NA2XSERY
Al / XLPE / CTS / PVC / SWA / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed
Aplikasi
- For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XSERY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / CTS / PVC / SWA / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung dalam PVC
Polyvinyl chlorideBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 5
Perisai kawat baja bulat (SWA)
Steel round-wire armourProteksi mekanis + kekuatan tarik tinggi.
- 6
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XSERY 3 x (25-300) mm² 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 40.5 | 2,589 |
| 35 | 43.5 | 2,993 |
| 50 | 48.0 | 3,705 |
| 70 | 52.0 | 4,324 |
| 95 | 56.0 | 4,947 |
| 120 | 59.5 | 5,541 |
| 150 | 62.5 | 6,126 |
| 185 | 67.0 | 6,886 |
| 240 | 72.5 | 8,037 |
| 300 | 80.0 | 10,170 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.346 | 120 | 114 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.326 | 145 | 137 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.314 | 173 | 161 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.296 | 217 | 197 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.284 | 262 | 235 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.276 | 301 | 266 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.269 | 340 | 297 | 14.10 | 1.03 |
| 185 | 0.164 | 0.212 | 0.262 | 390 | 337 | 17.39 | 1.03 |
| 240 | 0.125 | 0.162 | 0.256 | 457 | 389 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.253 | 521 | 436 | 28.20 | 1.37 |
NA2XSERY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 46.5 | 3,417 |
| 35 | 49.5 | 3,840 |
| 50 | 52.0 | 4,225 |
| 70 | 56.5 | 4,837 |
| 95 | 60.5 | 5,535 |
| 120 | 64.0 | 6,139 |
| 150 | 67.0 | 6,712 |
| 185 | 71.0 | 7,490 |
| 240 | 78.0 | 9,474 |
| 300 | 83.0 | 10,662 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.372 | 122 | 114 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.350 | 147 | 136 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.336 | 175 | 160 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.316 | 219 | 197 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.303 | 263 | 234 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.293 | 303 | 266 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.285 | 342 | 297 | 14.10 | 1.03 |
| 185 | 0.164 | 0.211 | 0.277 | 392 | 336 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.268 | 459 | 387 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.261 | 521 | 435 | 28.20 | 1.37 |
NA2XSERY 3 x (25-300) mm² 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 52.0 | 4,099 |
| 35 | 55.0 | 4,509 |
| 50 | 57.5 | 4,882 |
| 70 | 62.0 | 5,620 |
| 95 | 66.0 | 6,296 |
| 120 | 69.0 | 6,895 |
| 150 | 72.5 | 7,486 |
| 185 | 78.5 | 9,262 |
| 240 | 83.5 | 10,461 |
| 300 | 88.5 | 11,679 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.400 | 123 | 114 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.376 | 149 | 136 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.361 | 177 | 160 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.338 | 219 | 196 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.323 | 265 | 233 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.312 | 304 | 265 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.304 | 343 | 296 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.294 | 393 | 335 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.284 | 460 | 387 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.276 | 522 | 434 | 28.20 | 1.37 |
NA2XSERY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 60.0 | 5,172 |
| 50 | 62.5 | 5,557 |
| 70 | 66.5 | 6,279 |
| 95 | 70.5 | 6,990 |
| 120 | 74.0 | 7,614 |
| 150 | 79.0 | 9,176 |
| 185 | 83.0 | 10,120 |
| 240 | 88.5 | 11,358 |
| 300 | 93.0 | 12,519 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.868 | 1.113 | 0.397 | 150 | 136 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.380 | 178 | 160 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.357 | 221 | 196 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.340 | 267 | 233 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.328 | 306 | 265 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.319 | 344 | 295 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.308 | 394 | 334 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.297 | 460 | 386 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.289 | 522 | 433 | 28.20 | 1.37 |
NA2XSERY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 76.0 | 8,156.2 |
| 70 | 80.5 | 9,015.5 |
| 95 | 84.5 | 9,832.9 |
| 120 | 87.5 | 10,594.3 |
| 150 | 91.0 | 11,381.5 |
| 185 | 95.5 | 12,339.3 |
| 240 | 100.0 | 13,628.8 |
| 300 | 105.5 | 15,076.6 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.641 | 0.822 | 0.423 | 180 | 159 | 4.70 | 1.37 |
| 70 | 0.443 | 0.568 | 0.396 | 223 | 195 | 6.58 | 1.37 |
| 95 | 0.320 | 0.411 | 0.377 | 268 | 232 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.364 | 308 | 264 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.353 | 346 | 294 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.340 | 395 | 333 | 17.39 | 1.37 |
| 240 | 0.125 | 0.161 | 0.327 | 461 | 384 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.317 | 521 | 431 | 28.20 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.