NA2XY
Al / XLPE / PVC Deskripsi
Aluminium Conductor, XLPE Insulated, PVC Sheathed
Aplikasi
- Power cable Indoors, cable trunking, outdoors and burried in the ground, for power stations, industry and switchgear as well as for urban supply networks, if mechanical damage is unlikely
Konstruksi Kabel
Pelajari kode penamaan kabel →Susunan lapisan NA2XY dari dalam ke luar — sesuai kode konstruksi Al / XLPE / PVC.
- 1
Konduktor aluminium
Aluminium conductorPenghantar arus utama — aluminium, lebih ringan dengan konduktivitas per berat yang baik.
- 2
Isolasi XLPE
Cross-linked polyethyleneIsolasi utama — suhu kerja 90 °C, kuat dielektrik tinggi, kapasitas hantar lebih besar dari PVC.
- 3
Selubung luar PVC
Polyvinyl chlorideSelubung terluar — proteksi terhadap lingkungan, kelembapan, dan abrasi.
Datasheet Resmi KMI
Unduh lembar data pabrik (PDF) untuk NA2XY.
Spesifikasi Teknis
NA2XY 1 x (10-800) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 8.5 | 84 |
| 16 | 9.7 | 113 |
| 25 | 11.3 | 156 |
| 35 | 12.5 | 196 |
| 50 | 14.1 | 257 |
| 70 | 16.2 | 335 |
| 95 | 18.1 | 425 |
| 120 | 19.6 | 500 |
| 150 | 22.5 | 639 |
| 185 | 25.0 | 783 |
| 240 | 28.0 | 1,008 |
| 300 | 30.5 | 1,208 |
| 400 | 36.0 | 1,696 |
| 500 | 39.0 | 1,982 |
| 630 | 43.5 | 2,473 |
| 800 | 48.0 | 3,037 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 10 | 3.08 | 3.949 | 0.336 | 0.382 | 60 | 71 | 62 | 70 | 0.94 |
| 16 | 1.91 | 2.449 | 0.311 | 0.357 | 81 | 92 | 84 | 91 | 1.50 |
| 25 | 1.20 | 1.539 | 0.302 | 0.348 | 109 | 118 | 112 | 117 | 2.35 |
| 35 | 0.868 | 1.113 | 0.289 | 0.335 | 134 | 142 | 138 | 140 | 3.29 |
| 50 | 0.641 | 0.822 | 0.279 | 0.325 | 165 | 168 | 170 | 166 | 4.70 |
| 70 | 0.443 | 0.568 | 0.269 | 0.316 | 211 | 206 | 218 | 203 | 6.58 |
| 95 | 0.320 | 0.411 | 0.263 | 0.309 | 260 | 245 | 269 | 242 | 8.93 |
| 120 | 0.253 | 0.325 | 0.260 | 0.306 | 303 | 279 | 312 | 275 | 11.28 |
| 150 | 0.206 | 0.265 | 0.258 | 0.304 | 353 | 313 | 364 | 309 | 14.10 |
| 185 | 0.164 | 0.212 | 0.258 | 0.304 | 411 | 355 | 424 | 350 | 17.39 |
| 240 | 0.125 | 0.162 | 0.253 | 0.299 | 494 | 412 | 510 | 406 | 22.56 |
| 300 | 0.100 | 0.130 | 0.249 | 0.295 | 571 | 465 | 590 | 458 | 28.20 |
| 400 | 0.0778 | 0.103 | 0.245 | 0.292 | 688 | 536 | 711 | 528 | 37.60 |
| 500 | 0.0605 | 0.081 | 0.245 | 0.291 | 796 | 609 | 823 | 599 | 47.00 |
| 630 | 0.0469 | 0.065 | 0.243 | 0.289 | 932 | 692 | 963 | 680 | 59.22 |
| 800 | 0.0367 | 0.053 | 0.241 | 0.287 | 1074 | 778 | 1111 | 764 | 75.20 |
NA2XY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 17.2 | 347 |
| 16 | 19.7 | 460 |
| 25 | 22.0 | 587 |
| 35 | 24.5 | 734 |
| 50 | 27.5 | 836 |
| 70 | 31.5 | 1,092 |
| 95 | 35.5 | 1,433 |
| 120 | 39.0 | 1,734 |
| 150 | 42.5 | 2,040 |
| 185 | 48.5 | 2,595 |
| 240 | 53.5 | 3,211 |
| 300 | 59.0 | 3,943 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 67 | 75 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 91 | 100 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 119 | 128 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 147 | 154 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 179 | 183 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 227 | 226 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 277 | 270 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 322 | 308 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 364 | 344 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 425 | 391 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 501 | 454 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 574 | 511 | 28.20 |
NA2XY 3 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 18.0 | 382 |
| 16 | 21.0 | 510 |
| 25 | 23.5 | 660 |
| 35 | 26.0 | 830 |
| 50 | 28.0 | 828 |
| 70 | 32.5 | 1,126 |
| 95 | 36.0 | 1,422 |
| 120 | 39.0 | 1,716 |
| 150 | 44.0 | 2,113 |
| 185 | 48.5 | 2,577 |
| 240 | 54.5 | 3,279 |
