N2XY (FRC)
Cu / Mica / XLPE / PVC Deskripsi
Copper Conductor, Mica Tape, XLPE Insulated, PVC Sheathed
Aplikasi
- For wiring of fire resistant safety circuits, such as fire alarm system, emergency lighting and power, public address and emergency voice communication systems in highrise building, control and instrumentation services in industrial, commercial and residential complexes
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan N2XY (FRC) dari dalam ke luar — sesuai kode konstruksi Cu / Mica / XLPE / PVC.
- 1
Konduktor tembaga
Copper conductorPenghantar arus utama — tembaga anil, solid / stranded / compacted.
- 2
Pita mika (mica tape)
Mica tapePenghalang api — menjaga integritas sirkuit saat kebakaran (fire resistant, IEC 60331).
- 3
Selubung dalam XLPE
Cross-linked polyethyleneBantalan (bedding) — alas perisai/pelindung dan pengikat inti kabel.
- 4
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk N2XY (FRC).
Spesifikasi Teknis
FIRE RESISTANT CABLES
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 6.8 | 58 |
| 2.5 | 7.2 | 72 |
| 4 | 7.8 | 92 |
| 6 | 8.4 | 115 |
| 10 | 9.4 | 162 |
| 16 | 10.4 | 222 |
| 25 | 12.2 | 332 |
| 35 | 13.3 | 427 |
| 50 | 15.0 | 576 |
| 70 | 16.9 | 782 |
| 95 | 18.9 | 1,030 |
| 120 | 21.0 | 1,274 |
| 150 | 23.0 | 1,550 |
| 185 | 25.5 | 1,951 |
| 240 | 29.0 | 2,543 |
| 300 | 31.5 | 3,080 |
| 400 | 35.0 | 3,935 |
| 500 | 39.5 | 5,025 |
| 630 | 44.0 | 6,526 |
| 800 | 49.0 | 8,181 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 12.1 | 15.429 | 0.478 | 0.524 | 25 | 33 | 26 | 33 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.441 | 0.487 | 34 | 43 | 35 | 43 | 0.36 |
| 4 | 4.61 | 5.878 | 0.409 | 0.455 | 45 | 56 | 46 | 55 | 0.57 |
| 6 | 3.08 | 3.927 | 0.387 | 0.433 | 57 | 69 | 58 | 68 | 0.86 |
| 10 | 1.83 | 2.333 | 0.356 | 0.402 | 78 | 92 | 80 | 91 | 1.43 |
| 16 | 1.15 | 1.466 | 0.333 | 0.379 | 104 | 118 | 107 | 117 | 2.29 |
| 25 | 0.727 | 0.927 | 0.317 | 0.363 | 141 | 152 | 145 | 151 | 3.58 |
| 35 | 0.524 | 0.668 | 0.303 | 0.349 | 173 | 182 | 178 | 180 | 5.01 |
| 50 | 0.387 | 0.494 | 0.290 | 0.336 | 213 | 216 | 220 | 214 | 7.15 |
| 70 | 0.268 | 0.342 | 0.280 | 0.326 | 271 | 265 | 279 | 261 | 10.01 |
| 95 | 0.193 | 0.247 | 0.272 | 0.318 | 335 | 316 | 346 | 312 | 13.59 |
| 120 | 0.153 | 0.196 | 0.268 | 0.314 | 392 | 359 | 404 | 355 | 17.16 |
| 150 | 0.124 | 0.160 | 0.267 | 0.313 | 451 | 403 | 466 | 397 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.265 | 0.311 | 526 | 455 | 543 | 449 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.260 | 0.306 | 630 | 527 | 650 | 519 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.255 | 0.301 | 728 | 593 | 751 | 584 | 42.90 |
| 400 | 0.0470 | 0.064 | 0.254 | 0.300 | 848 | 671 | 875 | 660 | 57.20 |
| 500 | 0.0366 | 0.052 | 0.251 | 0.297 | 985 | 757 | 1018 | 744 | 71.50 |
| 630 | 0.0283 | 0.043 | 0.247 | 0.293 | 1141 | 849 | 1179 | 834 | 90.09 |
| 800 | 0.0221 | 0.036 | 0.244 | 0.291 | 1295 | 937 | 1339 | 921 | 114.40 |
FIRE RESISTANT CABLES — tabel lanjutan (2)
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 14.5 | 255 |
| 2.5 | 15.5 | 301 |
| 4 | 16.6 | 363 |
| 6 | 18.0 | 441 |
| 10 | 19.9 | 582 |
| 16 | 22.0 | 758 |
| 25 | 25.0 | 1,050 |
| 35 | 27.5 | 1,324 |
| 50 | 30.0 | 1,626 |
| 70 | 34.5 | 2,248 |
| 95 | 38.0 | 2,873 |
| 120 | 41.5 | 3,486 |
| 150 | 46.5 | 4,337 |
| 185 | 51.0 | 5,256 |
| 240 | 56.5 | 6,644 |
| 300 | 62.5 | 8,207 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.315 | 29 | 34 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.293 | 38 | 44 | 0.36 |
