N2XSY
Cu / XLPE / CTS / PVC Deskripsi
Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed
Aplikasi
- For power stations and switchgear as well as stations because of small bending radius in confined spaces indoors. As underground because of light weight where installation conditions are difficult
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XSY dari dalam ke luar — sesuai kode konstruksi Cu / XLPE / CTS / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
N2XSY 1 x (25-630) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 17.1 | 531 |
| 35 | 18.2 | 646 |
| 50 | 19.2 | 777 |
| 70 | 21.0 | 1,005 |
| 95 | 22.5 | 1,276 |
| 120 | 24.5 | 1,519 |
| 150 | 25.5 | 1,759 |
| 185 | 27.5 | 2,131 |
| 240 | 30.5 | 2,711 |
| 300 | 33.0 | 3,308 |
| 400 | 36.5 | 4,116 |
| 500 | 40.5 | 5,192 |
| 630 | 44.0 | 6,567 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Condu Max (kA | ctor Screen . Max. ) (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.394 | 0.441 | 156 | 152 | 160 | 156 | 3.5 | 8 1.14 |
| 35 | 0.524 | 0.668 | 0.374 | 0.420 | 190 | 182 | 195 | 187 | 5.0 | 1 1.14 |
| 50 | 0.387 | 0.494 | 0.359 | 0.405 | 227 | 214 | 233 | 220 | 7.1 | 5 1.14 |
| 70 | 0.268 | 0.342 | 0.339 | 0.385 | 285 | 263 | 293 | 270 | 10.0 | 1 1.14 |
| 95 | 0.193 | 0.247 | 0.325 | 0.371 | 348 | 314 | 357 | 322 | 13.5 | 9 1.14 |
| 120 | 0.153 | 0.196 | 0.313 | 0.359 | 403 | 358 | 414 | 367 | 17.1 | 6 1.14 |
| 150 | 0.124 | 0.159 | 0.302 | 0.348 | 459 | 401 | 472 | 411 | 21.4 | 5 1.14 |
| 185 | 0.0991 | 0.128 | 0.295 | 0.341 | 528 | 452 | 543 | 463 | 26.4 | 6 1.14 |
| 240 | 0.0754 | 0.098 | 0.288 | 0.334 | 627 | 523 | 644 | 536 | 34.3 | 2 1.14 |
| 300 | 0.0601 | 0.079 | 0.282 | 0.329 | 721 | 590 | 741 | 603 | 42.9 | 0 1.14 |
| 400 | 0.0470 | 0.064 | 0.276 | 0.323 | 842 | 669 | 864 | 684 | 57.2 | 0 1.14 |
| 500 | 0.0366 | 0.051 | 0.271 | 0.318 | 974 | 755 | 999 | 772 | 71.5 | 0 1.14 |
| 630 | 0.0283 | 0.042 | 0.265 | 0.311 | 1118 | 846 | 1146 | 864 | 90.0 | 9 1.14 |
N2XSY 1 x (25-630) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 18.9 | 594 |
| 35 | 20.5 | 712 |
| 50 | 21.5 | 846 |
| 70 | 23.0 | 1,078 |
| 95 | 24.5 | 1,353 |
| 120 | 26.0 | 1,559 |
| 150 | 27.5 | 1,853 |
| 185 | 29.5 | 2,218 |
| 240 | 32.0 | 2,794 |
| 300 | 34.0 | 3,334 |
| 400 | 37.5 | 4,163 |
| 500 | 41.0 | 5,217 |
| 630 | 44.5 | 6,595 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Condu Max (kA) | ctor Screen . Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.415 | 0.461 | 159 | 152 | 163 | 156 | 3.58 | 1.14 |