| 300 | 59.0 | 3,963 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 57 | 63 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 77 | 84 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 101 | 107 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 125 | 129 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 155 | 157 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 195 | 193 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 240 | 231 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 279 | 263 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 319 | 294 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 370 | 335 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 439 | 388 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 506 | 439 | 28.20 |
NA2XY 4 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 19.5 | 446 |
| 16 | 23.0 | 601 |
| 25 | 25.5 | 787 |
| 35 | 28.5 | 994 |
| 50 | 32.5 | 1,058 |
| 70 | 36.5 | 1,431 |
| 95 | 40.5 | 1,820 |
| 120 | 45.5 | 2,275 |
| 150 | 51.5 | 2,749 |
| 185 | 56.0 | 3,336 |
| 240 | 62.5 | 4,243 |
| 300 | 68.0 | 5,131 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 63 | 69 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 85 | 90 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 112 | 116 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 139 | 140 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 164 | 162 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 206 | 197 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 253 | 237 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 295 | 269 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 343 | 305 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 393 | 344 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 466 | 399 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 537 | 451 | 28.20 |
NA2XY 5 x (10-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.5 | 521 |
| 16 | 24.5 | 709 |
| 25 | 27.5 | 935 |
| 35 | 31.0 | 1,187 |
| 50 | 36.0 | 1,479 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 65 | 70 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 88 | 92 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 117 | 118 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 144 | 143 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 176 | 168 | 4.70 |
NA2XY 1 x (10-500) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 8.5 | 84 |
| 16 | 9.7 | 113 |
| 25 | 11.3 | 156 |
| 35 | 12.5 | 196 |
| 50 | 14.1 | 257 |
| 70 | 16.2 | 335 |
| 95 | 18.3 | 434 |
| 120 | 19.8 | 509 |
| 150 | 22.5 | 639 |
| 185 | 24.5 | 772 |
| 240 | 28.0 | 1,008 |
| 300 | 30.5 | 1,208 |
| 400 | 36.0 | 1,696 |
| 500 | 39.0 | 1,982 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance Trefoil formation (mH/km) | Flat formation (mH/km) | Current - Carrying Capacity at 30° C * in air Max. (A) | in ground Max. (A) | in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 10 | 3.08 | 3.949 | 0.336 | 0.382 | 60 | 71 | 62 | 72 | 0.94 |
| 16 | 1.91 | 2.449 | 0.311 | 0.357 | 81 | 92 | 84 | 94 | 1.50 |
| 25 | 1.20 | 1.539 | 0.302 | 0.348 | 109 | 118 | 112 | 121 | 2.35 |
| 35 | 0.868 | 1.113 | 0.289 | 0.335 | 134 | 142 | 138 | 145 | 3.29 |
| 50 | 0.641 | 0.822 | 0.279 | 0.325 | 165 | 168 | 170 | 172 | 4.70 |
| 70 | 0.443 | 0.568 | 0.269 | 0.316 | 211 | 206 | 218 | 212 | 6.58 |
| 95 | 0.320 | 0.411 | 0.265 | 0.312 | 261 | 245 | 269 | 253 | 8.93 |
| 120 | 0.253 | 0.325 | 0.262 | 0.308 | 303 | 279 | 313 | 287 | 11.28 |
| 150 | 0.206 | 0.265 | 0.258 | 0.304 | 353 | 313 | 364 | 323 | 14.10 |
| 185 | 0.164 | 0.212 | 0.256 | 0.302 | 410 | 355 | 423 | 366 | 17.39 |
| 240 | 0.125 | 0.162 | 0.253 | 0.299 | 494 | 412 | 510 | 426 | 22.56 |
| 300 | 0.100 | 0.130 | 0.249 | 0.295 | 571 | 465 | 590 | 481 | 28.20 |
| 400 | 0.0778 | 0.103 | 0.245 | 0.292 | 688 | 536 | 711 | 555 | 37.60 |
| 500 | 0.0605 | 0.081 | 0.245 | 0.291 | 796 | 609 | 823 | 631 | 47.00 |
NA2XY 2 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 17.2 | 347 |
| 16 | 19.7 | 460 |
| 25 | 22.0 | 587 |
| 35 | 24.5 | 734 |
| 50 | 27.5 | 836 |
| 70 | 31.5 | 1,092 |
| 95 | 35.5 | 1,433 |
