N2XY (FRC)

Cu / Mica / XLPE / PVC
0.6/1 kV IEC 60502-1 and IEC 60331

Deskripsi

Copper Conductor, Mica Tape, XLPE Insulated, PVC Sheathed

Aplikasi

  • For wiring of fire resistant safety circuits, such as fire alarm system, emergency lighting and power, public address and emergency voice communication systems in highrise building, control and instrumentation services in industrial, commercial and residential complexes

Susunan lapisan N2XY (FRC) dari dalam ke luar — sesuai kode konstruksi Cu / Mica / XLPE / PVC.

Penampang konstruksi kabel N2XY (FRC) — ilustrasi resmi KMI
Ilustrasi resmi katalog KMI
  1. 1

    Konduktor tembaga

    Copper conductor

    Penghantar arus utama — tembaga anil, solid / stranded / compacted.

  2. 2

    Pita mika (mica tape)

    Mica tape

    Penghalang api — menjaga integritas sirkuit saat kebakaran (fire resistant, IEC 60331).

  3. 3

    Selubung dalam XLPE

    Cross-linked polyethylene

    Bantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.

  4. 4

    Selubung luar PVC

    Polyvinyl chloride

    Selubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.

Datasheet Resmi KMI

Unduh lembar data pabrik (PDF) untuk N2XY (FRC).

Spesifikasi Teknis

FIRE RESISTANT CABLES

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 6.8 58
2.5 7.2 72
4 7.8 92
6 8.4 115
10 9.4 162
16 10.4 222
25 12.2 332
35 13.3 427
50 15.0 576
70 16.9 782
95 18.9 1,030
120 21.0 1,274
150 23.0 1,550
185 25.5 1,951
240 29.0 2,543
300 31.5 3,080
400 35.0 3,935
500 39.5 5,025
630 44.0 6,526
800 49.0 8,181
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Trefoil formation (mH/km) Flat formation (mH/km) Current - Carrying Capacity at 30° C * in air Max. (A) in ground Max. (A) in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
1.5 12.1 15.429 0.478 0.524 25 33 26 33 0.21
2.5 7.41 9.449 0.441 0.487 34 43 35 43 0.36
4 4.61 5.878 0.409 0.455 45 56 46 55 0.57
6 3.08 3.927 0.387 0.433 57 69 58 68 0.86
10 1.83 2.333 0.356 0.402 78 92 80 91 1.43
16 1.15 1.466 0.333 0.379 104 118 107 117 2.29
25 0.727 0.927 0.317 0.363 141 152 145 151 3.58
35 0.524 0.668 0.303 0.349 173 182 178 180 5.01
50 0.387 0.494 0.290 0.336 213 216 220 214 7.15
70 0.268 0.342 0.280 0.326 271 265 279 261 10.01
95 0.193 0.247 0.272 0.318 335 316 346 312 13.59
120 0.153 0.196 0.268 0.314 392 359 404 355 17.16
150 0.124 0.160 0.267 0.313 451 403 466 397 21.45
185 0.0991 0.128 0.265 0.311 526 455 543 449 26.46
240 0.0754 0.099 0.260 0.306 630 527 650 519 34.32
300 0.0601 0.080 0.255 0.301 728 593 751 584 42.90
400 0.0470 0.064 0.254 0.300 848 671 875 660 57.20
500 0.0366 0.052 0.251 0.297 985 757 1018 744 71.50
630 0.0283 0.043 0.247 0.293 1141 849 1179 834 90.09
800 0.0221 0.036 0.244 0.291 1295 937 1339 921 114.40