| 35 | 0.524 | 0.668 | 0.393 | 0.440 | 193 | 182 | 198 | 187 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.377 | 0.423 | 231 | 215 | 237 | 220 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.355 | 0.402 | 290 | 263 | 297 | 270 | 10.0 | 1 1.14 |
| 95 | 0.193 | 0.247 | 0.340 | 0.387 | 353 | 314 | 362 | 322 | 13.5 | 9 1.14 |
| 120 | 0.153 | 0.196 | 0.327 | 0.373 | 407 | 357 | 418 | 366 | 17.1 | 6 1.14 |
| 150 | 0.124 | 0.159 | 0.318 | 0.364 | 465 | 401 | 477 | 410 | 21.4 | 5 1.14 |
| 185 | 0.0991 | 0.128 | 0.308 | 0.354 | 534 | 453 | 548 | 463 | 26.4 | 6 1.14 |
| 240 | 0.0754 | 0.098 | 0.298 | 0.344 | 632 | 524 | 649 | 536 | 34.3 | 2 1.14 |
| 300 | 0.0601 | 0.079 | 0.290 | 0.336 | 724 | 590 | 744 | 603 | 42.9 | 0 1.14 |
| 400 | 0.0470 | 0.064 | 0.281 | 0.327 | 844 | 670 | 867 | 685 | 57.2 | 0 1.14 |
| 500 | 0.0366 | 0.051 | 0.273 | 0.320 | 975 | 756 | 1001 | 772 | 71.5 | 0 1.14 |
| 630 | 0.0283 | 0.042 | 0.267 | 0.313 | 1119 | 847 | 1148 | 865 | 90.0 | 9 1.14 |
N2XSY 1 x (25-630) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 21.5 | 678 |
| 35 | 22.5 | 799 |
| 50 | 23.5 | 936 |
| 70 | 25.0 | 1,134 |
| 95 | 27.0 | 1,423 |
| 120 | 28.5 | 1,673 |
| 150 | 30.0 | 1,974 |
| 185 | 32.0 | 2,345 |
| 240 | 34.0 | 2,875 |
| 300 | 36.5 | 3,475 |
| 400 | 40.0 | 4,317 |
| 500 | 43.5 | 5,384 |
| 630 | 47.0 | 6,775 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Condu Max (kA | ctor Screen . Max. ) (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 25 | 0.727 | 0.927 | 0.437 | 0.484 | 162 | 152 | 166 | 156 | 3.5 | 8 1.14 |
| 35 | 0.524 | 0.668 | 0.415 | 0.461 | 197 | 182 | 202 | 186 | 5.0 | 1 1.14 |
| 50 | 0.387 | 0.494 | 0.398 | 0.444 | 235 | 215 | 241 | 220 | 7.1 | 5 1.14 |
| 70 | 0.268 | 0.342 | 0.373 | 0.419 | 293 | 263 | 301 | 269 | 10.0 | 1 1.14 |
| 95 | 0.193 | 0.247 | 0.358 | 0.405 | 357 | 314 | 366 | 321 | 13.5 | 9 1.14 |
| 120 | 0.153 | 0.196 | 0.345 | 0.391 | 412 | 357 | 423 | 365 | 17.1 | 6 1.14 |
| 150 | 0.124 | 0.159 | 0.335 | 0.381 | 470 | 400 | 482 | 410 | 21.4 | 5 1.14 |
| 185 | 0.0991 | 0.128 | 0.325 | 0.371 | 539 | 452 | 553 | 463 | 26.4 | 6 1.14 |
| 240 | 0.0754 | 0.098 | 0.312 | 0.359 | 637 | 524 | 653 | 536 | 34.3 | 2 1.14 |
| 300 | 0.0601 | 0.079 | 0.304 | 0.350 | 730 | 590 | 749 | 603 | 42.9 | 0 1.14 |
| 400 | 0.0470 | 0.063 | 0.294 | 0.340 | 850 | 670 | 872 | 685 | 57.2 | 0 1.14 |
| 500 | 0.0366 | 0.051 | 0.285 | 0.331 | 982 | 757 | 1007 | 774 | 71.5 | 0 1.14 |
| 630 | 0.0283 | 0.042 | 0.277 | 0.324 | 1127 | 850 | 1155 | 868 | 90.0 | 9 1.14 |
N2XSY 1 x (35-630) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 24.5 | 884 |
| 50 | 25.5 | 984 |
| 70 | 27.5 | 1,236 |
| 95 | 29.0 | 1,518 |
| 120 | 30.5 | 1,786 |
| 150 | 32.0 | 2,078 |
