N2XBY (FRC)

Cu / Mica / XLPE / DATA / PVC
0.6/1 kV IEC 60502-1 and IEC 60331

Deskripsi

Copper Conductor, Mica Tape, XLPE Insulated, Double Aluminium Tape Armor, PVC Sheathed

Aplikasi

  • For wiring of fire resistant safety circuits, such as fire alarm system, emergency lighting and power, public address and emergency voice communication systems in highrise building, control and instrumentation services in industrial, commercial and residential complexes

Susunan lapisan N2XBY (FRC) dari dalam ke luar — sesuai kode konstruksi Cu / Mica / XLPE / DATA / PVC.

Penampang konstruksi kabel N2XBY (FRC) — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Pita mika (mica tape)

    Mica tape

    Penghalang api — menjaga integritas sirkuit saat kebakaran (fire resistant, IEC 60331).

  3. 3

    Selubung dalam XLPE

    Cross-linked polyethylene

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  4. 4

    Perisai pita aluminium ganda (DATA)

    Double aluminium tape armour

    Dua lapis pita aluminium — perisai non-magnetik untuk kabel inti tunggal.

  5. 5

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XBY (FRC).

Spesifikasi Teknis

FIRE RESISTANT CABLES

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
16 15.5 386
25 16.9 494
35 18.0 602
50 19.4 749
70 21.5 988
95 23.5 1,254
120 25.5 1,535
150 27.5 1,823
185 30.0 2,209
240 33.0 2,864
300 36.0 3,445
400 39.5 4,358
500 44.0 5,465
630 48.5 6,968
800 54.0 8,765
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
16 1.15 1.466 0.414 0.460 118 118 121 121 2.29
25 0.727 0.927 0.385 0.431 154 153 158 157 3.58
35 0.524 0.668 0.366 0.412 188 183 193 188 5.01
50 0.387 0.494 0.348 0.394 229 217 235 223 7.15
70 0.268 0.342 0.331 0.377 287 265 295 272 10.01
95 0.193 0.247 0.316 0.362 352 317 361 324 13.59
120 0.153 0.196 0.307 0.353 407 359 418 367 17.16
150 0.124 0.159 0.302 0.348 465 402 476 410 21.45
185 0.0991 0.128 0.296 0.342 537 453 549 461 26.46
240 0.0754 0.098 0.287 0.333 636 523 648 529 34.32
300 0.0601 0.079 0.281 0.327 728 585 739 590 42.90
400 0.0470 0.064 0.278 0.325 838 655 846 657 57.20
500 0.0366 0.051 0.273 0.319 960 731 964 728 71.50
630 0.0283 0.042 0.267 0.313 1092 807 1087 797 90.09
800 0.0221 0.035 0.264 0.310 1216 877 1202 858 114.40

FIRE RESISTANT CABLES — tabel lanjutan (2)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 15.6 336
2.5 16.5 387
4 17.6 456
6 19.1 543
10 21.0 694
16 22.5 831
25 25.5 1,130
35 27.5 1,408
50 30.5 1,738
70 35.0 2,386
95 39.5 3,391
120 43.5 4,056
150 48.5 4,964
185 53.0 5,944
240 58.5 7,407
300 64.0 9,001
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 29 34 0.21
2.5 7.41 9.449 0.293 39 45 0.36
4 4.61 5.878 0.275 51 59 0.57
6 3.08 3.927 0.263 65 74 0.86
10 1.83 2.334 0.248 89 100 1.43
16 1.15 1.466 0.238 118 130 2.29
25 0.727 0.927 0.240 157 167 3.58
35 0.524 0.668 0.233 193 201 5.01
50 0.387 0.494 0.232 233 239 7.15
70 0.268 0.342 0.229 295 293 10.01
95 0.193 0.247 0.224 360 350 13.59
120 0.153 0.196 0.223 423 401 17.16
150 0.124 0.160 0.224 482 449 21.45
185 0.0991 0.128 0.225 551 505 26.46
240 0.0754 0.099 0.223 652 584 34.32
300 0.0601 0.080 0.221 744 656 42.90

FIRE RESISTANT CABLES — tabel lanjutan (3)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 16.3 371
2.5 17.3 433
4 18.5 517
6 20.5 624
10 22.5 813
16 23.5 998
25 27.0 1,382
35 29.5 1,745
50 32.5 2,168
70 38.5 3,346
95 42.0 4,251
120 46.0 5,122
150 51.5 6,268
185 56.5 7,573
240 62.5 9,633
300 68.5 11,670
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 25 29 0.21
2.5 7.41 9.449 0.293 33 38 0.36
4 4.61 5.878 0.275 43 50 0.57
6 3.08 3.927 0.263 55 62 0.86
10 1.83 2.334 0.248 75 84 1.43
16 1.15 1.467 0.238 100 109 2.29
25 0.727 0.927 0.240 133 140 3.58
35 0.524 0.669 0.233 164 169 5.01
50 0.387 0.494 0.232 202 205 7.15
70 0.268 0.343 0.229 255 250 10.01
95 0.193 0.247 0.224 312 299 13.59
120 0.153 0.197 0.223 366 342 17.16
150 0.124 0.160 0.224 418 382 21.45
185 0.0991 0.129 0.225 483 433 26.46
240 0.0754 0.099 0.223 569 499 34.32
300 0.0601 0.081 0.221 652 561 42.90

FIRE RESISTANT CABLES — tabel lanjutan (4)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 17.6 423
2.5 18.7 499
4 20.0 603
6 22.0 734
10 24.5 970
16 25.5 1,206
25 29.5 1,689
35 32.5 2,164
50 37.0 3,115
70 42.5 4,163
95 46.5 5,334
120 51.5 6,547
150 57.0 7,897
185 62.5 9,698
240 69.5 12,255
300 75.5 14,895
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 27 32 0.21
2.5 7.41 9.449 0.293 36 42 0.36
4 4.61 5.878 0.275 48 55 0.57
6 3.08 3.927 0.263 60 68 0.86
10 1.83 2.334 0.248 83 91 1.43
16 1.15 1.467 0.238 110 118 2.29
25 0.727 0.927 0.240 148 152 3.58
35 0.524 0.669 0.233 183 183 5.01
50 0.387 0.494 0.232 214 210 7.15
70 0.268 0.343 0.229 269 256 10.01
95 0.193 0.247 0.224 334 309 13.59
120 0.153 0.197 0.223 386 350 17.16
150 0.124 0.160 0.224 449 395 21.45
185 0.0991 0.129 0.225 512 444 26.46
240 0.0754 0.099 0.223 604 513 34.32
300 0.0601 0.081 0.221 692 577 42.90

Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.