N2XSEFGbY

Cu / XLPE / CTS / PVC / SFWA / PVC
3.6/6 kV IEC 60502-2

Deskripsi

Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed

Aplikasi

  • For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation

Susunan lapisan N2XSEFGbY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC / SFWA / PVC.

Penampang konstruksi kabel N2XSEFGbY — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Isolasi XLPE

    Cross-linked polyethylene

    Isolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.

  3. 3

    Pelindung pita tembaga (CTS)

    Copper tape screen

    Layar pita tembaga — pemerataan medan listrik & proteksi sentuh.

  4. 4

    Selubung dalam PVC

    Polyvinyl chloride

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  5. 5

    Perisai kawat baja pipih (SFWA)

    Steel flat-wire armour

    Proteksi mekanis berat — penanaman langsung & tarikan panjang.

  6. 6

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XSEFGbY.

Spesifikasi Teknis

N2XSEFGbY 3 x (25-300) mm² 3.6/6 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 38.5 2,603
35 41.5 3,074
50 44.5 3,641
70 48.5 4,536
95 52.0 5,542
120 56.0 6,516
150 59.5 7,593
185 63.0 8,940
240 69.0 11,074
300 75.5 13,395
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.342 152 147 3.58 1.03
35 0.524 0.668 0.325 185 175 5.01 1.03
50 0.387 0.494 0.313 219 205 7.15 1.03
70 0.268 0.342 0.296 273 251 10.01 1.03
95 0.193 0.247 0.285 330 299 13.59 1.03
120 0.153 0.196 0.276 379 339 17.16 1.03
150 0.124 0.160 0.268 430 379 21.45 1.03
185 0.0991 0.128 0.262 490 427 26.46 1.03
240 0.0754 0.099 0.255 573 490 34.32 1.37
300 0.0601 0.080 0.252 649 547 42.90 1.37

N2XSEFGbY 3 x (25-300) mm² 6/10 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 43.0 2,984
35 46.0 3,515
50 48.5 4,061
70 52.5 4,955
95 56.5 6,055
120 60.0 7,026
150 63.5 8,110
185 67.5 9,478
240 73.5 11,663
300 78.5 13,814
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.368 155 147 3.58 1.03
35 0.524 0.668 0.349 187 175 5.01 1.03
50 0.387 0.494 0.335 222 205 7.15 1.03
70 0.268 0.342 0.316 276 251 10.01 1.03
95 0.193 0.247 0.303 333 298 13.59 1.03
120 0.153 0.196 0.293 382 339 17.16 1.03
150 0.124 0.160 0.284 433 379 21.45 1.03
185 0.0991 0.128 0.277 493 426 26.46 1.37
240 0.0754 0.099 0.267 574 489 34.32 1.37
300 0.0601 0.080 0.261 650 546 42.90 1.37

N2XSEFGbY 3 x (25-300) mm² 8,7/15 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
25 49.0 3,552
35 51.5 4,072
50 54.0 4,606
70 58.5 5,619
95 62.0 6,697
120 65.5 7,705
150 69.0 8,810
185 73.0 10,284
240 79.0 12,429
300 83.5 14,586
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 0.395 156 146 3.58 1.03
35 0.524 0.668 0.374 189 174 5.01 1.03
50 0.387 0.494 0.359 225 205 7.15 1.03
70 0.268 0.342 0.338 278 250 10.01 1.03
95 0.193 0.247 0.324 336 298 13.59 1.03
120 0.153 0.196 0.312 385 338 17.16 1.03
150 0.124 0.159 0.302 435 378 21.45 1.37
185 0.0991 0.128 0.294 494 424 26.46 1.37
240 0.0754 0.098 0.283 577 488 34.32 1.37
300 0.0601 0.080 0.275 654 547 42.90 1.37

N2XSEFGbY 3 x (35-300) mm² 12/20 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
35 56.5 4,624
50 59.0 5,185
70 63.0 6,194
95 66.5 7,276
120 70.0 8,318
150 74.0 9,516
185 78.0 10,981
240 83.5 13,130
300 88.5 15,374
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
35 0.524 0.668 0.395 190 174 5.01 1.03
50 0.387 0.494 0.379 226 205 7.15 1.03
70 0.268 0.342 0.357 280 250 10.01 1.03
95 0.193 0.247 0.341 338 298 13.59 1.37
120 0.153 0.196 0.328 387 338 17.16 1.37
150 0.124 0.159 0.318 437 377 21.45 1.37
185 0.0991 0.128 0.308 496 424 26.46 1.37
240 0.0754 0.098 0.296 579 488 34.32 1.37
300 0.0601 0.079 0.287 655 546 42.90 1.37

N2XSEFGbY 3 x (50-300) mm² 18/30 kV

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
50 71.0 6,738
70 75.5 7,869
95 79.0 9,021
120 82.5 10,109
150 86.0 11,335
185 90.0 12,808
240 95.5 15,124
300 101.0 17,512
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Conductor Max. (kA) Screen Max. (kA)
50 0.387 0.494 0.421 229 204 7.15 1.37
70 0.268 0.342 0.396 282 249 10.01 1.37
95 0.193 0.247 0.378 340 296 13.59 1.37
120 0.153 0.196 0.364 389 336 17.16 1.37
150 0.124 0.159 0.351 440 376 21.45 1.37
185 0.0991 0.128 0.340 500 423 26.46 1.37
240 0.0754 0.098 0.326 582 487 34.32 1.37
300 0.0601 0.079 0.315 657 545 42.90 1.37

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.