N2XSERY
Cu / XLPE / CTS / PVC / SWA / PVC Deskripsi
Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed
Aplikasi
- For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XSERY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC / SWA / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat baja bulat (SWA)
Steel round-wire armourProteksi mekanis + kekuatan tarik tinggi.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
N2XSERY 3 x (25-300) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 41.0 | 3,102 |
| 35 | 43.5 | 3,587 |
| 50 | 48.0 | 4,576 |
| 70 | 52.0 | 5,579 |
| 95 | 55.5 | 6,642 |
| 120 | 59.5 | 7,711 |
| 150 | 63.0 | 8,859 |
| 185 | 67.0 | 10,280 |
| 240 | 73.0 | 12,529 |
| 300 | 81.0 | 15,860 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.342 | 155 | 148 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.325 | 188 | 176 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.313 | 224 | 207 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.296 | 279 | 253 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.285 | 337 | 302 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.276 | 386 | 342 | 17.16 | 1.03 |
| 150 | 0.124 | 0.160 | 0.268 | 438 | 382 | 21.45 | 1.03 |
| 185 | 0.0991 | 0.128 | 0.262 | 499 | 430 | 26.46 | 1.03 |
| 240 | 0.0754 | 0.099 | 0.255 | 584 | 495 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.252 | 662 | 552 | 42.90 | 1.37 |
N2XSERY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 46.5 | 3,907 |
| 35 | 50.0 | 4,496 |
| 50 | 52.5 | 5,103 |
| 70 | 56.5 | 6,093 |
| 95 | 60.5 | 7,262 |
| 120 | 64.0 | 8,309 |
| 150 | 67.5 | 9,448 |
| 185 | 71.0 | 10,884 |
| 240 | 78.5 | 14,033 |
| 300 | 83.5 | 16,345 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.368 | 158 | 148 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.349 | 191 | 176 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.335 | 227 | 207 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.316 | 281 | 253 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.303 | 339 | 301 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.293 | 389 | 341 | 17.16 | 1.03 |
| 150 | 0.124 | 0.160 | 0.284 | 440 | 382 | 21.45 | 1.03 |
| 185 | 0.0991 | 0.128 | 0.277 | 501 | 430 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.099 | 0.267 | 585 | 493 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.261 | 663 | 551 | 42.90 | 1.37 |
N2XSERY 3 x (25-300) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 52.5 | 4,594 |
| 35 | 55.0 | 5,174 |
| 50 | 57.5 | 5,755 |
| 70 | 62.0 | 6,876 |
| 95 | 65.5 | 7,989 |
| 120 | 69.0 | 9,065 |
| 150 | 73.0 | 10,266 |
| 185 | 78.5 | 12,655 |
| 240 | 84.0 | 14,959 |
| 300 | 89.0 | 17,314 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.395 | 159 | 147 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.374 | 192 | 176 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.359 | 229 | 207 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.338 | 283 | 252 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.324 | 341 | 300 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.312 | 391 | 341 | 17.16 | 1.03 |
| 150 | 0.124 | 0.159 | 0.302 | 442 | 381 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.294 | 503 | 428 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.283 | 587 | 492 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.275 | 664 | 550 | 42.90 | 1.37 |
N2XSERY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 60.5 | 5,831 |
| 50 | 62.5 | 6,479 |
| 70 | 66.5 | 7,534 |
| 95 | 70.5 | 8,673 |
| 120 | 74.0 | 9,784 |
| 150 | 79.5 | 11,920 |
| 185 | 83.0 | 13,514 |
| 240 | 89.0 | 15,860 |
| 300 | 93.5 | 18,224 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.524 | 0.668 | 0.395 | 193 | 175 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.379 | 229 | 206 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.357 | 284 | 252 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.341 | 343 | 300 | 13.59 | 1.37 |
| 120 | 0.153 | 0.196 | 0.328 | 393 | 340 | 17.16 | 1.37 |
| 150 | 0.124 | 0.159 | 0.318 | 444 | 380 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.308 | 504 | 427 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.296 | 587 | 491 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.079 | 0.287 | 665 | 550 | 42.90 | 1.37 |
N2XSERY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 76.0 | 9,043 |
| 70 | 80.5 | 10,271 |
| 95 | 84.0 | 11,550 |
| 120 | 87.5 | 12,764 |
| 150 | 91.5 | 14,133 |
| 185 | 95.5 | 15,733 |
| 240 | 100.5 | 18,203 |
| 300 | 106.0 | 20,795 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 0.494 | 0.421 | 232 | 205 | 7.15 | 1.37 |
| 70 | 0.268 | 0.342 | 0.396 | 287 | 250 | 10.01 | 1.37 |
| 95 | 0.193 | 0.247 | 0.378 | 345 | 298 | 13.59 | 1.37 |
| 120 | 0.153 | 0.196 | 0.364 | 395 | 338 | 17.16 | 1.37 |
| 150 | 0.124 | 0.159 | 0.351 | 445 | 378 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.340 | 506 | 426 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.326 | 589 | 490 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.079 | 0.315 | 664 | 547 | 42.90 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.