PT. Hartaperindo Sejahtera — Distributor Resmi Kabelmetal Indonesia
182 tipe produk — spesifikasi resmi Kabelmetal Indonesia

N2XSEBY

Cu / XLPE / CTS / PVC / STA / PVC
3.6/6 kV IEC 60502-2

Deskripsi

Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed

Aplikasi

  • For installation indoor, in ground direct burried, for power station and switchgear, if there is a risk that low mechanical damage may occur

Susunan lapisan N2XSEBY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC / STA / PVC.

Penampang konstruksi kabel N2XSEBY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  5. 5

    Perisai pita baja (STA)

    Steel tape armour

    Proteksi mekanis terhadap benturan & tekanan — untuk penanaman langsung.

  6. 6

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XSEBY.

Spesifikasi Teknis

N2XSEBY 3 x (25-300) mm² 3.6/6 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 38.5 2,417
35 41.0 2,865
50 44.0 3,391
70 48.0 4,272
95 51.5 5,266
120 55.5 6,232
150 59.0 7,271
185 63.0 8,585
240 69.0 10,679
300 75.5 12,965
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.342 152 146 3.58 1.03
35 0.524 0.668 0.325 184 175 5.01 1.03
50 0.387 0.494 0.313 219 206 7.15 1.03
70 0.268 0.342 0.296 273 251 10.01 1.03
95 0.193 0.247 0.285 330 299 13.59 1.03
120 0.153 0.196 0.276 379 339 17.16 1.03
150 0.124 0.160 0.268 430 380 21.45 1.03
185 0.0991 0.128 0.262 491 427 26.46 1.03
240 0.0754 0.099 0.255 575 492 34.32 1.37
300 0.0601 0.080 0.252 651 549 42.90 1.37

N2XSEBY 3 x (25-300) mm² 6/10 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 43.0 2,767
35 46.0 3,279
50 48.5 3,799
70 52.5 4,687
95 56.5 5,753
120 60.0 6,690
150 63.5 7,761
185 67.5 9,091
240 73.0 11,235
300 78.0 13,326
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.368 154 146 3.58 1.03
35 0.524 0.668 0.349 186 175 5.01 1.03
50 0.387 0.494 0.335 222 205 7.15 1.03
70 0.268 0.342 0.316 276 251 10.01 1.03
95 0.193 0.247 0.303 333 299 13.59 1.03
120 0.153 0.196 0.293 382 339 17.16 1.03
150 0.124 0.160 0.284 433 380 21.45 1.03
185 0.0991 0.128 0.277 493 427 26.46 1.37
240 0.0754 0.099 0.267 576 491 34.32 1.37
300 0.0601 0.080 0.261 654 550 42.90 1.37

N2XSEBY 3 x (25-300) mm2 8.7/15 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 48.5 3,293
35 51.0 3,790
50 53.5 4,324
70 58.0 5,310
95 61.5 6,354
120 65.0 7,321
150 69.0 8,412
185 73.0 9,854
240 78.5 11,980
300 85.0 14,914
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.395 156 146 3.58 1.03
35 0.524 0.668 0.374 189 174 5.01 1.03
50 0.387 0.494 0.359 224 205 7.15 1.03
70 0.268 0.342 0.338 278 250 10.01 1.03
95 0.193 0.247 0.324 336 298 13.59 1.03
120 0.153 0.196 0.312 385 339 17.16 1.03
150 0.124 0.159 0.302 436 379 21.45 1.37
185 0.0991 0.128 0.294 495 426 26.46 1.37
240 0.0754 0.098 0.283 578 490 34.32 1.37
300 0.0601 0.080 0.275 654 546 42.90 1.37

N2XSEBY 3 x (35-300) mm² 12/20 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
35 56.5 4,322
50 59.0 4,883
70 63.0 5,836
95 66.5 6,905
120 70.0 7,907
150 74.0 9,096
185 77.5 10,488
240 84.5 13,454
300 89.5 15,722
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
35 0.524 0.668 0.395 190 174 5.01 1.03
50 0.387 0.494 0.379 226 205 7.15 1.03
70 0.268 0.342 0.357 280 250 10.01 1.03
95 0.193 0.247 0.341 338 298 13.59 1.37
120 0.153 0.196 0.328 387 338 17.16 1.37
150 0.124 0.159 0.318 437 378 21.45 1.37
185 0.0991 0.128 0.308 497 426 26.46 1.37
240 0.0754 0.098 0.296 580 488 34.32 1.37
300 0.0601 0.079 0.287 655 545 42.90 1.37

N2XSEBY 3 x (50-300) mm² 18/30 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
50 71.0 6,335
70 75.0 7,435
95 79.0 8,574
120 83.5 10,439
150 87.0 11,661
185 91.0 13,200
240 96.5 15,483
300 102.0 17,950
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
50 0.387 0.494 0.421 229 204 7.15 1.37
70 0.268 0.342 0.396 282 249 10.01 1.37
95 0.193 0.247 0.378 340 297 13.59 1.37
120 0.153 0.196 0.364 390 336 17.16 1.37
150 0.124 0.159 0.351 441 376 21.45 1.37
185 0.0991 0.128 0.340 500 423 26.46 1.37
240 0.0754 0.098 0.326 582 486 34.32 1.37
300 0.0601 0.079 0.315 656 543 42.90 1.37

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.

Minta penawaran untuk N2XSEBY

Tim kami siap membantu pemilihan ukuran dan pengadaan untuk proyek Anda.

Hubungi Kami