N2XSEY
Cu / XLPE / CTS / PVC Deskripsi
Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed
Aplikasi
- Indoors, cable trunking, outdoors and in ground; For power stations, industry and switchgear
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XSEY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
N2XSEY 3 x (25-300) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 37.0 | 1,868 |
| 35 | 39.5 | 2,275 |
| 50 | 42.5 | 2,778 |
| 70 | 46.5 | 3,577 |
| 95 | 50.0 | 4,517 |
| 120 | 54.0 | 5,422 |
| 150 | 57.5 | 6,406 |
| 185 | 61.5 | 7,662 |
| 240 | 67.5 | 9,664 |
| 300 | 74.0 | 11,852 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.342 | 149 | 145 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.325 | 181 | 173 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.313 | 215 | 204 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.296 | 268 | 249 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.285 | 325 | 297 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.276 | 374 | 337 | 17.16 | 1.03 |
| 150 | 0.124 | 0.160 | 0.268 | 425 | 378 | 21.45 | 1.03 |
| 185 | 0.0991 | 0.128 | 0.262 | 486 | 426 | 26.46 | 1.03 |
| 240 | 0.0754 | 0.099 | 0.255 | 570 | 492 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.252 | 648 | 551 | 42.90 | 1.37 |
N2XSEY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 41.0 | 2,153 |
| 35 | 44.0 | 2,618 |
| 50 | 46.5 | 3,101 |
| 70 | 50.5 | 3,927 |
| 95 | 55.0 | 4,957 |
| 120 | 58.5 | 5,841 |
| 150 | 62.0 | 6,858 |
| 185 | 66.0 | 8,132 |
| 240 | 71.5 | 10,156 |
| 300 | 76.5 | 12,205 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.368 | 152 | 145 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.349 | 183 | 173 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.335 | 218 | 204 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.316 | 272 | 249 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.303 | 328 | 297 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.293 | 377 | 337 | 17.16 | 1.03 |
| 150 | 0.124 | 0.160 | 0.284 | 428 | 378 | 21.45 | 1.03 |
| 185 | 0.0991 | 0.128 | 0.277 | 488 | 426 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.099 | 0.267 | 572 | 491 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.261 | 651 | 551 | 42.90 | 1.37 |
N2XSEY 3 x (25-300) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 47.0 | 2,592 |
| 35 | 49.5 | 3,048 |
| 50 | 52.0 | 3,546 |
| 70 | 56.5 | 4,463 |
| 95 | 60.0 | 5,452 |
| 120 | 63.5 | 6,364 |
| 150 | 67.0 | 7,401 |
| 185 | 71.5 | 8,778 |
| 240 | 77.0 | 10,820 |
| 300 | 82.0 | 12,912 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.395 | 154 | 145 | 3.58 | 1.03 |
| 35 | 0.524 | 0.668 | 0.374 | 186 | 173 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.359 | 221 | 204 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.338 | 275 | 249 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.324 | 332 | 297 | 13.59 | 1.03 |
| 120 | 0.153 | 0.196 | 0.312 | 381 | 337 | 17.16 | 1.03 |
| 150 | 0.124 | 0.159 | 0.302 | 432 | 378 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.294 | 491 | 425 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.283 | 576 | 491 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.080 | 0.275 | 654 | 551 | 42.90 | 1.37 |
N2XSEY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 54.5 | 3,501 |
| 50 | 57.0 | 4,026 |
| 70 | 61.0 | 4,917 |
| 95 | 65.0 | 5,960 |
| 120 | 68.5 | 6,909 |
| 150 | 72.5 | 8,039 |
| 185 | 76.5 | 9,374 |
| 240 | 82.0 | 11,458 |
| 300 | 86.5 | 13,563 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.524 | 0.668 | 0.395 | 188 | 173 | 5.01 | 1.03 |
| 50 | 0.387 | 0.494 | 0.379 | 223 | 203 | 7.15 | 1.03 |
| 70 | 0.268 | 0.342 | 0.357 | 277 | 249 | 10.01 | 1.03 |
| 95 | 0.193 | 0.247 | 0.341 | 334 | 297 | 13.59 | 1.37 |
| 120 | 0.153 | 0.196 | 0.328 | 384 | 337 | 17.16 | 1.37 |
| 150 | 0.124 | 0.159 | 0.318 | 433 | 377 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.308 | 494 | 425 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.296 | 578 | 491 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.079 | 0.287 | 657 | 552 | 42.90 | 1.37 |
N2XSEY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 69.0 | 5,294 |
| 70 | 73.5 | 6,326 |
| 95 | 77.0 | 7,410 |
| 120 | 81.0 | 8,466 |
| 150 | 84.5 | 9,600 |
| 185 | 88.5 | 11,005 |
| 240 | 93.5 | 13,151 |
| 300 | 99.0 | 15,481 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 0.494 | 0.421 | 227 | 203 | 7.15 | 1.37 |
| 70 | 0.268 | 0.342 | 0.396 | 280 | 248 | 10.01 | 1.37 |
| 95 | 0.193 | 0.247 | 0.378 | 338 | 296 | 13.59 | 1.37 |
| 120 | 0.153 | 0.196 | 0.364 | 387 | 336 | 17.16 | 1.37 |
| 150 | 0.124 | 0.159 | 0.351 | 438 | 377 | 21.45 | 1.37 |
| 185 | 0.0991 | 0.128 | 0.340 | 498 | 425 | 26.46 | 1.37 |
| 240 | 0.0754 | 0.098 | 0.326 | 583 | 491 | 34.32 | 1.37 |
| 300 | 0.0601 | 0.079 | 0.315 | 660 | 552 | 42.90 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.