| 185 | 34.0 | 2,414 |
| 240 | 36.5 | 3,004 |
| 300 | 38.5 | 3,595 |
| 400 | 42.0 | 4,447 |
| 500 | 45.5 | 5,523 |
| 630 | 49.0 | 6,926 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Condu Max (kA) | ctor Screen . Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 35 | 0.524 | 0.668 | 0.432 | 0.478 | 200 | 182 | 204 | 186 | 5.01 | 1.14 |
| 50 | 0.387 | 0.494 | 0.413 | 0.459 | 238 | 214 | 243 | 219 | 7.15 | 1.14 |
| 70 | 0.268 | 0.342 | 0.390 | 0.437 | 297 | 262 | 304 | 269 | 10.0 | 1 1.14 |
| 95 | 0.193 | 0.247 | 0.373 | 0.419 | 361 | 314 | 369 | 321 | 13.5 | 9 1.14 |
| 120 | 0.153 | 0.196 | 0.360 | 0.407 | 416 | 357 | 427 | 365 | 17.1 | 6 1.14 |
| 150 | 0.124 | 0.159 | 0.348 | 0.394 | 474 | 401 | 486 | 410 | 21.4 | 5 1.14 |
| 185 | 0.0991 | 0.128 | 0.337 | 0.384 | 542 | 452 | 556 | 462 | 26.4 | 6 1.14 |
| 240 | 0.0754 | 0.098 | 0.325 | 0.371 | 641 | 524 | 657 | 536 | 34.3 | 2 1.14 |
| 300 | 0.0601 | 0.079 | 0.315 | 0.361 | 735 | 590 | 753 | 604 | 42.9 | 0 1.14 |
| 400 | 0.0470 | 0.063 | 0.304 | 0.350 | 855 | 672 | 876 | 686 | 57.2 | 0 1.14 |
| 500 | 0.0366 | 0.051 | 0.294 | 0.341 | 987 | 759 | 1011 | 775 | 71.5 | 0 1.14 |
| 630 | 0.0283 | 0.041 | 0.286 | 0.332 | 1133 | 853 | 1160 | 871 | 90.0 | 9 1.14 |
N2XSY 1 x (50-630) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 31.0 | 1,249 |
| 70 | 33.0 | 1,517 |
| 95 | 34.5 | 1,756 |
| 120 | 36.0 | 2,036 |
| 150 | 37.5 | 2,337 |
| 185 | 39.5 | 2,741 |
| 240 | 42.0 | 3,334 |
| 300 | 44.0 | 3,961 |
| 400 | 47.5 | 4,841 |
| 500 | 51.0 | 5,945 |
| 630 | 54.5 | 7,378 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Condu Max (kA | ctor Screen . Max. ) (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 0.494 | 0.453 | 0.499 | 243 | 214 | 249 | 219 | 7.1 | 5 1.14 |
| 70 | 0.268 | 0.342 | 0.428 | 0.474 | 303 | 262 | 310 | 268 | 10.0 | 1 1.14 |
| 95 | 0.193 | 0.247 | 0.408 | 0.454 | 367 | 313 | 375 | 320 | 13.5 | 9 1.14 |
| 120 | 0.153 | 0.196 | 0.393 | 0.439 | 423 | 356 | 433 | 364 | 17.1 | 6 1.14 |
| 150 | 0.124 | 0.159 | 0.379 | 0.425 | 481 | 400 | 492 | 409 | 21.4 | 5 1.14 |
| 185 | 0.0991 | 0.127 | 0.368 | 0.414 | 550 | 451 | 563 | 462 | 26.4 | 6 1.14 |
| 240 | 0.0754 | 0.098 | 0.353 | 0.399 | 649 | 524 | 664 | 535 | 34.3 | 2 1.14 |
| 300 | 0.0601 | 0.079 | 0.342 | 0.388 | 742 | 591 | 760 | 603 | 42.9 | 0 1.14 |
| 400 | 0.0470 | 0.063 | 0.328 | 0.375 | 863 | 673 | 883 | 687 | 57.2 | 0 1.14 |
| 500 | 0.0366 | 0.050 | 0.318 | 0.364 | 995 | 762 | 1018 | 777 | 71.5 | 0 1.14 |
| 630 | 0.0283 | 0.041 | 0.308 | 0.354 | 1143 | 858 | 1168 | 875 | 90.0 | 9 1.14 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.