| 120 | 39.0 | 1,734 |
| 150 | 42.5 | 2,040 |
| 185 | 48.5 | 2,595 |
| 240 | 53.5 | 3,211 |
| 300 | 59.0 | 3,943 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 61 | 72 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 88 | 99 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 119 | 130 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 145 | 157 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 175 | 185 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 220 | 229 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 272 | 276 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 317 | 320 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 362 | 351 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 420 | 400 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 497 | 467 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 577 | 532 | 28.20 |
NA2XY 3 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 18.0 | 382 |
| 16 | 21.0 | 510 |
| 25 | 23.5 | 660 |
| 35 | 26.0 | 830 |
| 50 | 28.0 | 828 |
| 70 | 32.5 | 1,126 |
| 95 | 36.0 | 1,422 |
| 120 | 39.0 | 1,716 |
| 150 | 44.0 | 2,113 |
| 185 | 48.5 | 2,577 |
| 240 | 54.5 | 3,279 |
| 300 | 59.0 | 3,963 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 52 | 60 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 75 | 84 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 100 | 110 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 123 | 132 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 149 | 156 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 189 | 193 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 233 | 232 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 271 | 268 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 310 | 296 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 359 | 336 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 429 | 429 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 496 | 447 | 28.20 |
NA2XY 4 x (10-300) mm² 0.6/1 kV
| Nom. Cross Section Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 19.5 | 446 |
| 16 | 23.0 | 601 |
| 25 | 25.5 | 787 |
| 35 | 28.5 | 994 |
| 50 | 32.5 | 1,058 |
| 70 | 36.5 | 1,431 |
| 95 | 40.5 | 1,820 |
| 120 | 45.5 | 2,275 |
| 150 | 51.5 | 2,749 |
| 185 | 56.0 | 3,336 |
| 240 | 62.5 | 4,243 |
| 300 | 68.0 | 5,131 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 52 | 60 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 75 | 84 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 110 | 110 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 123 | 132 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 149 | 156 | 4.70 |
| 70 | 0.443 | 0.568 | 0.229 | 189 | 193 | 6.58 |
| 95 | 0.320 | 0.411 | 0.224 | 233 | 232 | 8.93 |
| 120 | 0.253 | 0.325 | 0.223 | 271 | 268 | 11.28 |
| 150 | 0.206 | 0.265 | 0.225 | 310 | 296 | 14.10 |
| 185 | 0.164 | 0.211 | 0.225 | 359 | 336 | 17.39 |
| 240 | 0.125 | 0.162 | 0.223 | 429 | 393 | 22.56 |
| 300 | 0.100 | 0.130 | 0.222 | 496 | 447 | 28.20 |
NA2XY 5 x (10-50) mm² 0.6/1 kV
| om. ross ection Area | Overall Diameter approx. | Cable Weight approx. |
|---|---|---|
| mm² | mm | kg/km |
| 10 | 21.5 | 521 |
| 16 | 24.5 | 709 |
| 25 | 27.5 | 935 |
| 35 | 31.0 | 1,187 |
| 50 | 36.0 | 1,479 |
| Conductor Nom. Cross Sect. (mm²) | DC Resistance at 20°C Max. (Ω/km) | AC Resistance at 90°C Max. (Ω/km) | Inductance | Current - Carrying Capacity at 30°C * in air Max. (A) | in ground Max. (A) | Short circuit current at 1 sec Max. (kA) |
|---|---|---|---|---|---|---|
| (mH/km) | ||||||
| 10 | 3.08 | 3.949 | 0.248 | 52 | 60 | 0.94 |
| 16 | 1.91 | 2.449 | 0.236 | 75 | 84 | 1.50 |
| 25 | 1.20 | 1.539 | 0.242 | 100 | 110 | 2.35 |
| 35 | 0.868 | 1.113 | 0.234 | 123 | 132 | 3.29 |
| 50 | 0.641 | 0.822 | 0.232 | 144 | 156 | 4.70 |
Data spesifikasi bersumber dari katalog resmi pabrik Kabelmetal Indonesia (KMI). Nilai bersifat nominal/perkiraan dan dapat berubah tanpa pemberitahuan. Hubungi kami untuk konfirmasi teknis terkini.