FIRE RESISTANT CABLES — tabel lanjutan (2)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 14.5 255
2.5 15.5 301
4 16.6 363
6 18.0 441
10 19.9 582
16 22.0 758
25 25.0 1,050
35 27.5 1,324
50 30.0 1,626
70 34.5 2,248
95 38.0 2,873
120 41.5 3,486
150 46.5 4,337
185 51.0 5,256
240 56.5 6,644
300 62.5 8,207
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 29 34 0.21
2.5 7.41 9.449 0.293 38 44 0.36
4 4.61 5.878 0.275 50 58 0.57
6 3.08 3.927 0.263 64 73 0.86
10 1.83 2.334 0.248 88 98 1.43
16 1.15 1.466 0.238 116 128 2.29
25 0.727 0.927 0.240 154 165 3.58
35 0.524 0.668 0.233 190 199 5.01
50 0.387 0.494 0.232 230 236 7.15
70 0.268 0.342 0.229 292 292 10.01
95 0.193 0.247 0.224 356 348 13.59
120 0.153 0.196 0.223 414 397 17.16
150 0.124 0.160 0.224 474 445 21.45
185 0.0991 0.128 0.225 544 502 26.46
240 0.0754 0.099 0.223 644 582 34.32
300 0.0601 0.080 0.221 737 654 42.90

FIRE RESISTANT CABLES — tabel lanjutan (3)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 15.2 282
2.5 16.2 338
4 17.4 415
6 18.9 511
10 21.0 689
16 23.5 915
25 26.5 1,289
35 29.0 1,646
50 32.0 2,039
70 37.0 2,828
95 40.5 3,682
120 44.5 4,496
150 50.0 5,575
185 54.5 6,814
240 61.0 8,794
300 66.5 10,755
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 21 28 0.21
2.5 7.41 9.449 0.293 32 37 0.36
4 4.61 5.878 0.275 43 49 0.57
6 3.08 3.927 0.263 54 61 0.86
10 1.83 2.334 0.248 74 83 1.43
16 1.15 1.467 0.238 99 107 2.29
25 0.727 0.927 0.240 131 139 3.58
35 0.524 0.669 0.233 162 167 5.01
50 0.387 0.494 0.232 200 203 7.15
70 0.268 0.343 0.229 252 248 10.01
95 0.193 0.247 0.224 309 298 13.59
120 0.153 0.197 0.223 359 339 17.16
150 0.124 0.160 0.224 411 379 21.45
185 0.0991 0.129 0.225 475 430 26.46
240 0.0754 0.099 0.223 562 497 34.32
300 0.0601 0.081 0.221 645 560 42.90

FIRE RESISTANT CABLES — tabel lanjutan (4)

Data Konstruksi
Nom. Cross Section Area Overall Diameter approx. Cable Weight approx.
mm² mm kg/km
1.5 16.3 323
2.5 17.5 392
4 18.8 488
6 20.5 606
10 23.0 839
16 25.5 1,125
25 29.0 1,602
35 32.0 2,073
50 36.0 2,628
70 41.0 3,586
95 44.5 4,700
120 50.0 5,848
150 55.5 7,148
185 61.0 8,849
240 67.5 11,313
300 74.0 13,867
Data Elektrik
Conductor Nom. Cross Sect. (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km) Inductance Current - Carrying Capacity at 30°C * in air Max. (A) in ground Max. (A) Short circuit current at 1 sec Max. (kA)
(mH/km)
1.5 12.1 15.429 0.315 27 31 0.21
2.5 7.41 9.449 0.293 35 41 0.36
4 4.61 5.878 0.275 47 53 0.57
6 3.08 3.927 0.263 59 67 0.86
10 1.83 2.334 0.248 81 89 1.43
16 1.15 1.467 0.238 108 116 2.29
25 0.727 0.927 0.240 146 151 3.58
35 0.524 0.669 0.233 180 181 5.01
50 0.387 0.494 0.232 212 208 7.15
70 0.268 0.343 0.229 265 254 10.01
95 0.193 0.247 0.224 327 305 13.59
120 0.153 0.197 0.223 379 347 17.16
150 0.124 0.160 0.224 442 392 21.45
185 0.0991 0.129 0.225 504 441 26.46
240 0.0754 0.099 0.223 597 511 34.32
300 0.0601 0.081 0.221 685 576 42.90