NA2XSEY
Al / XLPE / CTS / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed
Aplikasi
- Indoors, cable trunking, outdoors and in ground; For power stations, industry and switchgear
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XSEY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / CTS / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Pelindung pita tembaga (CTS)
Copper tape screenLayar pita tembaga — pemerataan medan listrik & proteksi sentuh.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Spesifikasi Teknis
NA2XSEY 3 x (25-300) mm2 3.6/6 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 36.5 | 1,380 |
| 35 | 39.5 | 1,620 |
| 50 | 42.0 | 1,908 |
| 70 | 46.5 | 2,322 |
| 95 | 50.0 | 2,781 |
| 120 | 54.0 | 3,252 |
| 150 | 57.0 | 3,673 |
| 185 | 61.5 | 4,268 |
| 240 | 67.0 | 5,172 |
| 300 | 73.0 | 6,226 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.346 | 115 | 112 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.326 | 140 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.314 | 166 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.296 | 208 | 193 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.284 | 253 | 231 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.276 | 291 | 262 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.269 | 329 | 293 | 14.10 | 1.03 |
| 185 | 0.164 | 0.212 | 0.262 | 379 | 333 | 17.39 | 1.03 |
| 240 | 0.125 | 0.162 | 0.256 | 446 | 385 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.253 | 508 | 433 | 28.20 | 1.37 |
NA2XSEY 3 x (25-300) mm² 6/10 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 40.5 | 1,663 |
| 35 | 44.0 | 1,962 |
| 50 | 46.5 | 2,224 |
| 70 | 50.5 | 2,672 |
| 95 | 55.0 | 3,230 |
| 120 | 58.5 | 3,671 |
| 150 | 61.5 | 4,122 |
| 185 | 66.0 | 4,738 |
| 240 | 71.0 | 5,661 |
| 300 | 76.0 | 6,586 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.372 | 117 | 112 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.350 | 142 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.336 | 169 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.316 | 211 | 194 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.303 | 255 | 230 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.293 | 294 | 262 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.285 | 332 | 293 | 14.10 | 1.03 |
| 185 | 0.164 | 0.211 | 0.277 | 381 | 332 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.268 | 447 | 384 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.261 | 510 | 433 | 28.20 | 1.37 |
NA2XSEY 3 x (25-300) mm2 8.7/15 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 25 | 46.5 | 2,097 |
| 35 | 49.5 | 2,384 |
| 50 | 52.0 | 2,673 |
| 70 | 56.5 | 3,207 |
| 95 | 60.0 | 3,719 |
| 120 | 63.5 | 4,194 |
| 150 | 66.5 | 4,662 |
| 185 | 71.5 | 5,384 |
| 240 | 76.5 | 6,321 |
| 300 | 81.5 | 7,277 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 25 | 1.20 | 1.539 | 0.400 | 119 | 112 | 2.35 | 1.03 |
| 35 | 0.868 | 1.113 | 0.376 | 144 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.361 | 171 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.338 | 213 | 193 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.323 | 258 | 231 | 8.93 | 1.03 |
| 120 | 0.253 | 0.325 | 0.312 | 297 | 262 | 11.28 | 1.03 |
| 150 | 0.206 | 0.265 | 0.304 | 335 | 293 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.294 | 383 | 332 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.284 | 449 | 384 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.276 | 512 | 432 | 28.20 | 1.37 |
NA2XSEY 3 x (35-300) mm² 12/20 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 35 | 54.5 | 2,842 |
| 50 | 57.0 | 3,144 |
| 70 | 61.0 | 3,661 |
| 95 | 65.0 | 4,238 |
| 120 | 68.5 | 4,739 |
| 150 | 72.0 | 5,296 |
| 185 | 76.5 | 5,980 |
| 240 | 81.5 | 6,956 |
| 300 | 86.0 | 7,922 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 35 | 0.868 | 1.113 | 0.397 | 145 | 134 | 3.29 | 1.03 |
| 50 | 0.641 | 0.822 | 0.380 | 173 | 158 | 4.70 | 1.03 |
| 70 | 0.443 | 0.568 | 0.357 | 215 | 193 | 6.58 | 1.03 |
| 95 | 0.320 | 0.411 | 0.340 | 260 | 230 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.328 | 298 | 262 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.319 | 336 | 292 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.308 | 385 | 332 | 17.39 | 1.37 |
| 240 | 0.125 | 0.162 | 0.297 | 451 | 384 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.289 | 514 | 432 | 28.20 | 1.37 |
NA2XSEY 3 x (50-300) mm² 18/30 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 50 | 69.0 | 4,407 |
| 70 | 73.5 | 5,071 |
| 95 | 77.5 | 5,693 |
| 120 | 81.0 | 6,296 |
| 150 | 84.0 | 6,848 |
| 185 | 88.5 | 7,611 |
| 240 | 93.0 | 8,641 |
| 300 | 98.5 | 9,826 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Conductor Max. (kA) | Screen Max. (kA) |
|---|---|---|---|---|---|---|---|
| 50 | 0.641 | 0.822 | 0.423 | 175 | 157 | 4.70 | 1.37 |
| 70 | 0.443 | 0.568 | 0.396 | 217 | 192 | 6.58 | 1.37 |
| 95 | 0.320 | 0.411 | 0.377 | 263 | 230 | 8.93 | 1.37 |
| 120 | 0.253 | 0.325 | 0.364 | 301 | 261 | 11.28 | 1.37 |
| 150 | 0.206 | 0.265 | 0.353 | 339 | 292 | 14.10 | 1.37 |
| 185 | 0.164 | 0.211 | 0.340 | 388 | 331 | 17.39 | 1.37 |
| 240 | 0.125 | 0.161 | 0.327 | 454 | 384 | 22.56 | 1.37 |
| 300 | 0.100 | 0.130 | 0.317 | 515 | 431 | 28.20 | 1.37 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.