754 | 0.098 | 0.316 | 0.362 | 639 | 523 | 654 | 533 3 | 4.32 1.14 |
| 300 | 0.0601 | 0.079 | 0.309 | 0.356 | 733 | 588 | 748 | 598 4 | 2.90 1.14 |
| 400 | 0.0470 | 0.063 | 0.300 | 0.346 | 851 | 667 | 868 | 677 5 | 7.20 1.14 |
| 500 | 0.0366 | 0.051 | 0.294 | 0.341 | 979 | 751 | 997 | 760 7 | 1.50 1.14 |
| 630 | 0.0283 | 0.041 | 0.286 | 0.332 | 1120 | 840 | 1136 | 848 9 | 0.09 1.14 |
N2XSB(AL)Y 1 x (25-630) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 23.5 | 812 |
| 35 | 24.5 | 941 |
| 50 | 25.5 | 1,086 |
| 70 | 27.0 | 1,337 |
| 95 | 29.0 | 1,641 |
| 120 | 30.5 | 1,862 |
| 150 | 32.0 | 2,175 |
| 185 | 34.0 | 2,589 |
| 240 | 36.5 | 3,196 |
| 300 | 39.0 | 3,762 |
| 400 | 42.0 | 4,631 |
| 500 | 46.0 | 5,767 |
| 630 | 49.5 | 7,192 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) ( | Short circuit current at 1 sec ductor Screen ax. Max. kA) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.454 | 0.500 | 166 | 153 | 170 | 156 3 | .58 1.14 |
| 35 | 0.524 | 0.668 | 0.431 | 0.477 | 201 | 183 | 206 | 187 5 | .01 1.14 |
| 50 | 0.387 | 0.494 | 0.413 | 0.459 | 240 | 216 | 246 | 221 7 | .15 1.14 |
| 70 | 0.268 | 0.342 | 0.389 | 0.435 | 299 | 264 | 307 | 270 1 | 0.01 1.14 |
| 95 | 0.193 | 0.247 | 0.373 | 0.419 | 363 | 315 | 372 | 322 1 | 3.59 1.14 |
| 120 | 0.153 | 0.196 | 0.358 | 0.404 | 418 | 358 | 428 | 365 1 | 7.16 1.14 |
| 150 | 0.124 | 0.159 | 0.347 | 0.393 | 476 | 401 | 487 | 410 2 | 1.45 1.14 |
| 185 | 0.0991 | 0.128 | 0.338 | 0.385 | 545 | 452 | 557 | 461 2 | 6.46 1.14 |
| 240 | 0.0754 | 0.098 | 0.326 | 0.372 | 642 | 523 | 657 | 532 3 | 4.32 1.14 |
| 300 | 0.0601 | 0.079 | 0.316 | 0.362 | 734 | 588 | 750 | 598 4 | 2.90 1.14 |
| 400 | 0.0470 | 0.063 | 0.305 | 0.351 | 852 | 666 | 869 | 677 5 | 7.20 1.14 |
| 500 | 0.0366 | 0.051 | 0.297 | 0.343 | 980 | 750 | 997 | 760 7 | 1.50 1.14 |
| 630 | 0.0283 | 0.041 | 0.289 | 0.335 | 1120 | 840 | 1137 | 848 9 | 0.09 1.14 |
N2XSB(AL)Y 1 x (25-630) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 25.5 | 919 |
| 35 | 26.5 | 1,052 |
| 50 | 27.5 | 1,200 |
| 70 | 29.5 | 1,428 |
| 95 | 31.0 | 1,722 |
| 120 | 33.0 | 2,033 |
| 150 | 34.5 | 2,339 |
| 185 | 36.5 | 2,745 |
| 240 | 39.0 | 3,303 |
| 300 | 41.0 | 3,913 |
| 400 | 45.0 | 4,834 |
| 500 | 48.5 | 5,942 |
| 630 | 52.0 | 7,379 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Co Max. (A) | Short circuit current at 1 sec nductor Screen Max. Max. (kA) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.473 | 0.519 | 168 | 153 | 172 | 156 | 3.58 1.14 |
| 35 | 0.524 | 0.668 | 0.448 | 0.495 | 203 | 183 | 208 | 187 | 5.01 1.14 |
| 50 | 0.387 | 0.494 | 0.430 | 0.476 | 242 | 216 | 248 | 220 | 7.15 1.14 |
| 70 | 0.268 | 0.342 | 0.405 | 0.451 | 302 | 263 | 309 | 269 1 | 0.01 1.14 |
| 95 | 0.193 | 0.247 | 0.387 | 0.433 | 366 | 315 | 374 | 321 1 | 3.59 1.14 |
| 120 | 0.153 | 0.196 | 0.376 | 0.422 | 422 | 357 | 431 | 364 1 | 7.16 1.14 |
| 150 | 0.124 | 0.159 | 0.363 | 0.409 | 479 | 401 | 490 | 409 2 | 1.45 1.14 |
| 185 | 0.0991 | 0.128 | 0.352 | 0.399 | 548 | 452 | 560 | 460 2 | 6.46 1.14 |
| 240 | 0.0754 | 0.098 | 0.338 | 0.385 | 645 | 522 | 659 | 532 3 | 4.32 1.14 |