| 4 | 4.61 | 5.878 | 0.275 | 50 | 58 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 64 | 73 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 88 | 98 | 1.43 |
| 16 | 1.15 | 1.466 | 0.238 | 116 | 128 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 154 | 165 | 3.58 |
| 35 | 0.524 | 0.668 | 0.233 | 190 | 199 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 230 | 236 | 7.15 |
| 70 | 0.268 | 0.342 | 0.229 | 292 | 292 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 356 | 348 | 13.59 |
| 120 | 0.153 | 0.196 | 0.223 | 414 | 397 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 474 | 445 | 21.45 |
| 185 | 0.0991 | 0.128 | 0.225 | 544 | 502 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 644 | 582 | 34.32 |
| 300 | 0.0601 | 0.080 | 0.221 | 737 | 654 | 42.90 |
FIRE RESISTANT CABLES — tabel lanjutan (3)
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 15.2 | 282 |
| 2.5 | 16.2 | 338 |
| 4 | 17.4 | 415 |
| 6 | 18.9 | 511 |
| 10 | 21.0 | 689 |
| 16 | 23.5 | 915 |
| 25 | 26.5 | 1,289 |
| 35 | 29.0 | 1,646 |
| 50 | 32.0 | 2,039 |
| 70 | 37.0 | 2,828 |
| 95 | 40.5 | 3,682 |
| 120 | 44.5 | 4,496 |
| 150 | 50.0 | 5,575 |
| 185 | 54.5 | 6,814 |
| 240 | 61.0 | 8,794 |
| 300 | 66.5 | 10,755 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.315 | 21 | 28 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.293 | 32 | 37 | 0.36 |
| 4 | 4.61 | 5.878 | 0.275 | 43 | 49 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 54 | 61 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 74 | 83 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 99 | 107 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 131 | 139 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 162 | 167 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 200 | 203 | 7.15 |
| 70 | 0.268 | 0.343 | 0.229 | 252 | 248 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 309 | 298 | 13.59 |
| 120 | 0.153 | 0.197 | 0.223 | 359 | 339 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 411 | 379 | 21.45 |
| 185 | 0.0991 | 0.129 | 0.225 | 475 | 430 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 562 | 497 | 34.32 |
| 300 | 0.0601 | 0.081 | 0.221 | 645 | 560 | 42.90 |
FIRE RESISTANT CABLES — tabel lanjutan (4)
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 1.5 | 16.3 | 323 |
| 2.5 | 17.5 | 392 |
| 4 | 18.8 | 488 |
| 6 | 20.5 | 606 |
| 10 | 23.0 | 839 |
| 16 | 25.5 | 1,125 |
| 25 | 29.0 | 1,602 |
| 35 | 32.0 | 2,073 |
| 50 | 36.0 | 2,628 |
| 70 | 41.0 | 3,586 |
| 95 | 44.5 | 4,700 |
| 120 | 50.0 | 5,848 |
| 150 | 55.5 | 7,148 |
| 185 | 61.0 | 8,849 |
| 240 | 67.5 | 11,313 |
| 300 | 74.0 | 13,867 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 1.5 | 12.1 | 15.429 | 0.315 | 27 | 31 | 0.21 |
| 2.5 | 7.41 | 9.449 | 0.293 | 35 | 41 | 0.36 |
| 4 | 4.61 | 5.878 | 0.275 | 47 | 53 | 0.57 |
| 6 | 3.08 | 3.927 | 0.263 | 59 | 67 | 0.86 |
| 10 | 1.83 | 2.334 | 0.248 | 81 | 89 | 1.43 |
| 16 | 1.15 | 1.467 | 0.238 | 108 | 116 | 2.29 |
| 25 | 0.727 | 0.927 | 0.240 | 146 | 151 | 3.58 |
| 35 | 0.524 | 0.669 | 0.233 | 180 | 181 | 5.01 |
| 50 | 0.387 | 0.494 | 0.232 | 212 | 208 | 7.15 |
| 70 | 0.268 | 0.343 | 0.229 | 265 | 254 | 10.01 |
| 95 | 0.193 | 0.247 | 0.224 | 327 | 305 | 13.59 |
| 120 | 0.153 | 0.197 | 0.223 | 379 | 347 | 17.16 |
| 150 | 0.124 | 0.160 | 0.224 | 442 | 392 | 21.45 |
| 185 | 0.0991 | 0.129 | 0.225 | 504 | 441 | 26.46 |
| 240 | 0.0754 | 0.099 | 0.223 | 597 | 511 | 34.32 |
| 300 | 0.0601 | 0.081 | 0.221 | 685 | 576 | 42.90 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.