| 300 | 0.0601 | 0.079 | 0.327 | 0.374 | 738 | 588 | 753 | 598 4 | 2.90 1.14 |
| 400 | 0.0470 | 0.063 | 0.317 | 0.363 | 855 | 667 | 871 | 676 5 | 7.20 1.14 |
| 500 | 0.0366 | 0.050 | 0.307 | 0.353 | 984 | 752 | 1000 | 761 7 | 1.50 1.14 |
| 630 | 0.0283 | 0.041 | 0.297 | 0.344 | 1125 | 842 | 1141 | 850 9 | 0.09 1.14 |
N2XSB(AL)Y 1 x (35-630) mm2 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 29.0 | 1,172 |
| 50 | 30.0 | 1,281 |
| 70 | 31.5 | 1,554 |
| 95 | 33.5 | 1,884 |
| 120 | 35.5 | 2,173 |
| 150 | 37.0 | 2,483 |
| 185 | 38.5 | 2,839 |
| 240 | 41.0 | 3,441 |
| 300 | 43.5 | 4,076 |
| 400 | 47.0 | 5,011 |
| 500 | 50.5 | 6,131 |
| 630 | 54.0 | 7,580 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Con Max. M (A) ( | Short circuit current at 1 sec ductor Screen ax. Max. kA) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 35 | 0.524 | 0.668 | 0.465 | 0.511 | 205 | 183 | 210 | 187 5 | .01 1.14 |
| 50 | 0.387 | 0.494 | 0.445 | 0.491 | 244 | 215 | 249 | 220 7 | .15 1.14 |
| 70 | 0.268 | 0.342 | 0.420 | 0.466 | 304 | 263 | 311 | 269 1 | 0.01 1.14 |
| 95 | 0.193 | 0.247 | 0.404 | 0.450 | 368 | 314 | 376 | 320 1 | 3.59 1.14 |
| 120 | 0.153 | 0.196 | 0.389 | 0.435 | 424 | 357 | 433 | 364 1 | 7.16 1.14 |
| 150 | 0.124 | 0.159 | 0.376 | 0.422 | 482 | 400 | 492 | 408 2 | 1.45 1.14 |
| 185 | 0.0991 | 0.127 | 0.364 | 0.410 | 550 | 451 | 562 | 460 2 | 6.46 1.14 |
| 240 | 0.0754 | 0.098 | 0.349 | 0.395 | 648 | 522 | 661 | 532 3 | 4.32 1.14 |
| 300 | 0.0601 | 0.079 | 0.338 | 0.384 | 740 | 588 | 755 | 597 4 | 2.90 1.14 |
| 400 | 0.0470 | 0.063 | 0.327 | 0.373 | 858 | 667 | 873 | 676 5 | 7.20 1.14 |
| 500 | 0.0366 | 0.050 | 0.316 | 0.362 | 986 | 752 | 1002 | 761 7 | 1.50 1.14 |
| 630 | 0.0283 | 0.041 | 0.306 | 0.352 | 1128 | 843 | 1143 | 850 9 | 0.09 1.14 |
N2XSB(AL)Y 1 x (50-630) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 35.5 | 1,639 |
| 70 | 37.5 | 1,913 |
| 95 | 39.0 | 2,185 |
| 120 | 40.5 | 2,467 |
| 150 | 42.5 | 2,806 |
| 185 | 44.5 | 3,252 |
| 240 | 47.0 | 3,895 |
| 300 | 49.5 | 4,553 |
| 400 | 52.5 | 5,475 |
| 500 | 56.0 | 6,623 |
| 630 | 60.0 | 8,158 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Co Max. (A) | Short circuit current at 1 sec nductor Screen Max. Max. (kA) (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 0.494 | 0.481 | 0.528 | 248 | 214 | 253 | 219 | 7.15 1.14 |
| 70 | 0.268 | 0.342 | 0.453 | 0.500 | 308 | 262 | 314 | 268 1 | 0.01 1.14 |
| 95 | 0.193 | 0.247 | 0.434 | 0.480 | 372 | 313 | 380 | 319 1 | 3.59 1.14 |
| 120 | 0.153 | 0.196 | 0.417 | 0.463 | 428 | 356 | 437 | 363 1 | 7.16 1.14 |
| 150 | 0.124 | 0.159 | 0.403 | 0.449 | 486 | 399 | 496 | 407 2 | 1.45 1.14 |
| 185 | 0.0991 | 0.127 | 0.391 | 0.438 | 554 | 450 | 565 | 459 2 | 6.46 1.14 |
| 240 | 0.0754 | 0.098 | 0.376 | 0.422 | 652 | 521 | 664 | 530 3 | 4.32 1.14 |
| 300 | 0.0601 | 0.078 | 0.364 | 0.410 | 744 | 587 | 757 | 596 4 | 2.90 1.14 |
| 400 | 0.0470 | 0.062 | 0.349 | 0.395 | 861 | 666 | 876 | 676 5 | 7.20 1.14 |
| 500 | 0.0366 | 0.050 | 0.337 | 0.383 | 990 | 753 | 1005 | 761 7 | 1.50 1.14 |
| 630 | 0.0283 | 0.040 | 0.327 | 0.373 | 1132 | 845 | 1145 | 852 9 | 0.09 1.14 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.